The clearances listed below are Minimum distances unless otherwise stated:
A major cause of fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
fi replace be installed only in accordance with these instructions.
Caution Requirements
The top, back and sides of the fi replace are defi ned by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
Clearance:
A: Sidewall
B: Ceiling
C: Mantel Height (min.)
D: Mantel Depth (max.)
E: Alcove Width
F: Alcove Depth
Notes:
B
D
C
Regency Horizon™ HZO42 Gas Fireplace
MINIMUM CLEARANCES TO COMBUSTIBLES
HZO42 Clearance Requirements
Dimension
Measured From:
11" (203mm)
Side of Fireplace Opening
36" (914mm)
Top of Fireplace Opening
18" (457mm)
Top of Fireplace Opening
12" (304mm)
From Wall
57"(1148mm)
Wall to Wall (Minimum)
36" (914mm)
Front to Back Wall (Maximum)
0"
No Hearth Required
F
A
E
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fi replace be
installed only in accordance with these instructions.
WARNING:
When installing this appliance; do not cover or surround
with insulation.
This appliance can overheat and cause malfunction
and component failure, if covered, or partially covered.
If the appliance is installed inside a chase, insulation
must be installed on the walls of the chase, not on the
appliance.
B
F
Alcove
INSTALLATION
A
E
9