Download Print this page

Emerson Carbon Dioxide Sensor Product Information Sheet

Carbon dioxide sensor

Advertisement

Quick Links

Overview
CPC's CO
sensor (P/N 210-2000) is a non-dispersive
2
infrared
analyzer
designed
environmental CO
concentration in ventilation
2
systems and indoor spaces. Its measurement range of
0-2000 or 0-5000 ppm covers the range required to
monitor compliance with ASHRAE and other
ventilation efficiency standards.
An LCD display is available to provide local indication
of CO
concentration and facilitate the setup and
2
calibration process. An adjustable setpoint relay is
available for direct control and alarm applications.
Microprocessor-based digital electronics and a
unique self-calibration algorithm improves long-term
stability and accuracy
Mounting
Before mounting, remove the door from the circuit
board by pressing a screwdriver against the locking
tab on the top of the enclosure. Pry the circuit board
Figure 1 - CO
Sensor (exploded view)
2
Carbon Dioxide Sensor
Carbon Dioxide Sensor
Product Information Sheet
Product Information Sheet
for
measuring
40
away from the mounting plate using a screwdriver
inserted into the two tab slots on the top of the
enclosure.
Choose a location for the sensor with good air
circulation, away from ventilation inlets, doors,
windows, or other points where fresh air enters the
room. The sensor should be mounted at least 4-1/2
feet above the floor. The environment temperature
must be within 32°–112°F (0°–50°C).
If wiring will be coming in through the mounting
plate from the back, punch out openings in the
mounting plate and use the plate as a template for
locating holes. Mount the mounting plate against a
wall or other flat surface by using the two mounting
holes and the screws provided (use wall anchors for
drywall installations).
NOTE: Sensors must be mounted vertically (straight
up and down) to ensure proper readings.
210-2000

Advertisement

loading

Summary of Contents for Emerson Carbon Dioxide Sensor

  • Page 1 Carbon Dioxide Sensor Carbon Dioxide Sensor 210-2000 Product Information Sheet Product Information Sheet Overview CPC’s CO sensor (P/N 210-2000) is a non-dispersive away from the mounting plate using a screwdriver infrared analyzer designed measuring inserted into the two tab slots on the top of the environmental CO concentration in ventilation enclosure.
  • Page 2: Power Wiring

    Carbon Dioxide Sensor 210-2000 Product Information Sheet Wiring middle (COMMON) terminal of this connector, and either the N.C. or N.O. terminal, depending on The mounting plate has two sets of three-terminal whether you want the relay to be OPEN or CLOSED connectors.
  • Page 3 Carbon Dioxide Sensor 210-2000 Product Information Sheet Figure 4 - CO2 Sensor Keys and Screens Setpoint Figure 3 - CO Sensor Reassembly If you are using the CO sensor’s relay for alarming or control, use the + and - keys to adjust the value of the set point.
  • Page 4 Emerson Climate Technologies logos are trademarks and service marks of Emerson Electric Co. Intelligent Store is a trademark of Emerson Climate Technologies. All other trademarks are the property of their respective owners. © 2011 Emerson Climate Technologies, Inc. All rights reserved.

This manual is also suitable for: