SYSTEM
In column four of this menu, the selections in
procedures; related instructions are displayed on the LOI. All other parameters are display only.
Figure 6-4. Menu Tree for Local Operator Interface (LOI) on the Oxymitter 4000 (Sheet 2 of 2)
6-6

OXYMITTER 4000 SETUP AT THE LOI

In setting up the Oxymitter 4000 from the LOI,
it's best to start at the SYSTEM/Calibration
Setup menu, Figure 6-4.
a. SYSTEM/Calibration Setup
1. O2 Gas #1 – Enter the high or low cal
gas value (the order is not important).
2. O2 Gas #2 – Enter the second cal gas
value.
Refer to Section 9, MAINTENANCE AND
SERVICE, for calibration instructions.
6-4
Startup and Operation with LOI
Calib Setup
Input/Output
Parameters
Software
Status
NOTE
O2 Gas 1
O2 Gas 2
O2-Reset Vals
O2
O2 Cal Intervl
O2-
Gas Time
Purge Time
Auto Calib?
O2 Type
Analog
O2 Range
O2 Alarm Leve
Do O2 Trim
Logic IO Mode
Low
Input State
Digital
Force Output
O2 Slope
O2 Constant
O2 T90 Time
Auto Tune?
Lockout Time
Revert Time
Luminance
Version
Checksum
Build Number
Build Date
Test Code
SW Err File
SW Err Line
Alarms
PID Parameters
Reset Device?
(Cal. required after reset)
NOTE
Italics
are user configurable.
Bold
Rosemount Analytical recommends
0.4% O
and 8% O
2
3. O2 – Reset Values- resets factory de-
fault values.
4. O2 Output Tracks – 4 to 20 mA signal
can be held at the last value during
calibration, or the signal can be left to
track the cal gases.
5. O2 Cal Interval – If automatic calibra-
tion is selected, this selects the interval
between calibrations.
Rosemount Analytical Inc.
Oxymitter 4000
_____%
_____%
Yes/No
Out Tracks
Yes/No
____H
Next Cal
____H
___Sec.
___Sec.
Yes/No
_______
______%
l
_____mA
See Table 4-1
O2 Alarm
See para. 9-3b
_______
_______
____ mV/D
____ mV
0:00
Yes/No
0:00
0:00
______
xxx
xxx
xxx
xxxxxx
xx
xx
xx
__________
115/220
Yes/No
text selections are
37260018
NOTE
for calibration gases.
2
A Division of Emerson Process Management