Control Cable And Communications; Figure 2 External Interface Board Connections Layout - Emerson Liebert NXL 250 Installation Manual

250-400kva, 60hz, three phase single-module
Hide thumbs Also See for Liebert NXL 250:
Table of Contents

Advertisement

Bottom Cable Entry
When making the power connections for bottom cable entry, the recommended order of pull-
ing and installing cables is to start from the bottom connections to the top connections. The
cables must be routed around the fault braces (see Detail in Figure 9). This is to prevent the
cables from contacting other busbars. The recommended conduit layout is shown in Figure 7.
NOTE
For a Single Input configuration, linking busbars must be installed between the bypass and
the rectifier input.
WARNING
!
Risk of electrical shock. Can cause injury or death.
If the load equipment will not be ready to accept power on the arrival of the commissioning
engineer, ensure that the system output cables are safely isolated at their termination.
WARNING
!
Risk of electrical shock. Can cause injury or death.
When connecting the cables between the battery extremities to the circuit breaker always
connect the circuit breaker end of the cable first.
5. For control connection details, see 2.3 - Control Cable and Communications.
NOTE
If fault bracing brackets were removed during installation, they MUST be replaced.
6. Close and secure the interior and exterior doors.
2.3

Control Cable and Communications

Based on your site's specific needs, the UPS may require auxiliary connections to manage the battery
system (external battery circuit breaker), communicate with a personal computer or provide alarm
signaling to external devices or for Remote Emergency Power Off (REPO). The External Interface
Board, arranged for this purpose, is on the rear of the operator access door.
Figure 2
External Interface Board connections layout
EPO
STATUS
TB0823
TB0826
LBS
VOLTAGE
EXTERNAL
BATT
MTR OPT
TB0821
TB0829
EXT BATT
INT BATT
CAN
CAN
CAN
TB0825
REPO
LEPO
TB0824
REPO
FORM C
8
UPS Electrical Installation
MAINT BYP
ACT FILT
ENABLE
CNTL
TEMP 1
TEMP 2
BATT GND FLT
MOB
TB0811
ACT FILT
MIB
STATUS
TB0810
TB0816
ON GEN
RIB IN
TB0813
BYP
MBB
CNTRL
TB0812
RECT
BIB
CNTRL
TB0820
KEY
INV
STATUS
CNTRL