Figure 12 Outline drawing, 400kVA Liebert NXL UPS
25.8
(655)
3.7
10.6
(95)
( 269)
32.9
(835)
69.5
(1766)
NOTES:
1. All dimensions are in inches (mm).
2. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate conduits.
7. Aluminum and copper-clad aluminum cables are not recommended.
8. Widths are with side panels. the width is 76.7" (1948mm) without side panels.
9. The depth dimension includes the front door and rear panel.
78.5
( 1995)
29.5
( 749)
FRONT
12.4
12.4
10.6
( 316)
( 316)
( 269)
3.1
( 80 )
TYP
BOTTOM VIEW
TOP VIEW
39.4
( 1000)
RIGHT SIDE VIEW
FRONT
ACCESS
PLATE
A
DETAIL A
B
ACCESS
PLATE
21
Installation Drawings
76.8
(1950)
14.5
( 368)
CONDUIT
LANDING
AREA
(NOTE 4)
CONDUIT
LANDING
AREA
(NOTE4)
DETAIL B