"B" Function
Func.
Name /
Code
SRW Display
B_01 Selection of restart
mode
IPS POWR
B_02 Allowable under-
voltage power failure
time
IPS UVTIME 01.0s
B_03 Retry wait time before
motor restart
IPS WAIT
001.0s
Description
Select inverter restart method,
four option codes:
00 ...Alarm output after trip,
ALM
no automatic restart
01 ...Restart at 0Hz
02 ...Resume operation after
frequency matching
03 ...Resume previous freq.
after freq. matching, then
decelerate to stop and display
trip info.
The amount of time a power
input under-voltage can occur
without tripping the power
failure alarm. Range is 0.3 to
25 sec. If under-voltage exists
longer than this time, the
inverter trips, even if the restart
mode is selected.
Time delay after under-voltage
condition goes away, before
the inverter runs motor again.
Range is 0.3 to 100 seconds.
L100 Inverter
Defaults
Run
Mode
–FE
–FU
–FR
Edit
(CE)
(UL)
(Jpn)
00
00
1.0
1.0
1.0
1.0
3–23
Units
00
1.0
sec.
1.0
sec.