Terminal Tightening Torque and Wire Size
The wire size range and tightening torque for field wiring terminals are presented in the
table below.
Motor Output
Input
Voltage
kW
0.2
0.4
0.55
0.75
1.1
200V
1.5
2.2
3.7
5.5
7.5
0.4
0.75
1.5
2.2
400V
3.0
4.0
5.5
7.5
Wire Connectors
WARNING: Field wiring connections must be
made by a UL Listed and CSA Certified ring lug
terminal connector sized for the wire gauge being
used. The connector must be fixed using the
crimping tool specified by the connector
manufacturer.
Inverter Model
HP
1/4
L100-002NFE/NFU
1/2
L100-004NFE/NFU
3/4
L100-005NFE
1
L100-007NFE/NFU
1 1/2
L100-011NFE
2
L100-015NFE/NFU
3
L100-022NFE/NFU
5
L100-037LFU
7 1/2
L100-055LFU
10
L100-075LFU
1/2
L100-004HFE/HFU
1
L100-007HFE/HFU
2
L100-015HFE/HFU
3
L100-022HFE/HFU
4
L100-030HFE
5
L100-040HFE/HFU
7 1/2
L100-055HFE/HFU
10
L100-075HFE/HFU
L100 Inverter
Wiring Size
Range (AWG)
ft-lbs
0.6
16
14
0.9
12
10
12
10
1.5
8
16
0.9
14
12
1.5
Terminal (ring lug)
Cable support
xiii
Torque
(N-m)
0.8
1.2
2.0
1.2
2.0
Cable