SUBJECT: OVERVOLTAGE & UNDERVOLTAGE TRIP LEVELS
APPLICABLE MODELS: L100 INVERTERS, 400 V CLASS
The following are the ranges of OV an UV trip levels for the L100 inverter.
Variation is due to normal component tolerances:
OV:
767 VDC to 848 VDC
UV:
354 VDC to 393 VDC
PGC - 2/8/02