Output Deviation For Pid Control - Hitachi L100 Series Instruction Manual

Hide thumbs Also See for L100 Series:
Table of Contents

Advertisement

4–26
Using Intelligent Output Terminals

Output Deviation for PID Control

The PID loop error is defined as the
magnitude (absolute value) of the differ-
ence between the Setpoint (target value)
and the Process Variable (actual value).
When the error magnitude exceeds the
preset value for C_44, the [OD] terminal
signal turns ON. Refer to
Operation" on page
Option
Terminal
Code
Symbol
04
OD
Valid for outputs:
Required settings:
Notes:
The default difference value is set to 3%. To change
this value, change parameter C_44 (deviation
level).
NOTE: The example circuit in the table above drives a relay coil. Note the use of a
diode to prevent the negative-going turn-off spike generated by the coil from damaging
the inverter's output transistor.
"PID Loop
4–32.
Output
Function Name
State
Output Deviation for
ON
PID Control
OFF
11, 12
C_44
SP, PV
C 44
C 44
[OD]
1
ON
0
Signal
Description
when PID error is more than the set threshold for
the deviation signal
when PID error is less than the set threshold for
the deviation signal
Example (requires output configuration—
see page 3–36):
Inverter output
terminal circuit
H O OI
L
See I/O specs on page 4–6.
Process variable
Setpoint
ON
t
OD
FM CM2
12 11
+
RY

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents