4–28
Using Intelligent Output Terminals
The alarm output terminals are connected as shown below (left) by default. The contact
logic can be inverted as shown (below right) by using the parameter setting C_33. The
relay contacts normally open (N.O.) and normally closed (N.O.) convention uses
"normal" to mean the inverter has power and is in Run or Stop Mode. The relay contacts
switch to the opposite position when it is in Trip Mode or when input power is OFF.
N.C. contacts (after initialization)
During normal running
AL0
AL1
AL2
Contact
Power
N.C.
ON
(after
ON
initialize,
C_33=01)
OFF
When an alarm occurs
or power is turned OFF
AL0
AL1
AL2
Run
AL0-
AL0-
State
AL1
AL2
Normal Closed
Open
Trip
Open
Closed
Open
Closed
N.O. contact (inverted by C_33 setting)
During normal running
or power is turned OFF
AL0
AL1
AL2
Run
Contact
Power
State
N.O.
ON
Normal
(set
ON
Trip
C_33=00)
OFF
When an alarm occurs
AL0
AL1
AL2
AL0-
AL0-
AL1
AL2
Open
Closed
Closed
Open
Open
Closed