2.6.6 Digital Communicator and Annunciators

2.6.6.1 UDACT-F Digital Alarm Communicator/Transmitter

The UDACT-F transmits system status to UL listed Central Station receivers via the
public switched telephone network. It is capable of reporting up to 99 software
zones or up to 636 addressable points. The UDACT-F can be mounted remotely in
a UBS-1F or ABS-8RF enclosure or in the panel cabinet using the P/N: BRKT-9600
Universal Bracket. For additional information, refer to the UDACT-F Manual.
Programming
The MS-9600 must be programmed to operate with the UDACT-F. Refer to
"Annunciators/UDACT" on page 97 for control panel programming information.

2.6.6.2 ACM-8RF Relay Control Module

The ACM-8RF module provides eight Form-C relays with contacts rated for 5
amps. When installed with an MS-9600 FACP, the ACM-8RF modules provide
relay activation for each of the 99 possible FACP zones plus special functions.
Options exist to allow for alarm only or alarm and trouble activation per zone.
Output activation for general alarm, general trouble, general supervisory, NAC
fault, AC fail, walktest start and battery trouble are also available. The ACM-8RF
can be mounted remotely in an ABS-8RF annunciator surface-mount backbox or in
the panel cabinet using the P/N: BRKT-9600 Universal Bracket. Refer to the
ACM-8RF manual for information on setting module switches for addressing and
relay functions.

2.6.6.3 BRKT-9600 Universal Bracket Installation

The optional BRKT-9600 Universal Bracket can be used to mount specific modules
inside the MS-9600 cabinet. The BRKT-9600 mounts to two studs located in the
lower right corner of the control panel cabinet as illustrated below. It is secured to
the PEM studs on the back wall of the cabinet with two supplied hex nuts.
IMPORTANT! When the BRKT-9600 is installed, the MS-9600 cabinet can hold a
maximum of two 12 Amp Hour batteries with the orientation illustrated below.
TB3
JP3
REMOVE
TO DISABLE
LOCAL
CHARGER
JP10
JP2
1
2
DISABLE
GND
FLT
4
5
GHI
J17
J16
7
8
PRS
0
*
QZ
RECALL
CB1
HOT
MS-9600 Cabinet
Figure 2.19 BRKT-9600 Bracket Installation
TB5
TB4
TB6
TB7
JP5
4XTM OPT BD
JP11
AC POWER
M AINTENANCE
ALARM
FIRE ALARM
SILENCED
SUPERVISORY
DISABLED
TROUBLE
BATTERY
GROUND
ACK/STEP
3
JP8
1
st
JP7
J2
ABC
DEF
EVENT
ALARM
SILENCE
6
CLR
OPT DACT
CUT TO
ENTER
JKL
MONITOR 4XTM
MNO
JP6
ESC
DRILL
9
J8
J6
JP4
TUV
WXY
HOLD 2 SEC
1
LCD DISPLAY
2
#
MODE
KEYPAD I/F
RESET
3
TB1
TB2
-/.
J12
J7
NEUT EARTH
+BATTERY-
Optional Modules and Devices
TB8
OPT SLC
Mount BRKT-9600 to PEM
J3
studs on back of cabinet
using supplied hex nuts.
MS-9600 PN 51335:E 7/9/03

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9600e

Table of Contents