Specifications - Fire-Lite MS-2 Instruction Manual

Fire alarm control panel
Hide thumbs Also See for MS-2:
Table of Contents

Advertisement

Specifications

Zone Enable/Disable (one per zone)
LED Indicators
Fire Alarm (one per zone)
Supervisory (one per zone)
Trouble (one per zone)
Maintenance (one per zone)
AC Power
NAC Disable
Zone Disable
NAC Fault
System Trouble
Power Trouble
Walktest
Alarm Silence
Earth Fault LED (on circuit board) lights if zero impedance between FACP and ground exist
Battery Fault (on circuit board)
Charger Fault (on circuit board)
Piezo sounder for alarm, trouble and supervisory
24 volt operation
Low AC voltage sense
Alarm Verification
NACs Programmable for:
Silence Inhibit
Auto-Silence
Strobe Synchronization
Selective Silence (horn-strobe mute)
Temporal or Steady Signal
Silenceable or Nonsilenceable
Automatic battery trickle charger
Silent or audible walktest capabilities
Optional NAC Class A converter module (MS-4 only)
Optional 4XTMF Transmitter Module (MS-2 and MS-4)
Optional 4XZMF Zone Relay Module (MS-4 only)
Optional 4XLMF Module for RZA-4XF Remote LED Annunciator (MS-4 only)
1.2 Specifications
AC Power - TB8
MS-2/MS-4: 120 VAC, 50/60 Hz, 2.3 amps
MS-2E/MS-4E: 240 VAC, 50 Hz, 1.15 amps
Wire size: minimum #14 AWG (2.0 mm
Battery (sealed lead acid only) - J8
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 0.8 amp
Maximum Charger Capacity: 18 Amp Hour battery (two 7 Amp Hour batteries can be housed in the
FACP cabinet. Larger batteries require a separate battery box such as the BB-17F.)
MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011
) with 600V insulation