Power connection

The AC power input for the P9500 disk array has a duplex PDU structure. This duplex structure
enables the entire rack to remain powered on if power is removed from one of the two power
distribution panels.
CAUTION:
When installing a system, connect the AC cables between the PDUs and PDPs correctly.
Otherwise, a system failure can occur when one of the AC inputs is interrupted.

AC Power - PDU Options

P9500 is configured for input power using separate rackmount PDU products. PDUs are available
for three phase or single phase power for NEMA and IEC compliance applications.
Table 10 P9500 AC PDU Options
Product
Number
AV404A
AV404AU
AV405A
AV405AU
AV406A
AV406AU
AV407A
AV407AU
Notes
1.
Each PDU has one fixed power cord with attached plug. Power cord is not removable.
18
Installation requirements
Number of
PDU per Rack
Local Power
3 phase (4
2
wire)
3 phase (5
2
wire)
single phase
4
NEMA
single phase
4
IEC
Branch circuit
requirements
1
per PDU
Plug Type
208-240V, 3Ø,
NEMA
4-wire, 30A
L15-30P
380-415V, 3Ø,
IEC60309 4
5-wire, 16A
pole, 5-wire
380-415VAC,
16A
200-240V, 1Ø,
NEMA L6-30P
3-wire, 30A
200-240V, 1Ø,
IEC60309 2
3-wire, 32A
pole, 3-wire,
240VAC, 32A
Facility
receptacle
needed
Notes
NEMA
For customers
L15-30R
with, 208 - 240
VAC, 3-Phase,
4-Wire Power
Distribution
System
IEC60309 4
For customers
pole, 5-wire,
with 380 - 415
380-415 VAC,
VAC,
16A
Three-Phase,
5-Wire Wye
Power
Distribution
System
NEMA L6-30R
For customers
with single
phase power
and need
NEMA L6-30P
plug
IEC60309 2
For customers
pole, 3-wire,
with single
240VAC, 32A
phase power
and need
IEC60309 32A
plug