Table 1 1 P9500 environmental specifications (continued)
Item
Vibration
to 10Hz: 0.25 mm
Earthquake
resistance (m/s2)
Shock
Altitude
Notes:
1.
Recommended temperature range is 21 to 24°C.
2.
On shipping/storage condition, the product should be packed with factory packing.
3.
The above specifications of vibration are applied to all three axes.
4.
See ASTM D999-01 The Methods for Vibration Testing of Shipping Containers.
5.
See ASTM D5277-92 Test Method for Performing Programmed Horizontal Impacts Using an Inclined Impact Tester.
6.
See ASTM D6055-96 Test Methods for Mechanical Handling of Unitized Loads and Large Shipping Cases and
Crates.
7.
Time is 5 seconds or less in case of the testing with device resonance point (6 to 7Hz).

Heat output and air flow

The following table lists the heat output and air flow requirements for the P9500 disk array.
Both the control chassis and the disk chassis contain front and rear fans to circulate air through
the chassis from front to back. Air flows in through the front bezel to the rear of the component
and exits through the perforations in the rear door. Either the front fans or the rear fans can cool
the chassis by themselves. The racks do not contain fans. Airflow is from front to back.
Table 12 Heat, power, and airflow
Model Number
AV400A - HP P9500 Disk
Array DKC Module-0 Rack
AV401A - HP P9500 DKC
Module- 1 Rack
AV402A - HP P9500 DKU
Disk Unit Rack
AV413A - HP P9500 Drive
Chassis SAS Switch Kit
20
Installation requirements
Operating
Not Operating
10 to 300 Hz
5 to 10 Hz: 2.5 mm
1
0.49 m/s
10 to 70 Hz: 4.9 m/s
70 to 99 Hz: 0.05 mm
99 to 300 Hz: 9.8 m/s
7
Up to 2.5
-
-
78.4 m/s
-60 to 3,000m
Heat Output (kW)
1
1.88
1
1.83
1
1.47
0.120
In Storage
Sine Vibration:
1
4.9 m/s
At the resonant frequency with
the highest displacement found
1
between 3 to 100 Hz
Random Vibration:
0.147 m2/s3
30 min, 5 to 100 Hz
-
1
, 15 ms
Horizontal:
Incline Impact 1.22 m/s
5
Vertical:
Rotational Edge 0.15 m
6
-
Power Consumption (kVA)
1
1.97
1
1.93
1
1.54
0.076
1
, 5 min.
3
4
Air Flow (M3/min)
25
25
27
-