Appendix D M320 Router Power Guidelines, Requirements, And Specifications; Site Electrical Wiring Guidelines For M Series, Mx Series, And T Series Routers - Juniper M320 Hardware Manual

Multiservice edge router
Hide thumbs Also See for M320:
Table of Contents

Advertisement

APPENDIX D
M320 Router Power Guidelines,
Requirements, and Specifications

Site Electrical Wiring Guidelines for M Series, MX Series, and T Series Routers

Copyright © 2010, Juniper Networks, Inc.
Site Electrical Wiring Guidelines for M Series, MX Series, and T Series Routers on page 249
M320 Chassis Grounding Cable and Lug Specifications on page 250
M320 Power Requirements on page 250
M320 AC Power Specifications on page 252
M320 DC Power Specifications on page 255
Distance limitations for signaling—Improperly installed wires can emit radio interference.
In addition, the potential for damage from lightning strikes increases if wires exceed
recommended distances or if wires pass between buildings. The electromagnetic pulse
(EMP) caused by lightning can damage unshielded conductors and destroy electronic
devices. If your site has previously experienced such problems, you might want to
consult experts in electrical surge suppression and shielding.
Radio frequency interference—You can reduce or eliminate the emission of radio
frequency interference (RFI) from your site wiring by using twisted-pair cable with a
good distribution of grounding conductors. If you must exceed the recommended
distances, use a high-quality twisted-pair cable with one ground conductor for each
data signal when applicable.
Electromagnetic compatibility—If your site is susceptible to problems with
electromagnetic compatibility (EMC), particularly from lightning or radio transmitters,
you might want to seek expert advice. Strong sources of electromagnetic interference
(EMI) can destroy the signal drivers and receivers in the router and conduct power
surges over the lines into the equipment, resulting in an electrical hazard. It is particularly
important to provide a properly grounded and shielded environment and to use electrical
surge-suppression devices.
CAUTION: To comply with intrabuilding lightning and surge requirements,
intrabuilding wiring must be shielded, and the shield for the wiring must be
grounded at both ends.
249