How It Works / Basic Function; Detection Zone; Presence Control Pro - STEINEL DUAL HF COM 1 Manual

Presence detector
Hide thumbs Also See for DUAL HF COM 1:
Table of Contents

Advertisement

Available languages

Available languages

How it works / Basic function

The high-frequency presence
cy technology guarantees that
detectors from the Control PRO
movement is detected absolute-
range control lighting as well as
ly anywhere irrespective of radi-
heating, ventilation and air-con-
ated temperature. Sensing
ditioning (COM 2 only), e.g. in of-
movement in two directions, the
fices, WCs, public buildings or at
DUAL HF sensor is ideal for corri-
home, in relation to ambient
dors in hotels, schools and office
light level and the presence of
buildings. The presence detec-
persons. Modern, high-frequen-
tor's switching outputs and

Presence Control PRO

Presence Control PRO
HF 360 COM 1 / COM 1 AP
HF 360 COM 2
DUAL HF COM 1 / COM 1 AP
1 switching output, such as
1 switching output operating
COM 1. Plus a 2nd switching
in relation to brightness setting
output for HVAC (heating /
and presence of persons.
ventilation / air conditioning)
governed by presence.
Settings:
- Brightness setting
Settings:
- Stay-'ON' time, pulse mode,
- Stay-'ON' time
IQ mode
- Switch-'ON' delay
- Room surveillance

Detection zone

HF 360 mounting height 2.8 m
The reach of the HF 360 is electronically adjustable.
1 or 2 detection directions can be masked out for
adjustment to the room situation. An angle of cov-
erage of 360° provides a max. reach of 8 m.
reach are set at the potentio-
meters and dip switches or by
means of the optional remote
control. Presence Control has
a low intrinsic power consump-
tion.
Presence Control PRO
HF 360 DIM
DUAL HF DIM
1 switching output operating
in relation to brightness setting
and presence of persons.
Settings:
- Brightness setting
- Stay-'ON' time, IQ mode
- Orientation light
- Constant lighting control
PC PRO DUAL HF mounting height 2.8 m for all
The DUAL HF sensor has 2 special HF sensors that
detect movement from the ceiling in both direc-
tions. Controlled electronically, reach is infinitely
variable in both directions from 3 x 3 m – 10 x 3 m.
- 20 -
Electrical installation/Automatic mode
In selecting the wiring leads, it is
section 6 of VDE 0100 520, a multi-
important to meet the wiring
ple-core lead containing both the
regulations laid down in VDE 0100
mains voltage leads and the con-
(see Safety warnings on page 19).
trol leads (e.g. NYM 5 x 1.52) may
The following applies to wiring
be used for wiring between the
presence detectors: According to
sensor and electronic ballast. The
COM 1
COM 2
L
L
L
N
N
N
P
P S N
COM1
L L'
B1
B2
COM 1 AP
L
N
mains connection lead must be no
greater than 10 mm in diameter.
The clamping range of the mains
terminal is designed for a maxi-
mum of 2 x 1.5 mm
2
DIM
L
L
N
N
P
P S N
DIM
COM2
L L' B1 B2
max. 1 A
1-10V
B1
B2
max. 100 mA
L
N
P
L'
L
S
P
P N
N
- 21 -
or 1 x 2.5 mm
2
.
L
N
P S N
1-10V
L L'
+ –