Download Print this page

About This Document; General Safety Precautions; Mounting Installation; Function And Setting - STEINEL Control PRO Series Quick Start Quide

Advertisement

GB
1� About this document
– Please read carefully and keep in a safe
place.
– Under copyright. Reproduction either in
whole or in part only with our consent.
– Subject to change in the interest of
technical progress.
Symbols
!
Hazard warning!
Reference to other information in
the document�
...
2� General safety precautions
Disconnect the power supply before
!
attempting any work on the sensor�
• During installation, the electric power
cable to be connected must not be live.
Therefore, switch off the power first and use
a voltage tester to make sure the wiring is
off-circuit.
• Installing the sensor involves work on
the mains power supply. This work must
therefore be carried out professionally in
accordance with national wiring regulations
and electrical operating conditions. (e.g.
DE: VDE 0100, AT: ÖVE-EN 1,
CH: SEV 1000 )
3� IR Quattro HD / DUAL HF /
HF 360
Proper use:
– Presence detector for indoor ceiling
mounting
Sensing movement in two directions,
DUAL HF is ideal for corridors in hotels,
schools and office buildings.
HF 360 is ideal for WCs with toilet compart-
ments, changing rooms, stairwells, multi-storey
car parks, kitchens. IR Quattro HD with highly
advanced lens provides a square detection
zone, as the typical shape of a room, in which
the smallest of movements are sensed.
The sensor is connected to the control unit via
a DALI bus. The sensor uses the DALI line for
communication and for supplying power.
Product dimensions for IR Quattro HD
(Fig� 3�1)
Product dimensions for HF 360 (Fig� 3�2)
Product dimensions for DUAL HF (Fig� 3�3)
Detection zone (Fig� 3�4-3�7)
4� Mounting / installation
For wiring up the motion detectors, the
following applies: under section 6 of VDE
0100 520, for example, a multiple-core lead
containing both the mains voltage leads and
the control leads (e.g. NYM 5 × 1.5 mm²) may
be used for the wiring between sensor and
DALI Application Controller. The lead between
DALI Application Controller and sensor must
be no longer than 300 m (with 1.5 mm²). After
installing and switching ON, the sensor starts
to flash once a second.
• Check all components for damage.
• Do not use the product if it is damaged.
• Select an appropriate mounting location,
taking the reach and motion detection into
consideration.
Mounting procedure
Switch OFF power supply (Fig� 4�1)
Mount sensor (Fig� 4�2-4�4)
Connect conductors (Fig� 4�6-4�7)
Switch ON power supply (Fig� 4�8)
8
5� Function and setting
The sensor is put into operation in accordance
with the applicable DALI 2 standard. All func-
tions and commands are available from DALI
standard IEC 62386 Part 101, Part 103, Part
303 and Part 304. The motion detection values
and light levels measured by the sensor can be
requested from the DALI Application Controller.
Automatic or time-based cyclical transmission
can also be selected.
You will find detailed information in the
interface description on the Internet at:
www.DALI-2.steinel.de
LED function:
Blue LED
Initialisation: LED flashes once every 2 seconds
Normal mode: LED stays OFF.
DALI identification: LED flashes once a second.
Adjusting detection reach
IR Quattro HD
Setting detection reach (Fig� 5�1)
IR Quattro HD
Presence
Radial
Tangential
1
3.6 m × 3.6 m
3.6 m × 3.6 m
4 m × 4 m
2
4 m × 4 m
4 m × 4 m
4 m × 4 m
3
4.6 m × 4.6 m
4.6 m × 4.6 m
5 m × 5 m
4
5.2 m × 5.2 m
5.2 m × 5.2 m
6 m × 6 m
5
5.8 m × 5.8 m
5.8 m × 5.8 m
8 m × 8 m
6
6.8 m × 6.8 m
6.8 m × 6.8 m
13 m × 13 m
7
7.8 m × 7.8 m
7.8 m × 7.8 m
18 m × 18 m
1
3.8 m × 3.8 m
3.8 m × 3.8 m
4 m × 4 m
2
4.4 m × 4.4 m
4.4 m × 4.4 m
4.5 m × 4.5 m
3
5.1 m × 5.1 m
5.1 m × 5.1 m
5.5 m × 5.5 m
4
5.5 m × 5.5 m
5.5 m × 5.5 m
6.5 m × 6.5 m
5
5.9 m × 5.9 m
5.9 m × 5.9 m
8.5 m × 8.5 m
6
6.9 m × 6.9 m
6.9 m × 6.9 m
17 m × 17 m
7
7.9 m × 7.9 m
7.9 m × 7.9 m
20 m × 20 m
1
4 m × 4 m
4 m × 4 m
4 m × 4 m
2
4.8 m × 4.8 m
4.8 m × 4.8 m
5 m × 5 m
3
5.6 m × 5.6 m
5.6 m × 5.6 m
6 m × 6 m
4
5.8 m × 5.8 m
5.8 m × 5.8 m
7 m × 7 m
5
6 m × 6 m
6 m × 6 m
9 m × 9 m
6
7 m × 7 m
8 m × 8 m
20 m × 20 m
7
8 m × 8 m
8 m × 8 m
22 m × 22 m
1
4.8 m × 4.8 m
5 m × 5 m
6 m × 6 m
2
5 m × 5 m
5.5 m × 5.5 m
6 m × 6 m
3
5.4 m × 5.4 m
6 m × 6 m
6 m × 6 m
4
5.8 m × 5.8 m
7 m × 7 m
9.5 m × 9.5 m
5
6.2 m × 6.2 m
8 m × 8 m
13 m × 13 m
6
7.2 m × 7.2 m
9.5 m × 9.5 m
20.5 m × 20.5 m
7
8.2 m × 8.2 m
11 m × 11 m
28 m × 28 m
1
6 m × 6 m
7 m × 7 m
2
6 m × 6 m
7.5 m × 7.5 m
3
6 m × 6 m
8 m × 8 m
4
7 m × 7 m
12 m × 12 m
5
8 m × 8 m
15 m × 15 m
6
8 m × 8 m
20 m × 20 m
7
8.4 m × 8.4 m
24 m × 24 m
1
6 m × 6 m
8 m × 8 m
2
6.3 m × 6.3 m
11 m × 11 m
3
6.7 m × 6.7 m
14 m × 14 m
4
7 m × 7 m
17 m × 17 m
5
7.4 m × 7.4 m
20 m × 20 m
6
7.7 m × 7.7 m
24 m × 24 m
7
8.1 m × 8.1 m
27 m × 27 m
1
7 m × 7 m
9 m × 9 m
2
7.1 m × 7.1 m
12 m × 12 m
3
7.3 m × 7.3 m
16 m × 16 m
4
7.4 m × 7.4 m
19 m × 19 m
5
7.5 m × 7.5 m
23 m × 23 m
6
7.7 m × 7.7 m
26 m × 26 m
7
7.8 m × 7.8 m
30 m × 30 m
1
7.3 m × 7.3 m
10 m × 10 m
2
7.3 m × 7.3 m
13.8 m × 13.8 m
3
7.4 m × 7.4 m
17.6 m × 17.6 m
4
7.4 m × 7.4 m
21.5 m × 21.5 m
5
7.5 m × 7.5 m
25.3 m × 25.3 m
6
7.5 m × 7.5 m
29.1 m × 29.1 m
7
7.6 m × 7.6 m
32.9 m × 32.9 m
9

Advertisement

loading

This manual is also suitable for:

Ir quattro hd dali-2Dual hf dali-2Hf 306 dali-2