Download Print this page

Hytronik HCD450/D2 Application/Installation And Instruction Manual

Microwave motion sensor dali output

Advertisement

Quick Links

Installation and Instruction Manual
Microwave Motion Sensor
DALI Output
1. Technical Specifications
Sensor principle
High Frequency (microwave)
Operation frequency
10.525GHz
Frequency range
>10.5 Ghz and <10.6 Ghz
Operating yoltage
120 ~ 277VAC 50/60Hz
Warming-up
20s
Current Consumption
Max. 2mA from DALI Bus
Output
DALI-2 Command
Transmission power
<0.5mW
Max installation height: 27m (forklift)
Detection range(Max.)
Max installation height: 20m (human)
Max detection range: 17 * 14m (L * W)
Detection angle
30° ~ 150°
Operation temperature
Ta: -20°C ~ +60°C
Case temperature (Max.)
Tc: +75°C
Storage temperature
-40°C ~ 70°C
Relative humidity
20 ~ 90%
IP rating
IP65
Insulation
Class II
Wire Preparation
0.75~1.5mm²
8mm
To make or release the wire from the terminal,
use a screwdriver to push down the button.
1. 200 metres (total) max. for 1mm² CSA (Ta = 50℃)
2. 300 metres (total) max. for 1.5mm² CSA (Ta = 50℃)
Subject to change without notice.
HCD450/D2
2. Installation
Mechanical Structure & Dimensions
Wire out
HCD450/D2-20250527-A1
Wiring Diagram
3.Detection Pattern
60°
27m
27m
17m
17m
Forklift driving
60°
3m
24m
Single person continuous walking
Subject to change without notice.
———This product should be installed by a qualified electrician.
60°
20m
20m
12m
12m
Single person continuous walking
16m
24m
15m
Single person continuous walking
HCD450/D2-20250527-A1

Advertisement

loading
Need help?

Need help?

Do you have a question about the HCD450/D2 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Hytronik HCD450/D2

  • Page 1 Installation and Instruction Manual Wiring Diagram Microwave Motion Sensor HCD450/D2 DALI Output 1. Technical Specifications 2. Installation Mechanical Structure & Dimensions Sensor principle High Frequency (microwave) Operation frequency 10.525GHz Frequency range >10.5 Ghz and <10.6 Ghz Operating yoltage 120 ~ 277VAC 50/60Hz...
  • Page 2 3. Data sheet is subject to change without notice. Please always refer to the most recent release on https://hytronik.com/products/motion-daylight-sensors *Set sensitivity: 0x26 *Query sensitivity: 0x2B 4. Regarding Hytronik standard guarantee policy, please kindly refer to https://hytronik.com/service/downloads(Guarantee Conditions document) Address Command...