Akytec MK210-312 User Manual

Akytec MK210-312 User Manual

Digital i/o module
Hide thumbs Also See for MK210-312:

Advertisement

Quick Links

MK210-312
Digital I/O module
User guide
MK210-312_3-EN-38929-1.10
© All rights reserved
Subject to technical changes and misprints
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MK210-312 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Akytec MK210-312

  • Page 1 MK210-312 Digital I/O module User guide MK210-312_3-EN-38929-1.10 © All rights reserved Subject to technical changes and misprints akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 2: Table Of Contents

    6.3 Module access password...................35 6.4 Firmware update .......................35 6.5 Real-time clock setting....................36 6.6 Restore default settings .....................36 6.7 Сounter reset......................36 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 3 7.2 Battery replacement ....................37 8 Transportation and storage ....................39 9 Scope of delivery ......................40 Appendix A Encrypting the log file ..................41 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 4: Warning Notice System

    NOTICE indicates a potentially dangerous situation that could result in damage to property. NOTE NOTE indicates helpful tips and recommendations, as well as information for efficient and trouble-free operation. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 5: Safety

    Failure to obey these warnings could result in personal injury or equipment damage. Akytec company shall not be liable for technical or editorial errors or omissions contained in this document. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 6: Introduction

    Connection, adjustment and maintenance of the device must be carried out only by qualified personnel after reading this operating manual. Order code: MK210-312. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 7: Abbreviations

    – UTC – coordinated universal time. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 8: Overview

    Digital outputs provide the function of the load interruption monitoring and relay operation monitoring. Modules are used in various fields of industry and agriculture. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 9: Specifications

    Output type Electromagnetic relay Contact type Normally open contact – logic state switch Operation mode – PWM signal generation akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 10: Isolation Of The Device Components

    2.2 Isolation of the Device Components The circuit of galvanic isolated components and the strength of galvanic isolation are shown in Figure 2.1. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 11: Environmental Conditions

    IEC 61131-2-2012. The resistance to climatic influences during the operation of the Device is in accordance with IEC 61131-2-2012. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 12: Installation

    Fig. 3.2 Improper installation CAUTION Long-term operation of Module with improper installation can lead to damage (see Figure 3.2). akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 13 3 Installation Fig. 3.4 Mounting dimensions Fig. 3.3 Dimension drawing akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 14: Connection

    Fig. 4.1 Terminal block layout Table 4.1 Contact assignment Marking Description Inputs DI1 – DI12 DI1 – DI12 Common input power supply point akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 15: Connectors

    The connectors of the interfaces and of the power supply of the Device are shown in Figure 4.2. Fig. 4.2 Device's connectors akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 16: Power Supply

    The SS circuits are connected inside the device. Connection diagram is shown in Figure 4.4. Fig. 4.4 Connection to inputs DI1-DI12 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 17: Connection Of P-N-P And N-P-N Transistors

    Figure 4.9 shows the connection diagram to the outputs of the relay type. Fig. 4.9 External connections to digital outputs of the relay type akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 18: Ethernet Connection

    2. An adjacent connection scheme is allowed. 3. The unused Ethernet port should be closed with a blanking plug. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 19: Construction And Operation

    Main application and / or configuration failure Lights 200 ms once every RTC battery must be replaced 3 seconds akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 20: Real Time Clock

    As a string of HEX characters with leading the parameter zeros string 1 byte Separator Character ";" (without quotes) akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 21 If in response to the request a message is received with error code 0x04 (MODBUS_SLAVE_DEVICE_FAILURE), then you can conclude that the addresses of the registers akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 22: Data Exchange Modes

    Additional mode 0х40 Read and write UINT 16 0 – off; for Input DI1 1 – period measurement; akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 23 Read and write UINT 16 0 – off; for Input DI7 1 – period measurement; 2 – high frequency pulse count; akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 24 0 – 10 ms; measuring period 1 – 100 ms; for input DI2 2 – 1 s; 3 – 10 s akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 25 DI7 in additional pulses mode Value on input 0…4294967295 0хАЕ Read only UINT 32 DI8 in additional pulses mode akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 26 Reset pulse 0хEА Read and write UINT 16 0 – reset counter on input 1 – do not reset DI11 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 27 UINT 16 output DO3 Diagnostic of 0 – on, 1 – off 0х1B7 Read and write UINT 16 output DO4 akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 28 0x16 Read and write UINT 32 mask — Set the gateway 0x18 Read and write UINT 32 IP address akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 29: Error Codes For Modbus Protocol

    Writing values to multiple registers MULTIPLE_REGISTERS MODBUS_READ_FILE_ 20 (0x14) Reading log from file RECORD MODBUS_WRITE_FILE_ 21 (0x15) Writing log to file RECORD akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 30 – could not open the file for reading (it may be missing) MODBUS_ILLEGAL_ – could not move to the desired offset DATA_VALUE in the file akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 31: Operation Modes Of The Digital Inputs

    GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 32: Сounting Of High-Frequency Pulses

    Network Master. NOTE The factory setting for Safe state activation timeout is activated is 30 seconds. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 33: Load Interruption Monitoring

    10 kΩ and at least 90 V AC at a load resistance of not more than 20 kΩ. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 34: Configuration

    1. In the drop-down menu, select the akYtec Auto Detection Protocol. Fig. 6.2 Select Protocol 2. Select Find device. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 35: Configuring Network Settings

    If the IP address assignment with service button does not work, set the DHCP mode to One- off setting with service button in the akYtecToolPro program (default setting). akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 36: Module Access Password

    A restart of the Module is required to complete the update. If the Module is connected via USB, it must also be disconnected. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 37: Real-Time Clock Setting

    If the input state counter overflows, then the corresponding register is reset automatically. To force the counter to zero, write the value 0 to the counter reset register. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 38: Maintenance

    6. Alternately remove the hooks from the holes on one side and on the other side and remove the top cover. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 39 When loosing the fastening screws, the terminal block rises, so it is recommended to unscrew the screws by turns several turns at a time. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 40: Transportation And Storage

    IEC 61131-2-2012. In the air no aggressive impurities must be present. Device should be stored in the racks. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 41: Scope Of Delivery

    Ethernet connector plug 1 unit NOTICE The manufacturer reserves the right to introduce amendments to the scope of delivery. akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...
  • Page 42: Appendix A Encrypting The Log File

    (!str) break; temp.hi += (unsigned char) (*str); temp.hi –= (temp.hi << 13) | (temp.hi >> 19); str++; return temp.hilo; akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de...