Connecting the Standard I/O Panel
4.6
The standard I/O panel is connected to the TechCase iC7 with the D-type cable, which is included in the delivery.
The same cable can be used to connect the standard I/O panel and the optional advanced I/O panel.
Connect the standard I/O panel to the OPERATING PANEL terminal. See the locations of the terminals in
In the I/O panel, the terminal is on the left side of the panel.
The D-type cable has a male connector in one end and a female connector in the other end. Connect the male connector to the case and
the female connector to the I/O panel.
Connecting Extra I/Os
4.7
More analog and digital I/Os can be connected to the optional advanced I/O panel (the option is not available yet). The connections are
done with 4 mm safety sockets.
Connecting Ethernet Cables
4.8
The TechCase iC7 has 3 built-in communication ports with RJ45 connectors:
Ethernet ports X1 and X2 allow connections to fieldbus systems, with support for daisy chaining and single connections. The
l
selected protocol is preconfigured. Modbus TCP is offered as standard, and other protocols such as PROFINET RT and EtherNet/IP are
available either preinstalled, or alternatively, they can be activated later with a proof-of-purchase token. Safe Fieldbus protocols are
also supported.
Ethernet port X0 is available to connect to a PC or similar tools used for commissioning or service.
l
For instructions on using MyDrive® Insight, see the iC7 Series Industry Application Guide.
¢
See the locations of the terminals in
Connecting Cases in Series
4.9
TechCase iC7 units can be connected in series (daisy-chain connection). For instructions, see the iC7-Automation Frequency Converters
Design Guide.