National Electric Code (NEC ) and local the life, affect performance, or codes. completely destroy sensitive electronic components. When performing service, proper ESD equipment should be used to prevent possible damage from occurring. MG.17.D3.02 – VLT is a registered Danfoss trademark...
The Semikron and Eupec SCRs are fully interchangeable and can be mixed within the same soft starter. • Connect the firing looms according to the diagrams below. 175G9032 175G9033 175G9034 175G9035 175G9036 MG.17.D3.02 – VLT is a registered Danfoss trademark...
Page 8
MCD 200 Series 175G9037 175G9038 175G9039 175G9040 175G9041 175G9042 MG.17.D3.02 – VLT is a registered Danfoss trademark...
Page 9
MCD 200 Series MG.17.D3.02 – VLT is a registered Danfoss trademark...
Version number is located in the serial number found on the side of the soft starter (e.g. XXXX-01-XXX is version 1). 175G9043 (990-02699-00) (Comes complete with top and middle plastic sections) 175G9056 (350-04160-00) MG.17.D3.02 – VLT is a registered Danfoss trademark...
Page 11
MCD 200 Series 175G9049 (350-03901-00) MG.17.D3.02 – VLT is a registered Danfoss trademark...
175G9153 (version 1-7) 175G9154 (version 1-7) Version number is located in the serial number found on the side of the soft starter (e.g. XXXX-01-XXX is version 1). 175G9147 ~ 175G9150 175G9151 ~ 175G9154 MG.17.D3.02 – VLT is a registered Danfoss trademark...
- Refit the original Main Control PCB. - Replace the Interface PCB. - Check for correct operation. • If correct operation is still not restored - Replace both the Main Control PCB and the Interface PCB. MG.17.D3.02 – VLT is a registered Danfoss trademark...
Verify plug connections between the Main Control Module, Interface PCB and Bypass Relay using the following method. Unplug the Main Control PCB from the Interface PCB. Unplug the Interface PCB from the Bypass Contactors. MG.17.D3.02 – VLT is a registered Danfoss trademark...
Page 18
If correct operation is not restored replace both the Main Control PCB and the Interface PCB. Bypass Control Pins : MCD 200 007, 015, 018, 022, 030 Bypass Control Pins : MCD 200 037, 045, 055 MG.17.D3.02 – VLT is a registered Danfoss trademark...
500 kΩ: MOV Location : MCD 200 007, 015, 018, 022, 030 The Main Control PCB, Interface PCB or connection between them items may be faulty. MG.17.D3.02 – VLT is a registered Danfoss trademark...
Application of incorrect control voltage is evidenced by damage to the MOV located on the Main Control PCB. MOV Location : Control PCB MG.17.D3.02 – VLT is a registered Danfoss trademark...
15%) or A2 to A3 voltage must be 380 V AC to 440 V AC (+10%/-15%). • If the Ready LED (Red) remains off, the Main PCB is damaged and must be replaced. MG.17.D3.02 – VLT is a registered Danfoss trademark...
5-10mm. This will release the clip securing the upper body moulding to the lower body moulding. • Repeat the above procedure for each of the four clips. MG.17.D3.02 – VLT is a registered Danfoss trademark...
5-10mm. This will release the clip securing the upper body moulding to the lower body moulding. • Repeat the above procedure for each of the four clips. MG.17.D3.02 – VLT is a registered Danfoss trademark...
Step 4. Reassemble the MCD 200 is reverse order. 5-10mm. This will release the clip securing the lid the upper body moulding. • Repeat the above procedure for each of the four clips. MG.17.D3.02 – VLT is a registered Danfoss trademark...
Semiconductor fuses: Use of semiconductor fuses reduces the potential for SCR damage caused by short circuits on the output of the starter. Note that protection systems such as circuit breakers or HRC MG.17.D3.02 – VLT is a registered Danfoss trademark...
2. Some contactor brands have a volt free electronic input (low voltage/low current). If this is available, the MCD 200 output relay can be wired directly into this input for contactor control. MG.17.D3.02 – VLT is a registered Danfoss trademark...
Application of incorrect voltages to the control inputs may cause equipment damage and necessitate replacement of the Main PCB. ATTENTION Damage to the control inputs caused by application of incorrect voltages is not covered by warranty. MG.17.D3.02 – VLT is a registered Danfoss trademark...