Operating Guide | TechCase iC7
Before updating the software on the iC7-Automation Frequency Converter, make sure that the software is compatible with the device.
Do not install application software which is not compatible with the iC7-Automation Frequency Converter.
Storage
3.8
Follow these instructions for storing the TechCase iC7.
Procedure
1.
Make sure that the ambient conditions agree to the ones defined in
2.
Make sure that all parts are included in the case and that the cover is closed properly.
3.
If the case is in storage for more than 2 months, keep it in controlled conditions.
a.
Make sure that the temperature variation is small.
b.
Make sure that the humidity is less than 50%.
4.
If the case is in storage for more than 12 months, it is recommended to connect power to the drive.
a.
Connect power to the drive.
b.
Keep the power on for a minimum of 2 hours.
c.
Disconnect the power.
d.
Wait for the correct discharge time before removing the drive and storing it again.
5.
If the case is in storage for several years, reform the capacitors to prevent damage to the capacitors.
Instructions for reforming the capacitors are available in the iC7-Automation Frequency Converters Design Guide.