Summary of Contents for Emerson Rosemount 8800DW

  • Page 1 (217) 352-9330 | Click HERE Find the Emerson / Rosemount Analytical 8800DW at our website:...
  • Page 2 Reference Manual 00809-0100-4004, Rev DC May 2016 ™ Rosemount 8800D Series Vortex Flowmeter Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 3 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 4: Table Of Contents

    Reference Manual Table of Contents 00809-0100-4004, Rev DC May 2016 Contents 1Section 1: Introduction How to use this manual..........1 Safety messages .
  • Page 5 Table of Contents Reference Manual May 2016 00809-0100-4004, Rev DC Meter body installation tasks ......... . .28 3.5.1 Handling .
  • Page 6 Reference Manual Table of Contents 00809-0100-4004, Rev DC May 2016 4.2.8 Device Information ..........64 4.2.9 Change HART Revisions .
  • Page 7 Table of Contents Reference Manual May 2016 00809-0100-4004, Rev DC B.2.3 Type n protection type in accordance with IEC 60079-15, EN60079-15 ..........141 European Directive Information .
  • Page 8 Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings. ™ For information on Rosemount nuclear-qualified products, contact your local Emerson Process Management Sales Representative. This product is intended to be used as a flowmeter for liquid, gas, or steam applications.
  • Page 9: Title Page

    Title Page Reference Manual May 2016 00809-0100-4004, Rev DC Title Page Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 10: How To Use This Manual

    Introduction Reference Manual May 2016 00809-0100-4004, Rev DC Section 1 Introduction How to use this manual This manual provides installation, configuration, operation, troubleshooting, and other ™ procedures for the use of the Rosemount 8800D Vortex Flowmeter. For model code ordering information, see the Rosemount 8800D Series Vortex Flowmeter Product Data Sheet.
  • Page 11 Introduction Reference Manual May 2016 00809-0100-4004, Rev DC Introduction Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 12: Process Variables

    Reference Manual Configuration 00809-0100-4004, Rev DC May 2016 Section 2 Configuration Process variables ............page 3 Basic setup .
  • Page 13: Process Variable Units

    Configuration Reference Manual May 2016 00809-0100-4004, Rev DC 2.1.4 Process Variable Units 2, 2, 2, 6 FastKeys Allows for the viewing and configuration of Process Variable Units such as Volume, Velocity, Mass Flow, Electronics Temperature, Process Density, and Corrected Volume units, including corrected volume Special Units configuration.
  • Page 14: Corrected Volumetric Flow Units

    Reference Manual Configuration 00809-0100-4004, Rev DC May 2016 Corrected Volumetric Flow Units 2,2,2,6,2 FastKeys Allows the user to select the corrected volumetric flow units from the available list. gallons per second imperial gallons per hour gallons per minute imperial gallons per day gallons per hour liters per second gallons per day...
  • Page 15: Velocity Flow

    Configuration Reference Manual May 2016 00809-0100-4004, Rev DC Mass Flow Units 2, 2, 2, 6, 5 FastKeys Allows the user to select the mass flow units from the available list. (1 STon = 2000 lb; 1 MetTon = 1000 kg) grams per hour pounds per day grams per minute...
  • Page 16: Special Units

    Reference Manual Configuration 00809-0100-4004, Rev DC May 2016 Special Units 2,2,2,7 (Volume) FastKeys 2,2,2,8 (Mass) 2,2,2,9 (Corrected Volume) Allows the user to create flow rate units that are not among the standard options. Configuration of a special unit involves entry of these values: base flow unit, base time unit, user defined unit and conversion number.
  • Page 17: Special Flow Unit

    Configuration Reference Manual May 2016 00809-0100-4004, Rev DC Special Flow Unit 2,2,2,7,5 (Volume) FastKeys 2,2,2,8,5 (Mass) 2,2,2,9,5 (Corrected Volume) A user created custom flow unit. The special unit is limited to four characters. The Field Communicator indicates the special unit with SPCL. The LCD display will display the actual four character user defined special unit.
  • Page 18: Totalizer Config

    Reference Manual Configuration 00809-0100-4004, Rev DC May 2016 Totalizer Config 2, 2, 4, 3, 3 FastKeys Used to configure the flow parameter (volume, mass, velocity, or corrected volume flow) that will be totaled. Note The totalizer value is saved in the non-volatile memory of the electronics every three seconds.
  • Page 19 Configuration Reference Manual May 2016 00809-0100-4004, Rev DC Calculated Process Density 3, 2, 1 FastKeys Allows the user to view the calculated process density value when the transmitter is configured for temperature compensated steam or temperature compensated liquid applications. Process Density Units 2, 2, 2, 6, 7 (without MTA) FastKeys 2, 2, 2, 6, 8 (with MTA)
  • Page 20: Basic Setup

    Reference Manual Configuration 00809-0100-4004, Rev DC May 2016 Basic setup 2, 1, 1, 1 FastKeys The Rosemount 8800D must be configured for certain basic variables in order to be operational. In most cases, all of these variables are pre-configured at the factory. Configuration may be required if your Rosemount 8800D is not configured or if the configuration variables need revision.
  • Page 21: Fixed Process Temperature

    2, 2, 1, 2, 1 FastKeys A factory calibration number relating the flow through the meter to the shedding frequency measured by the electronics. Every 8800 meter manufactured by Emerson is run through a water calibration to determine this value. Configuration...
  • Page 22: Flange Type

    Reference Manual Configuration 00809-0100-4004, Rev DC May 2016 2.2.5 Flange Type 2, 2, 1, 4, 2 FastKeys Enables the user to specify the type of flange on the flowmeter for later reference. This variable is preset at the factory but can be changed if necessary. Wafer PN25 ...
  • Page 23: Variable Mapping

    Configuration Reference Manual May 2016 00809-0100-4004, Rev DC Pipe size Schedule 10 Schedule 40 Schedule 80 inches (mm) inches (mm) inches (mm) inches (mm) 6 (150) 6.357 (161.5) 6.065 (154.1) 5.761 (146.3) 8 (200) 8.329 (211.6) 7.981 (202.7) 7.625 (193.7) 10 (250) 10.420 (264.67) 10.020 (254.51)
  • Page 24: Fourth Variable

    Reference Manual Configuration 00809-0100-4004, Rev DC May 2016 Fourth Variable 2, 2, 2, 4 FastKeys Selections for the Fourth Variable are identical to those of the Secondary Variable. 2.2.8 Process Variable Units 2, 2, 2, 6 FastKeys This selection allows the user to set the units of measure for all available process variables. 2.2.9 Analog Output 3, 4, 3, 1...
  • Page 25: Damping

    Configuration Reference Manual May 2016 00809-0100-4004, Rev DC 2.2.10 Damping 2, 1, 4, 1 FastKeys Damping changes the response time of the flowmeter to smooth variations in output readings caused by rapid changes in input. Damping is applied to the Analog Output, Primary Variable, Percent of Range, and Vortex Frequency.
  • Page 26 Reference Manual Configuration 00809-0100-4004, Rev DC May 2016 Table 2-2. Fast Keys for Rosemount 8800D HART 7 Device Revision 2 (DD Revision 1)/ HART 5 Device Revision 3 (DD Revision 1) Function Fast Key Function Fast Key Analog Output 3, 4, 3, 1 Polling Address 2, 2, –...
  • Page 27 Configuration Reference Manual May 2016 00809-0100-4004, Rev DC Figure 2-1. Overview Menu Map Overview Device Status Universal Refresh Alerts Comm Status Long Tag Field Device Clear Config Changed Flag Primary Variable Model Software Active Alerts Primary Variable Value Serial Number Hardware Status Date...
  • Page 28 Reference Manual Configuration 00809-0100-4004, Rev DC May 2016 Figure 2-2. Configure Menu Map Configuration Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 29 Configuration Reference Manual May 2016 00809-0100-4004, Rev DC Figure 2-3. Service Tools Menu Map Configuration Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 30: Safety Messages

    Reference Manual Installation 00809-0100-4004, Rev DC May 2016 Section 3 Installation Safety messages ............page 21 Commissioning .
  • Page 31 Installation Reference Manual May 2016 00809-0100-4004, Rev DC Figure 3-1. Installation Flowchart Bench START HERE Commissioning? FIELD INSTALL Review CONFIGURE Configuration Mount Configuration Flowmeter Process Config  Transmitter Mode  Process Fluid  Fixed Process Temp. Mount  Base Density Conduit Go to (Std.
  • Page 32: Commissioning

    Reference Manual Installation 00809-0100-4004, Rev DC May 2016 Commissioning Commission the Rosemount 8800D before putting it into operation. This ensures proper configuration and operation of the meter. It also enables you to check hardware settings, test the flowmeter electronics, verify flowmeter configuration data, and check output variables.
  • Page 33: Horizontal Installation

    Installation Reference Manual May 2016 00809-0100-4004, Rev DC Horizontal installation For horizontal installation, the preferred orientation is to have the electronics installed to the side of the pipe. In liquid applications, this ensures any entrained air or solids do not strike the shedder bar and disrupt the shedding frequency.
  • Page 34: Upstream/Downstream Piping

    Ensure that the process fluid is compatible with the meter body wetted materials when specifying the Rosemount 8800D. Corrosion will shorten the life of the meter body. Consult recognized sources of corrosion data or contact your Emerson Flow Sales Representative for more information.
  • Page 35: Environmental Considerations

    Installation Reference Manual May 2016 00809-0100-4004, Rev DC 3.2.4 Environmental considerations Avoid excessive heat and vibration to ensure maximum flowmeter life. Typical problem areas include high-vibration lines with integrally mounted electronics, warm-climate installations in direct sunlight, and outdoor installations in cold climates. Although the signal conditioning functions reduce susceptibility to extraneous noise, some environments are more suitable than others.
  • Page 36: Failure Mode Vs. Saturation Output Values

    Reference Manual Installation 00809-0100-4004, Rev DC May 2016 Figure 3-5. Alarm and Security Jumpers Alarm As part of normal operations, the Rosemount 8800D continuously runs a self-diagnostic routine. If the routine detects an internal failure in the electronics, flowmeter output is driven to a low or high alarm level, depending on the position of the failure mode jumper.
  • Page 37: Lcd Indicator Option

    Installation Reference Manual May 2016 00809-0100-4004, Rev DC Table 3-1. Analog Output: Standard alarm values vs. Saturation Values Level 4—20 mA saturation value 4—20 mA alarm value 3.9 mA < 3.75 mA ≥ 21.75 mA High 20.8 mA Table 3-2. Analog Output: NAMUR-Compliant Alarm Values vs. Saturation Values Level 4—20 mA saturation value 4—20 mA alarm value...
  • Page 38: Flow Direction

    Reference Manual Installation 00809-0100-4004, Rev DC May 2016 Figure 3-7. Lifting Supports 3.5.2 Flow direction Mount the meter body so the FORWARD end of the flow arrow, shown on the meter body, points in the direction of the flow in the pipe. 3.5.3 Gaskets The Rosemount 8800D requires gaskets supplied by the user.
  • Page 39 Installation Reference Manual May 2016 00809-0100-4004, Rev DC Table 3-3. Minimum Recommended Stud Bolt Lengths for Wafer Installation with ASME B16.5 (ANSI) Flanges Minimum recommended stud bolt lengths (in Inches) for each flange rating Line size Class 150 Class 300 Class 600 ½-inch 6.00...
  • Page 40: Wafer-Style Flowmeter Alignment And Mounting

    Reference Manual Installation 00809-0100-4004, Rev DC May 2016 3.5.5 Wafer-style flowmeter alignment and mounting Center the wafer-style meter body inside diameter with respect to the inside diameter of the adjoining upstream and downstream piping. This will ensure the flowmeter achieves its specified accuracy.
  • Page 41 Installation Reference Manual May 2016 00809-0100-4004, Rev DC Figure 3-8. Wafer-Style Flowmeter Installation with Alignment Rings FLOW A. Installation studs and nuts (supplied by customer) B. Alignment rings C. Spacer (for Rosemount 8800D to maintain Rosemount 8800A dimensions) D. Gaskets (supplied by customer) Figure 3-9.
  • Page 42: Flanged-Style Flowmeter Mounting

    Reference Manual Installation 00809-0100-4004, Rev DC May 2016 3.5.6 Flanged-style flowmeter mounting Physical mounting of a flanged-style flowmeter is similar to installing a typical section of pipe. Conventional tools, equipment, and accessories (such as bolts and gaskets) are required. Tighten the nuts following the sequence shown in Figure 3-11.
  • Page 43 Installation Reference Manual May 2016 00809-0100-4004, Rev DC Figure 3-10. RED Area for Both Integral and Remote Electronics Connection Types A. Do not insulate within the RED area for both integral and remote electronics connection types. B. 1 in. (25 mm) minimum Installation Artisan Technology Group - Quality Instrumentation ...
  • Page 44: Flowmeter Grounding

    Reference Manual Installation 00809-0100-4004, Rev DC May 2016 Figure 3-11. Flange Bolt Torquing Sequence 3.5.7 Flowmeter grounding Grounding is not required in typical vortex applications; however, a proper ground will eliminate possible noise pickup by the electronics. Grounding straps may be used to ensure that the meter is grounded to the process piping.
  • Page 45: High-Temperature Installations

    Installation Reference Manual May 2016 00809-0100-4004, Rev DC 3.6.1 High-temperature installations Install the meter body so the electronics are positioned to the side of or below the pipe as shown in Figure 3-2 on page 24. Insulation may be required around the pipe to maintain an ambient transmitter temperature below 185 °F (85 °C) or the more restrictive temperature ratings marked on hazardous locations tags.
  • Page 46: Cable Gland

    Reference Manual Installation 00809-0100-4004, Rev DC May 2016 3.6.4 Cable gland If you are using cable glands instead of conduit, follow the cable gland manufacturer’s instructions for preparation and make the connections in a conventional manner in accordance with local or plant electrical codes. Be sure to properly seal unused ports to prevent moisture or other contamination from entering the terminal block compartment of the electronics housing.
  • Page 47 Installation Reference Manual May 2016 00809-0100-4004, Rev DC Note A minimum loop resistance of 250 ohms is required to exchange information with a HART-based communicator. With 250 ohms of loop resistance, the flowmeter will require a minimum power supply voltage (V ) of 16.8 volts to output 24 mA.
  • Page 48 Reference Manual Installation 00809-0100-4004, Rev DC May 2016 Note Twisted pairs are required to minimize noise pickup in the 4–20 mA signal and digital communication signal. For high EMI/RFI environments, shielded signal wire is required and recommended in all other installations. To ensure communication, wiring should be 24 AWG or larger and not exceed 5,000 ft (1500 m).
  • Page 49 Installation Reference Manual May 2016 00809-0100-4004, Rev DC Note When using pulse output, be sure to follow these precautions: Shielded twisted pair is required when the pulse output and 4–20 mA output are  run in the same conduit or cable trays. Shielded wire will also reduce false triggering caused by noise pickup.
  • Page 50: Remote Electronics

    Reference Manual Installation 00809-0100-4004, Rev DC May 2016 Figure 3-16. 4-20 mA Wiring ≥ 250 Ω A. Power supply Figure 3-17. 4–20 mA and Pulse Wiring with Electronic Totalizer/Counter >250 Ω − 100 Ω < R < 100 kΩ − −...
  • Page 51: Cable Connections

    Installation Reference Manual May 2016 00809-0100-4004, Rev DC Cable connections Refer to Figure 3-18 and the following instructions to connect the loose end of the coaxial cable to the electronics housing. (See “Remote electronics procedure” on page 88 if con- necting/disconnecting the meter adapter to the meter body.) Figure 3-18.
  • Page 52: Calibration

    Reference Manual Installation 00809-0100-4004, Rev DC May 2016 Slide the housing adapter over the coaxial cable. Remove one of the four housing base screws. Attach the coaxial cable ground wire to the housing via the housing base ground screw. Attach and securely tighten the coaxial cable nut to the connection on the electronics housing.
  • Page 53 Installation Reference Manual May 2016 00809-0100-4004, Rev DC Figure 3-19. Rosemount 8800D with Optional Indicator A. Electronics board The indicator features an eight-character (and five alphanumeric) liquid crystal display that gives a direct reading of the digital signal from the microprocessor. During normal operation, the display can be configured to alternate between the following readings: Primary variable in engineering units ...
  • Page 54: Installing The Indicator

    Reference Manual Installation 00809-0100-4004, Rev DC May 2016 Figure 3-20. Optional Liquid Crystal Display A HART-based communicator can be used to change the engineering units of the parameters displayed on the indicator. (See Section 4: Operation for more information). 3.7.1 Installing the indicator For flowmeters ordered with the LCD indicator, the indicator is shipped installed.
  • Page 55: Transient Protection

    Installation Reference Manual May 2016 00809-0100-4004, Rev DC Insert the mounting screws into the LCD indicator. Remove the two jumpers on the circuit board that coincide with the Alarm and the Security settings. Insert the connector into the Alarm/Security junction. Gently slide the LCD indicator onto the connector and tighten the screws into place.
  • Page 56: Installing The Transient Protector

    Reference Manual Installation 00809-0100-4004, Rev DC May 2016 3.8.1 Installing the transient protector For flowmeters ordered with the transient protector option (T1), the protector is shipped installed. When purchased separately from the Rosemount 8800D, you must install the protector on a Rosemount 8800D Flowmeter using a small instrument screwdriver, a pliers, and the transient protection kit.
  • Page 57 Installation Reference Manual May 2016 00809-0100-4004, Rev DC Installation Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 58: Diagnostics/Service

    Reference Manual Operation 00809-0100-4004, Rev DC May 2016 Section 4 Operation Diagnostics/service ............page 49 Advanced functionality .
  • Page 59: Reset Transmitter

    Operation Reference Manual May 2016 00809-0100-4004, Rev DC Self Test 3, 4, 4, 1, 1 FastKeys Although the Rosemount 8800D performs continuous self-diagnostics, you can initiate an immediate diagnostic to check for possible electronics failure. Self test checks proper communications with the transmitter and provides diagnostic capabilities for transmitter problems.
  • Page 60: Simulate Flow

    Reference Manual Operation 00809-0100-4004, Rev DC May 2016 Simulate Flow 3, 5, 1, 2, 1 FastKeys Allows flow simulation using either an internal or external sensor input signal. Internal Flow Simulation 3, 5, 1, 2, 1, 2 FastKeys Disconnects the sensor signal from the electronics, and allows for configuration of the internal flow simulation for fixed or ramped flow.
  • Page 61: Scaled Analog Trim

    Operation Reference Manual May 2016 00809-0100-4004, Rev DC To trim the digital-to-analog output, initiate the Analog Trim function and connect an ammeter to the loop to measure the actual analog output of the meter. Follow the on-screen functions to complete the task. 4.1.5 Scaled Analog Trim 3, 4, 3, 8...
  • Page 62: Meter Body

    Reference Manual Operation 00809-0100-4004, Rev DC May 2016 The compensated K-factor is based on the reference K-factor as compensated for the given process temperature, wetted materials, body number, and pipe ID. Compensated K-factor is an informational variable that is calculated by the electronics of your flowmeter. Meter Body 2, 2, 1, 4 FastKeys...
  • Page 63: Pulse Output

    Operation Reference Manual May 2016 00809-0100-4004, Rev DC Restore Factory Calibration 3, 4, 3, 9 FastKeys Restores factory analog trim settings. 4.2.1 Pulse Output 2, 2, 4, 4, 2 FastKeys Can be configured using the configuration tool guided setups. Note Configuration of the pulse features is allowed even if the pulse option (Option P) was not ordered.
  • Page 64: Scaled Velocity

    Reference Manual Operation 00809-0100-4004, Rev DC May 2016 Scaled velocity This mode allows for configuration of the pulse output based on a velocity flow rate. Scaled mass This mode allows for configuration of the pulse output based on based on a mass flow rate. If Process Fluid = Tcomp Sat Steam or Tcomp Liquid, this is a temperature compensated mass flow.
  • Page 65: Temperature Compensated Steam

    Operation Reference Manual May 2016 00809-0100-4004, Rev DC Temperature Compensated Steam 2, 2, 1, 1, 3 FastKeys To compensate for changes in saturated steam, select the Temperature Compensated Steam (TComp Sat Steam) fluid type. Choosing this fluid type automatically enables dynamic density compensation while measuring mass flow or corrected volumetric flow by using the built-in steam tables.
  • Page 66: Smart Fluid Diagnostic

    Reference Manual Operation 00809-0100-4004, Rev DC May 2016 4.2.3 SMART Fluid Diagnostic 2, 2, 6 FastKeys Due to unpredictable flow conditions and multiple potential failure modes in a process piping system, the SMART Fluid Diagnostic should not be used as a fail-safe alert when the transition from liquid to gas represents a safety hazard.
  • Page 67: Alarm Latch

    Operation Reference Manual May 2016 00809-0100-4004, Rev DC Alarm Latch 2, 2, 6, 2, 5 FastKeys Dictates the behavior of the alarm once gas flow is detected. If Alarm Latch is Enabled, the alarm will continue until the user resets the alarm manually (using a HART communication device such as AMS Device Manager, or handheld communicator).
  • Page 68: Communications

    Reference Manual Operation 00809-0100-4004, Rev DC May 2016 4.2.4 Communications 2, 2, HART FastKeys Multidrop configuration refers to the connection of several flowmeters to a single communications transmission line. Communication occurs digitally between a HART-based communicator or control system and the flowmeters. Multidrop mode automatically deactivates the analog output of the flowmeters.
  • Page 69: Poll Address

    Operation Reference Manual May 2016 00809-0100-4004, Rev DC Poll address 2, 2, HART, 2, 1 FastKeys Enables configuration of the poll address for a multi-dropped meter. The poll address is used to identify each meter on the multi-drop line. Follow the on-screen instructions to set the address at a number from 1 to 15.
  • Page 70: Burst Option

    Reference Manual Operation 00809-0100-4004, Rev DC May 2016 Burst Option Enables you to select the variables to broadcast over the loop: PV—Selects the primary variable for broadcast over the loop. Percent Range/Current—Selects the primary variable as percent of range and analog output current for broadcast over the loop.
  • Page 71: Signal Strength

    Operation Reference Manual May 2016 00809-0100-4004, Rev DC Use signal processing only when recommended in the troubleshooting section of this manual. Some of the problems that may require signal processing include: High output (output saturation)  Erratic output with or without flow present ...
  • Page 72: Low Flow Cutoff

    Reference Manual Operation 00809-0100-4004, Rev DC May 2016 Low Flow Cutoff 2, 2, 5, 2, 2 FastKeys Enables the adjustment of the filter for noise at no flow. It is set at the factory to handle most applications, but certain applications may require adjustment either to expand measurability or to reduce noise.
  • Page 73: Restore Default Filter

    Operation Reference Manual May 2016 00809-0100-4004, Rev DC Note Do not adjust this parameter unless directed to do so by a Rosemount Technical Support Representative. Restore Default Filter 2, 2, 5, 5, 2 FastKeys Restores all of the signal conditioning variables to default values. Default values for signal conditioning variables will be set automatically depending on fluid type using the Optimize DSP function with a density setting of 40 lb/ft for liquid or 0.15 lb/ft...
  • Page 74: Write Protect

    Reference Manual Operation 00809-0100-4004, Rev DC May 2016 Descriptor 2, 2, Device Information, 1, 6 FastKeys Longer user-defined variable to assist with more specific identification of the particular flowmeter. It is usually used in multi-flowmeter environments and provides 16 characters. Message 2, 2, Device Information, 1, 7 FastKeys...
  • Page 75: Software Revision

    Operation Reference Manual May 2016 00809-0100-4004, Rev DC Software Revision 2, 2, Device Information, 2, 3 FastKeys Designates the internal software revision level for the Rosemount 8800D. Hardware Revision 2, 2, Device Information, 2, 4 FastKeys Designates the revision level for the Rosemount 8800D hardware.
  • Page 76 Reference Manual Troubleshooting 00809-0100-4004, Rev DC May 2016 Section 5 Troubleshooting Safety messages ............page 68 Troubleshooting tables .
  • Page 77: Safety Messages

    Troubleshooting Reference Manual May 2016 00809-0100-4004, Rev DC Safety messages Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Refer to the following safety messages before performing any in this section. Explosions could result in death or serious injury.
  • Page 78: Advanced Troubleshooting

    Reference Manual Troubleshooting 00809-0100-4004, Rev DC May 2016 Symptom Corrective action Incorrect 4–20 mA • Check for minimum 10.8 Vdc at transmitter • Check for corrosion on terminal block. Output terminals. • Replace electronics if necessary. • Check URV, LRV, Density, Special Units, LFC– •...
  • Page 79 Troubleshooting Reference Manual May 2016 00809-0100-4004, Rev DC Table 5-2. Field Communicator Diagnostic Messages Message Description ROM CHECKSUM ERROR The EPROM memory checksum test has failed. The transmitter will remain in ALARM until the ROM checksum test passes. NV MEM CHECKSUM ERROR The User Configuration area in Nonvolatile EEPROM memory has failed the checksum test.
  • Page 80: Electronics Test Points

    Reference Manual Troubleshooting 00809-0100-4004, Rev DC May 2016 Message Description FLOW SIMULATION The transmitter flow signal is being simulated by a signal generator internal to the transmitter. The actual flow through the meter body is NOT being measured. SENSOR SIGNAL IGNORED The transmitter flow signal is being simulated by a signal generator external to the transmitter.
  • Page 81 Troubleshooting Reference Manual May 2016 00809-0100-4004, Rev DC Figure 5-1. Electronics Test Points A. Ground B. Test Frequency IN C. TP1 The electronics is capable of internally generating a flow signal that may be used to simulate ™ a sensor signal to perform electronics verification with a handheld communicator or AMS Device Manager interface.
  • Page 82: Tp1-Test Point 1

    Reference Manual Troubleshooting 00809-0100-4004, Rev DC May 2016 5.3.3 TP1—Test point 1 TP1 is the vortex shedding signal after it has gone through the charge amplifier and low pass filter stages and into the input of the sigma delta A-to-D converter ASIC in the electronics. The signal strength at this point will be in the mV to Volt range.
  • Page 83 Troubleshooting Reference Manual May 2016 00809-0100-4004, Rev DC Figure 5-5. Improper Sizing/Filtering 3.0 V A. Vortex signal (TP1) B. Trigger level C. Shedding frequency output Troubleshooting Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 84: Diagnostic Messages On Lcd Display

    Reference Manual Troubleshooting 00809-0100-4004, Rev DC May 2016 Diagnostic messages on LCD display In addition to the output, the LCD display displays diagnostic messages for troubleshooting the flowmeter. These messages are as follows: SELFTEST The flowmeter is in the process of performing an electronics self test. FAULT_ROM The flowmeter electronics has undergone a EPROM checksum fault.
  • Page 85: Testing Procedures

    Troubleshooting Reference Manual May 2016 00809-0100-4004, Rev DC FAULT_SDPLS The flowmeter electronics has detected a loss of flow data from the sigma-delta ASIC. Contact your Field Service Center. FAULT_TASK(#) The flowmeter electronics has detected a fatal error. Record (#) and contact your Field Service Center.
  • Page 86: Hardware Replacement

    Reference Manual Troubleshooting 00809-0100-4004, Rev DC May 2016 Hardware replacement The following procedures will help you disassemble and assemble the Rosemount 8800D hardware if you have followed the troubleshooting guide earlier in this section of the manual and determined that hardware components need to be replaced. Note Use only the procedures and new parts specifically referenced in this manual.
  • Page 87: Install The Terminal Block

    Troubleshooting Reference Manual May 2016 00809-0100-4004, Rev DC Disconnect the wires from the field terminals. Be sure to secure them out of the way. Remove the ground screw if transient protection (Option T1) is installed. Loosen the three captive screws. Pull outward on the terminal block to remove it from the housing.
  • Page 88: Remove The Electronics Boards

    Reference Manual Troubleshooting 00809-0100-4004, Rev DC May 2016 Remove the electronics boards Turn off the power to the Rosemount 8800D. Unscrew and remove the electronics board compartment cover. (Unscrew and remove the LCD display cover if you have the LCD display option). Figure 5-7.
  • Page 89: Install The Electronics Boards

    Troubleshooting Reference Manual May 2016 00809-0100-4004, Rev DC Install the electronics boards Verify that power to the Rosemount 8800D is off. Align the sockets on the bottom of the two electronics boards over the pins protruding from the bottom of the housing cavity. Carefully guide the sensor cable through the notches on the edge of the circuit boards.
  • Page 90: Remove The Electronics Housing

    Reference Manual Troubleshooting 00809-0100-4004, Rev DC May 2016 Remove the electronics housing Turn off the power to the Rosemount 8800D. Remove the terminal block side cover. Disconnect the wires and conduit from the housing. Use a -in. (4 mm) hex wrench to loosen the housing rotation screws (at the base of the electronics housing) by turning screws clockwise (inward) until they clear the bracket.
  • Page 91: Replacing The Sensor

    Troubleshooting Reference Manual May 2016 00809-0100-4004, Rev DC 5.6.4 Replacing the sensor The sensor for the Rosemount 8800D is a sensitive instrument that should not be removed unless there is a problem with it. If you must replace the sensor, follow these procedures closely.
  • Page 92 Reference Manual Troubleshooting 00809-0100-4004, Rev DC May 2016 Note There are numerous tube fittings that could connect to the tube if there is a need to drain away process material. The tube on the valve has a ” OD with a 0.035” wall thickness. Using a -in.
  • Page 93: Cleaning The Sealing Surface

    Troubleshooting Reference Manual May 2016 00809-0100-4004, Rev DC Remove the support tube. Loosen and remove the sensor nut from the sensor cavity with a 1 -in. (28-mm) open end wrench. (Use a -in. (19-mm) open end wrench for 3- and 4-in. [80 and 100 mm] SST wafers.) Lift the sensor from the sensor cavity.
  • Page 94: Sensor Installation

    Reference Manual Troubleshooting 00809-0100-4004, Rev DC May 2016 Figure 5-9. O-Ring Sealing Surface in Sensor Cavity A.Sealing surface Sensor installation Carefully place sensor over the post in the sensor cavity. Ensure that the sensor is centered on the post. See Figure 5-10 for an example of improper installation and...
  • Page 95 Troubleshooting Reference Manual May 2016 00809-0100-4004, Rev DC Figure 5-10. Sensor Installation – Improper Alignment Improper Alignment (before seating) Top View of Flowmeter A.Sensor B. Sensor cavity in flowmeter C. Sensor not properly aligned D. Sensor centerline is not aligned with flowmeter centerline. Damage to sensor will occur. Troubleshooting Artisan Technology Group - Quality Instrumentation ...
  • Page 96 Reference Manual Troubleshooting 00809-0100-4004, Rev DC May 2016 Figure 5-11. Sensor Installation – Proper Alignment Proper Alignment (before seating) Top View of Flowmeter A.Sensor B. Sensor cavity in flowmeter C. Sensor centerline must be aligned with flowmeter centerline. Sensor should remain as close to vertical as possible when applying force to seat. Figure 5-12.
  • Page 97: Remote Electronics Procedure

    Troubleshooting Reference Manual May 2016 00809-0100-4004, Rev DC Figure 5-12. Sensor Installation – Applying Force Apply Force With Hand Until Sensor is Seated A.Pressure B. Sensor centerline must be aligned with flowmeter centerline. C. Sensor properly seated Manually push down on the sensor by applying equal pressure for engagement onto the post.
  • Page 98: Disconnect The Coaxial Cable At The Meter

    Reference Manual Troubleshooting 00809-0100-4004, Rev DC May 2016 Disconnect the coaxial cable at the meter Remove the access cover on the meter body support tube if present. Loosen the three housing rotation screws at the base of the meter adapter with a -in.
  • Page 99 Troubleshooting Reference Manual May 2016 00809-0100-4004, Rev DC Figure 5-13. Coaxial Cable Connections A.½ NPT conduit adapter or cable gland (supplied by customer) B. Coaxial cable C. Meter adapter D. Union E. Washer F. Nut G. Sensor cable nut H. Support tube I.
  • Page 100: Detach The Meter Adapter

    Reference Manual Troubleshooting 00809-0100-4004, Rev DC May 2016 Detach the meter adapter The above instructions will provide access to the meter body. Use the following steps if it is necessary to remove the coaxial cable: Loosen and remove the two screws that hold the union onto the meter adapter and pull the union away from the adapter.
  • Page 101: Coaxial Cable At The Electronics Housing

    Troubleshooting Reference Manual May 2016 00809-0100-4004, Rev DC 5.6.7 Coaxial cable at the electronics housing Remove the coaxial cable from the electronics housing Loosen the two housing screws from the housing adapter. Remove the housing adapter from the housing. Loosen and remove the coaxial cable nut from the base of the electronics housing. Remove the coaxial cable ground connection from the housing base by loosening the housing base screw that is connecting it to the housing base.
  • Page 102: Attach The Coaxial Cable

    Reference Manual Troubleshooting 00809-0100-4004, Rev DC May 2016 Attach the coaxial cable Route the coaxial cable through the conduit (if you are using conduit). Place a conduit adapter over the end of the coaxial cable. Remove the housing adapter from the electronics housing (if attached). Slide the housing adapter over the coaxial cable.
  • Page 103: Temperature Sensor Replacement (Mta Option Only)

    Troubleshooting Reference Manual May 2016 00809-0100-4004, Rev DC Note Do not rotate the housing while the sensor cable is attached to the base of the housing. This will stress the cable and may damage the sensor. Place the electronics housing into the top of the support tube. Use a hex wrench to turn the three housing rotation screws counterclockwise to engage the support tube.
  • Page 104: Return Of Material

    1-800-522-6277 (7:00 am to 7:00 pm CST) North American Response Center—Equipment service needs: 1-800-654-7768 (24 hours—includes Canada) Outside of the United States, contact your local Emerson Process Management representa- tive. Troubleshooting Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 105 Troubleshooting Reference Manual May 2016 00809-0100-4004, Rev DC Troubleshooting Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 106: Aappendix A: Specifications And Reference Data

    Dimensional drawings ........... page 124 Specifications ™ The following specifications are for the Rosemount 8800D, Rosemount 8800DR, Rosemount 8800DD, and Rosemount 8800DW, except where noted. Functional specifications Process fluids Liquid, gas, and steam applications. Fluids must be homogeneous and single-phase. Line sizes...
  • Page 107: Measurable Flow Rates

    Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Measurable flow rates Capable of processing signals from flow applications which meet the sizing requirements below. To determine the appropriate flowmeter size for an application, process conditions must be within the Reynolds number and velocity limitations for the desired line size provided in Table A-1,...
  • Page 108: Analog Output Adjustment

    Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Process temperature limits Standard –40 to 450 °F (–40 to 232 °C) Extended –330 to 800 °F (–200 to 427 °C) Severe –330 to 842 °F (–200 to 450 °C) - 157 to 800 °F (-105 to 427 °C) for European Pressure Equipment Directive (PED), ...
  • Page 109: Pressure Limits

    Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Storage –58 to 250 °F (–50 to 121 °C) –50 to 185 °F (–46 to 85 °C) for flowmeters with local indicator Pressure limits Flange style meter Rated for ASME B16.5 (ANSI) Class 150, 300, 600, 900, and 1500, EN 1092-1, PN 10, 16, 25, 40, 63, 100, and 160, and JIS 10K, 20K, and 40K Reducer style meter Rated for ASME B16.5 (ANSI) Class 150, 300, 600, 900, and 1500, EN 1092-1, PN 10, 16, 25,...
  • Page 110: Power Consumption

    Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Power consumption One watt maximum Load limitations (HART analog) Maximum loop resistance is determined by the voltage level of the external power supply, as described by: 1250 1000 Operating Region 10.8 Power Supply (Volts)
  • Page 111: Permanent Pressure Loss

    Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Permanent pressure loss The approximate permanent pressure loss (PPL) from the Rosemount 8800D flowmeter is calculated for each application in the Vortex sizing software available from your local Rosemount representative. The PPL is determined using the equation: ×...
  • Page 112: Failure Mode Alarm

    Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Failure mode alarm HART analog If self-diagnostics detect a gross flowmeter failure, the analog signal will be driven to the values below: 3.75 mA High 21.75 mA NAMUR Low 3.60 mA NAMUR High 22.6 mA...
  • Page 113: Security Lockout

    Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Transient protection The optional transient terminal block prevents damage to the flowmeter from transients induced by lightning, welding, heavy electrical equipment, or switch gears. The transient protection electronics are located in the terminal block. The transient terminal block meets the following specifications: IEEE C62.41 - 2002 Category B 3 kA crest (8 X 20 μs)
  • Page 114: Flow Calibration

    Table A-2 Table A-3. Velocities are referenced in schedule 40 pipe. Velocity range of the Rosemount 8800DW is the same as Rosemount 8800DF. Specifications and Reference Data Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 115 Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Table A-6. Water Flow Rate Limits for the Rosemount 8800D and 8800DR Process line size Minimum and maximum measurable water flow rates (Inches/ DN) Vortex meter Gallons/minute Cubic meters/hour 0.5/ 15 8800DF005 1.76 to 23.7...
  • Page 116 Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Table A-7. Air Flow Rate Limits at 59 °F (15 °C) Minimum and maximum air flow rates for line sizes inch/DN 15 through 1 inch/DN 25 Inch/DN 15 1 Inch/DN 25 Rosemount Rosemount Rosemount...
  • Page 117 Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Table A-8. Air Flow Rate Limits at 59 °F (15 °C) Minimum and maximum air flow rates for line sizes 1 inch/DN 40 through 2 inch/DN 50 1½ Inch/DN 40 2 Inch/DN 50 Rosemount Rosemount...
  • Page 118 Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Table A-9. Air Flow Rate Limits at 59 °F (15 °C), 14.7 psia (1.01 bar-a) Minimum and maximum air flow rates for line sizes 3 inch/DN 80 through 4 inch/DN 100 3 Inch/DN 80 4 Inch/DN 100 Rosemount...
  • Page 119 Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Table A-10. Air Flow Rate Limits at 59 °F (15 °C), 14.7 psia (1.01 bar-a) Minimum and maximum air flow rates for line sizes 6 inch/DN 150 through 8 inch/DN 200 6 Inch/DN 150 8 Inch/DN 200 Rosemount...
  • Page 120 Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Table A-11. Air Flow Rate Limits at 59 °F (15 °C), 14.7 psia (1.01 bar-a) Minimum and maximum air flow rates for line sizes 10 inch/DN 250 through 12 inch/DN 300 10 Inch/DN 250 12 Inch/DN 300 Rosemount...
  • Page 121 Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Table A-12. Saturated Steam Flow Rate Limits (Assumes Steam Quality is 100%) Minimum and maximum saturated steam flow rates for line sizes inch/DN 15 through 1 inch/DN 25 ½ Inch/DN 15 1 Inch/DN 25 Rosemount Rosemount...
  • Page 122 Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Table A-13. Saturated Steam Flow Rate Limits (Assumes Steam Quality is 100%) Minimum and maximum saturated steam flow rates for line sizes 1 inch/DN 40 through 2 inch/DN 50 1½...
  • Page 123 Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Table A-14. Saturated Steam Flow Rate Limits (Assumes Steam Quality is 100%) Minimum and maximum saturated steam flow rates for line sizes 3 inch/DN 80 through 4 inch/DN 100 3 Inch/DN 80 4 Inch/DN 100 Rosemount...
  • Page 124 Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Table A-15. Saturated Steam Flow Rate Limits (Assumes Steam Quality is 100%) Minimum and maximum saturated steam flow rates for line sizes 6 inch/DN 150 through 8 inch/DN 200 6 Inch/DN 150 8 Inch/DN 200 Rosemount...
  • Page 125 Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Table A-16. Saturated Steam Flow Rate Limits (Assumes Steam Quality is 100%) Minimum and maximum saturated steam flow rates for line sizes 10 inch/DN 250 through 12 inch/DN 300 10 Inch/DN 250 12 Inch/DN 300 Rosemount...
  • Page 126: Performance Specifications

    Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Performance specifications The following performance specifications are for all Rosemount models except where noted. Digital performance specifications applicable to Digital HART output. Flow accuracy Includes linearity, hysteresis, and repeatability. Liquids—for Reynolds Numbers over 20000 Digital and Pulse Output ±0.65% of rate...
  • Page 127: Mass Flow Accuracy For Temperature Compensated Steam Mass Flow

    Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Mass flow accuracy for temperature compensated steam mass flow 2.0% of rate (Typical) Repeatability ± 0.1% of actual flow rate Mass flow accuracy for temperature compensated liquid mass flow (water) ±...
  • Page 128: Ambient Temperature Effect

    Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Ambient temperature effect Digital and pulse outputs No effect Analog output ±0.1% of span from –58 to 185 °F (–50 to 85 °C) Vibration effect An output with no process flow may be detected if sufficiently high vibration is present. The meter design will minimize this effect, and the factory settings for signal processing are selected to eliminate these errors for most applications.
  • Page 129: Magnetic-Field Interference

    Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 HART analog Output error less than ±0.025% of span with twisted pair from 80-1000 MHz for radiated field strength of 10 V/m; 1.4 - 2.0 GHz for radiated field strength of 3 V/m; 2.0 - 2.7 GHz for radiated field strength of 1 V/m.
  • Page 130 Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Non-wetted materials Housing Low-copper aluminum (FM Type 4X, CSA Type 4X, IP66) Optional SST housing Paint Polyurethane Cover O-rings Buna-N Flanges 316/316L lap joint Temperature sensor (MTA option) Type-N Thermocouple Process-wetted materials Meter body CF-3M cast stainless, N06022 wrought Nickel Alloy and CW2M cast Nickel Alloy.
  • Page 131: Process Connections

    Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Process connections Mounts between the following flange configurations: ASME B16.5 (ANSI): Class 150, 300, 600, 900, 1500 EN 1092-1: PN 10, 16, 25, 40, 63, 100, 160 JIS: 10K, 20K, and 40K Weld-end: Schedule 10, Schedule 40, Schedule 80, Schedule 160 Mounting Integral (standard)
  • Page 132: Pipe Length Requirements

    Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Figure A-1. Rosemount 8800 Vortex Flowmeter Ambient/Process Temperature Limits Shows combinations of ambient and process temperatures needed to remain at or below 185°F (85°C) housing temperature 200 (93) 180 (82) 160 (71) 185°F Housing 140 (60)
  • Page 133: Dimensional Drawings

    Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Dimensional drawings Figure A-2. Flanged-Style Flowmeter—Line Sizes - through 12-in. (15 through 300 mm) Terminal Cover 3.40 (86) 2.56 2.85 (65) (72) 1.10 (28) Diameter 3.06 (78) 1.00 (25.4) Display Option Diameter B Without MTA option...
  • Page 134 Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Table A-18. Flanged-Style Flowmeter—Line Sizes 1/2- through 2-in. (15 through 50 mm) Nominal Size Flange Face-to-face A A-ANSI RTJ Diameter B Weight Inch (mm) Rating Inch (mm) Inch (mm) Inch (mm) Inch (mm) lb (kg)
  • Page 135 Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Table A-19. Flanged-Style Flowmeter—Line Sizes 3- through 6-in. (80 through 150mm) (refer to Figure A-2) Nominal size Flange Face-to-face A A ANSI RTJ Diameter B C inch inch (mm) rating inch (mm) inch (mm)
  • Page 136 Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Table A-20. Flanged-Style Flowmeter—Line Sizes 8- through 12-in. (200 through 300mm) (refer to Figure A-2) Nominal size Flange Face-to-face A A ANSI RTJ Diameter B C inch inch (mm) rating inch (mm) inch (mm)
  • Page 137 Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 ™ Figure A-3. Rosemount 8800DR Reducer Vortex Flowmeter—Line Sizes 1- through 12-in. (25 through 300 mm 3.40 2.85 (86) (72) 1.10 Terminal Cover 2.56 (28) (65) Diameter 1.00 3.06 (78) (25) Display Option Diameter B...
  • Page 138 Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Table A-21. Reducer Flowmeter—Line Sizes 1- through 3-in. (25 through 80 mm) Nominal size Flange Face-to-face A A-ANSI RTJ Diameter B Weight inch (mm) rating inch (mm) inch (mm) inch (mm) inch (mm) lb (kg)
  • Page 139 Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Table A-22. Reducer Flowmeter—Line Sizes 4- through 12-in. (100 through 300mm) (refer to Figure A-3) Nominal size Flange Face-to-face A A ANSI RTJ Diameter B inch (mm) rating inch (mm) inch (mm) inch (mm) C inch (mm)
  • Page 140 Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Figure A-4. Wafer-Style—Line Sizes - through 8-in. (15 through 200 mm) 3.40 Terminal Cover (86) 2.00 2.00 (51) 2.56 (51) (65) 2.85 1.10 (72) (28) 1.00 (25) Diameter 3.06 (78) Display Option Diameter D...
  • Page 141 Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Figure A-5. Vortex Dual-Sensor Style Flowmeter—Line Sizes - through 3-in. (15 through 80 mm) Electrical Connection Terminal Cover 3.40 2.00 2.00 (86) (51) (51) 2.56 2.85 (65) (72) 1.10 (28) 3.06 1.00...
  • Page 142 Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Table A-24. Vortex Dual-Sensor Style Flowmeter—Line Sizes - through 3-in. (15 through 80 mm) Nominal size Flange Face-to-face A A ANSI RTJ Diameter B Weight inch (mm) rating inch (mm) inch (mm) inch (mm) inch (mm)
  • Page 143 Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Figure A-6. Vortex Dual-Sensor Style Flowmeter—Line Sizes 4- through 12-in. (100 through 300 mm) Diameter B Table A-25. Vortex Dual-Sensor Style Flowmeter—Line Sizes 4- through 12-in. (100 through 300 mm) Nominal size Flange Face-to-face A...
  • Page 144 Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Table A-25. Vortex Dual-Sensor Style Flowmeter—Line Sizes 4- through 12-in. (100 through 300 mm) Nominal size Flange Face-to-face A A ANSI RTJ Diameter B Weight inch (mm) rating inch (mm) inch (mm) inch (mm) inch (mm)
  • Page 145 Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Figure A-7. Vortex Weld-End Style Flowmeter—Line Sizes - through 4-in. (15 through 100 mm) Electrical Connection Terminal Cover 3.40 2.00 (86) (51) 2.00 2.85 2.56 (51) (72) (65) 1.10 (28) ∅...
  • Page 146 Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Figure A-8. Remote Mount Transmitters 3.12 Terminal Cover 3.40 (80) (86) 2.00 (51) 2.56 2.85 (65) (72) 1.10 (28) ∅ 3.06 (78) 1.00 (25,4) Display 6.77 Option (172) 5.77 (147) ∅...
  • Page 147 Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Figure A-9. Remote Mount Wafer-Style Flowmeters—Line Sizes - through 8-in. (15 through 200 mm) -14 NPT (For Remote Cable Conduit) Table A-27. Rosemount 8800D Wafer-Style Meter Nominal size inch E Wafer style inch (mm) (mm)
  • Page 148 Specifications and Reference Data Reference Manual May 2016 00809-0100-4004, Rev DC Figure A-10. Flanged-and Dual Sensor Flanged-Style Remote Mount Flowmeters—Line Sizes - through 12-in. (15 through 300 mm) -14 NPT (For Remote Cable -14 NPT (For Remote Cable Conduit) Conduit) Dual-Sensor Style Flowmeter Flanged Flowmeter Dimensions are in inches (millimeters).
  • Page 149 Reference Manual Specifications and Reference Data 00809-0100-4004, Rev DC May 2016 Specifications and Reference Data Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 150: B.1 Overview

    Emerson Process Management—Eden Prairie, Minnesota, B.5 European Pressure Equipment Directive (PED) Emerson Process Management BV - Ede, The Netherlands Emerson Process Management Flow Technologies Co., Ltd - Rosemount 8800D Vortex Flowmeter Line Size 40 mm to Nanjing, Jiangsu Province, P.R. China...
  • Page 151: Hazardous Location Certifications

    Reference Manual Product Certifications 00809-0100-4004, Rev DC May 2016 B.6 Hazardous Location Canadian Standards Association (CSA) Certifications Explosion-Proof for Class I, Division 1, Groups B, C, and D; B.6.1 North American Certifications Dust-ignition proof for Class II and Class III, Division 1, Groups E, F, and G Factory Mutual (FM) Class I, Zone 1, Ex d[ia] IIC...
  • Page 152 Product Certifications Reference Manual May 2016 00809-0100-4004, Rev DC ATEX FISCO ATEX Flameproof Certification EN 60079-0: 2009 Certification No. Baseefa05ATEX0084X ATEX Marking EN 60079-1: 2007 II 1 G Ex ia IIC T4 Ga (-60 °C ≤ Ta ≤ 60 °C) EN 60079-11: 2012 0575 EN 60079-26: 2007...
  • Page 153: B.6.3 International Iecex Certifications

    Reference Manual Product Certifications 00809-0100-4004, Rev DC May 2016 B.6.3 International IECEx Certifications Special Conditions for Safe Use (X): 1. When fitted with 90V transient suppressors (T1 Intrinsic Safety Option), the equipment is not capable of passing the 500V isolation test. This must be taken into account IEC 60079-0: 2011 upon installation.
  • Page 154: Chinese Certifications (Nepsi)

    152 m. The cable shall also be provided by Certification No. GYJ12.1106X Rosemount Inc., or by Emerson Process Management Ex ia IIC T4 Ga (-60 °C ≤ Ta ≤ + 70 °C) 4-20 mA HART Flow Technologies Co., Ltd.
  • Page 155 Reference Manual Product Certifications 00809-0100-4004, Rev DC May 2016 2. When transient protection terminal block applied to Certification No. GYJ12.1107X Ex nA ic IIC T5 Gc (- 50 °C ≤ T ≤ +70 °C) 4-20 mA HART this product, during installation, users shall comply Ex nA ic IIC T5 Gc (- 50 °C ≤...
  • Page 156: Brazilian Certifications (Inmetro)

    Product Certifications Reference Manual May 2016 00809-0100-4004, Rev DC B.6.5 Brazilian Certifications (INMETRO) Special Conditions for Safe Use (X): 1. For information regarding the dimensions of the I. S. Certification flameproof joints, the manufacturer shall be contacted. ABNT NBR IEC 60079-0: 2013 2.
  • Page 157 Reference Manual Product Certifications 00809-0100-4004, Rev DC May 2016 Special conditions for safe use (X): Inductance and capacitance of intrinsically safe circuits of  flowmeters with Ex marking 0Ex ia IIC T4 Ga X, with given For flowmeters with Ex marking 0Ex ia IIC T6 Ga X, Ga / ...
  • Page 158 Product Certifications Reference Manual May 2016 00809-0100-4004, Rev DC Figure B-1. FM Intrinsic Safety Field Circuit Configurations for HART and Fieldbus (Sheet 1 of 5) Product Certifications Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 159 Reference Manual Product Certifications 00809-0100-4004, Rev DC May 2016 Figure B-2. FM Intrinsic Safety Field Circuit Configurations for HART and Fieldbus (Sheet 2 of 5) Product Certifications Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 160 Product Certifications Reference Manual May 2016 00809-0100-4004, Rev DC Figure B-3. FM Intrinsic Safety Field Circuit Configurations for HART and Fieldbus (Sheet 3 of 5) Product Certifications Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 161 Reference Manual Product Certifications 00809-0100-4004, Rev DC May 2016 Figure B-4. FM Intrinsic Safety Field Circuit Configurations for HART and Fieldbus (Sheet 4 of 5) Product Certifications Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 162 Product Certifications Reference Manual May 2016 00809-0100-4004, Rev DC Figure B-5. FM Intrinsic Safety Field Circuit Configurations for HART and Fieldbus (Sheet 5 of 5) Product Certifications Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 163 Reference Manual Product Certifications 00809-0100-4004, Rev DC May 2016 Figure B-6. CSA Intrinsic Safety Approval for HART and Fieldbus (Sheet 1 of 8) Product Certifications Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 164 Product Certifications Reference Manual May 2016 00809-0100-4004, Rev DC Figure B-7. CSA Intrinsic Safety Approval for HART and Fieldbus (Sheet 2 of 8) Product Certifications Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 165 Reference Manual Product Certifications 00809-0100-4004, Rev DC May 2016 Figure B-8. CSA Intrinsic Safety Approval for HART and Fieldbus (Sheet 3 of 8) Product Certifications Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 166 Product Certifications Reference Manual May 2016 00809-0100-4004, Rev DC Figure B-9. CSA Intrinsic Safety Approval for HART and Fieldbus (Sheet 4 of 8) Product Certifications Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 167 Reference Manual Product Certifications 00809-0100-4004, Rev DC May 2016 Figure B-10. CSA Intrinsic Safety Approval for HART and Fieldbus (Sheet 5 of 8) Product Certifications Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 168 Product Certifications Reference Manual May 2016 00809-0100-4004, Rev DC Figure B-11. CSA Intrinsic Safety Approval for HART and Fieldbus (Sheet 6 of 8) Product Certifications Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 169 Reference Manual Product Certifications 00809-0100-4004, Rev DC May 2016 Figure B-12. CSA Intrinsic Safety Approval for HART and Fieldbus (Sheet 7 of 8) Product Certifications Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 170 Product Certifications Reference Manual May 2016 00809-0100-4004, Rev DC Figure B-13. CSA Intrinsic Safety Approval for HART and Fieldbus (Sheet 8 of 8) Product Certifications Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 171 Reference Manual Product Certifications 00809-0100-4004, Rev DC May 2016 Product Certifications Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 172: Safety Messages

    Electronics Verification Reference Manual May 2016 00809-0100-4004, Rev DC Appendix C Electronics Verification Safety messages ............page 163 Electronics verification .
  • Page 173: Electronics Verification

    Reference Manual Electronics Verification 00809-0100-4004, Rev DC May 2016 Electronics verification Electronics verification of the Model 8800D can be done by either utilizing the internal signal simulation capability or by applying an external signal source to the “TEST FREQ IN” and “GROUND”...
  • Page 174: Electronics Verification Using An External Frequency Generator

    Electronics Verification Reference Manual May 2016 00809-0100-4004, Rev DC Note To manually disconnect the sensor for precautionary measures, see Replacing the electronics housing on page 5-80 for details. Figure C-14. Profile of Varying Flow Simulation Signal A. Max Flow Rate B.
  • Page 175 Reference Manual Electronics Verification 00809-0100-4004, Rev DC May 2016 Select the desired sinewave generator frequency. Verify the generator frequency against the frequency displayed on the Field Communicator or AMS Device Manager. 2, 2, 5, 1, 2 FastKeys Exit the Flow Simulation Mode. Reconnect the LCD indicator option (if applicable) to the electronics board by replacing and tightening the two screws.
  • Page 176: Calculating Output Variables With Known Input Frequency

    Electronics Verification Reference Manual May 2016 00809-0100-4004, Rev DC C.2.5 Calculating output variables with known input frequency Use the following equations with a known input frequency for verification of a flow rate or 4–20 mA output within a given calibrated range. Select the proper equation depending on if you are verifying a flow rate, mass flow rate, 4–20 mA output, or special units.
  • Page 177: Unit Conversion Table (User Units To Gps)

    Reference Manual Electronics Verification 00809-0100-4004, Rev DC May 2016 Unit conversion table (user units to GPS) UseTable C-1 when converting units of measure. Table C-1. Unit Conversions Units (actual) Conversion factor gal/s 1.00000E+00 gal/m 1.66667E-02 gal/h 2.77778E-04 Impgal/s 1.20095E+00 Impgal/m 2.00158E-02 Impgal/h 3.33597E-04...
  • Page 178: Examples

    Electronics Verification Reference Manual May 2016 00809-0100-4004, Rev DC Examples The following examples illustrate the flowrate calculations that may be necessary for your application. There are water, saturated steam, and natural gas applications represented in the examples. The first set of three examples is in English units. The second set of three examples is in SI units.
  • Page 179 Reference Manual Electronics Verification 00809-0100-4004, Rev DC May 2016 Example 2 (English units) Fluid = Saturated Steam = 40000 lb/hr Line size = 3 inch = 0 lb/hr ρ Line pressure = 500 psia (Table C-1 on page168) ρ Operating = 467 °F Density ( = 1.078 lb/cu-ft...
  • Page 180 Electronics Verification Reference Manual May 2016 00809-0100-4004, Rev DC Example 3 (English units) Fluid = Natural gas = 5833 SCFM Line size = 3 inch = 0 SCFM Line pressure = 140 psig /sp. units factor (from Table C-1 on page168) ρ...
  • Page 181: Units

    Reference Manual Electronics Verification 00809-0100-4004, Rev DC May 2016 C.3.2 SI units Example 1 (SI units) Fluid = Water = 2000 lpm Line size = 80 mm = 0 lpm Line pressure = 700 kPas = 4.40287E-03 (from Table C-1 on page 168) Operating = 60 °F...
  • Page 182 Electronics Verification Reference Manual May 2016 00809-0100-4004, Rev DC Example 2 (SI units) Fluid = Saturated Steam = 3600 kg/hr Line size = 80 mm = 0 kg/hr ρ Line pressure = 700 kPas (from Table C-1 on page168) ρ Operating = 170 °F Density(...
  • Page 183 Reference Manual Electronics Verification 00809-0100-4004, Rev DC May 2016 Example 3 (SI units) Fluid = Natural gas = 10,000 NCMH Line size = 80 mm = 0 NCMH Line pressure = 1000 KPas /sp. units factor (from Table C-1 on page168) ρ...
  • Page 184 HART® Fast Keys Reference Manual May 2016 00809-0100-4004, Rev DC ® Appendix D HART Fast Keys ™ Table D-1. Fast Keys for the Rosemount 8800D HART 5 Device Revision 1 and Device Revision 2 (DD Revision 1) Function Fast Keys Function Fast Keys Alarm Jumper...
  • Page 185 Reference Manual HART® Fast Keys 00809-0100-4004, Rev DC May 2016 Figure D-1. Rosemount 8800D HART 5 Menu Tree for Device Revision 1 and Device Revision 2 (DD Revision 1) 1. Process 1. PV 1. Volumetric Flow 1. Volume Flow 1. Base Volume Unit Variables 2.
  • Page 186 HART® Fast Keys Reference Manual May 2016 00809-0100-4004, Rev DC Table D-2. Fast Keys for Rosemount 8800D HART 5 Device Revision 2. (DD Revision 3) Function Fast Key Function Fast Key Alarm Direction 1, 3, 1, 3, 2 Percent of Range 3, 4, 3, 2 Analog Output 3, 4, 3, 1...
  • Page 187 Reference Manual HART® Fast Keys 00809-0100-4004, Rev DC May 2016 Figure D-2. Menu Tree for the Rosemount 8800D HART 5 Device Revision 2 (DD Revision 3) 1 Device Information 1 Tag 1 Check Status 1 Universal Revision 1 Overview 1 Device Information 2 Manufacturer 2 Primary Purpose 2 Sensor...
  • Page 188 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
  • Page 189: Global Headquarters

    Standard Terms and Conditions of Sale can be found at: www.Emerson.com/en-us/pages/Terms-of-Use.aspx Middle East and Africa Regional Office The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount and Rosemount logotype are trademarks of Emerson Process Emerson Process Management Management.