Thank You for Purchasing The Product Thank you for purchasing Autonics products. Please familiarize yourself with the information contained in the Safety Considerations section before using this product. This manual contains information about the porduct and its proper use, and should be kept in a place where it will be easy to access.
(www.autonics.com) to download a copy. • The manual’s content may vary depending on changes to the product’s software and other unforeseen developments within Autonics, and is subject to change without prior notice. Upgrade notice is provided through our homepage. • We contrived to describe this manual more easily and correctly. However, if there are any corrections or questions, please notify us these on our website.
Manual Symbols Failure to follow instructions can result in serious injury or death. Failure to follow instructions can lead to a minor injury or product damage. Supplementary information for a particular feature. An example of the concerned feature’s use. Important information of the concerned feature’s use. Manual Symbols ...
1. Modbus RTU Protocol 1.1. Modbus The Modbus industrial protocol was developed in 1979 to make communication possible between automation devices. The protocol has expanded to include implementations over serial, TCP/IP, and the user datagram protocol (UDP). Today, it is a common protocol used by countless devices for simple, reliable, and efficient communication across a variety of modern networks.
Slave Address Function Byte Count Data Data Data Error Check (CRC16) 1 Byte 1 Byte 1 Byte 2 Byte 2 Byte 2 Byte 2 Byte • Calculation range of CRC16 = Slave Address to Data 12 Autonics | TK Series...
Write function if you use the slave (device) connecting with external devices such as PLC, Graphic Panel, except in the case of download that presets the minimum/maximum or basic value of parameter by Input specifications in PC Loader Program. 14 Autonics | TK Series...
1.2.8. Exception Response - Error Code If occurs an error, send a response command and transmit each Exception Code after set(1) the highest level bit of received command(Function). Slave Address Function + 80H Exception Code Error Check (CRC16) 1 Byte 1 Byte 1 Byte 2 Byte...
The parameter address can be somewhat different for each manufacturer because the regulation for a starting number is not defined. Autonics Modbus address is started at ‘1’ for decimal (DEC) address, and at ‘0’ for hexadecimal (HEX). So, decimal (DEC) address values are +1 for Hex (HEX) address values.
100012(000B) MAN Indicator Manual Control Indicator 0: OFF, 1: ON 100013(000C) DI-1 Input DI-1 Input Status 0: OFF, 1: ON 100014(000D) DI-2 Input DI-2 Input Status 0: OFF, 1: ON 100015 to 100050 Reserved 18 Autonics | TK Series...
2.3. Read Input Registers (Func 04) No(Address) Parameter Description Default 300001 to 300100 Reserved 300101(0064) Product Number H 300102(0065) Product Number L 300103(0066) Hardware Version 300104(0067) Software Version 300105(0068) Model Name 1 “TK” 300106(0069) Model Name 2 “4” 300107(006A) Model Name 3 “14”...
Page 20
Heating Side MV 0 to 1000: H0.0 to H100 301006(03ED) C-MV Cooling Side MV 0 to 1000: C0.0 to C100 301007(03EE) Refer to 301007 (03EE) Bit data 301008(03EF) Heater Current Value Monitoring 0.0 to 50.0 20 Autonics | TK Series...
Page 21
301007 (03EE) Bit data Parameter Description Bit 0 ℃ Indicator Unit Indicator 0: OFF, 1: ON Bit 1 ℉ Indicator Unit Indicator 0: OFF, 1: ON Bit 2 % Indicator Unit Indicator 0: OFF, 1: ON Bit 3 OUT1 Indicator Control Output 1 Indicator 0: OFF, 1: ON Bit 4...
℃/℉/- 400002(0001) H-MV Heating MV 0 to 1000: H0.0 to H100 400003(0002) C-MV Cooling MV 0 to 1000: C0.0 to C100 400004(0003) Auto/Manual Control 0: AUTO 0: AUTO, 1: MAN 400005 to 400050 Reserved 22 Autonics | TK Series...
2.4.2. Parameter 1 Group (Func: 03/06/16) No(Address) Parameter Description Default 400051(0032) Control Output Run/Stop 0: RUN 0: RUN, 1: STOP 400052(0033) SV-N Multi SV Number 0: SV-0 0: SV-0, 1: SV-1, 2: SV-2, 3: SV-3 400053(0034) CT-A Heater Current Monitoring 0~500: 00.0~50.0 (display range) 400054(0035) AL1.L...
Page 24
Absolute Value Alarm: Within the display range ℃/℉/- 400063(003E) AL3.H Alarm Output 3 High-limit Set Value 1550 Deviation Alarm: -F.S. to F.S. Absolute Value Alarm: Within the display range ℃/℉/- 400064 to 400100 Reserved 24 Autonics | TK Series...
2.4.3. Parameter 2 Group (Func: 03/06/16) No(Address) Parameter Description Default 400101(0064) Auto-tuning Run/Stop 0: OFF 0: OFF, 1: ON 400102(0065) Heating Proportional Band 010.0 1 to 9999: 000.1 to 999.9 ℃/℉/% 400103(0066) Cooling Proportional Band 010.0 1 to 9999: 000.1 to 999.9 ℃/℉/% 400104(0067) Heating Integral Time...
Page 26
L-MV+0.1 to 100.0 MV High-limit Set Value 100.0 [Heating&Cooling Control] 000.0 to 100.0 400116(0073) RAMU Ramp Up Change Rate 0 to 999: 000 to 999 (Temp.H, Analog) 0 to 9999: 000.0 to 999.9 (Temp.L) ℃/℉/Digit 26 Autonics | TK Series...
Page 27
No(Address) Parameter Description Default 400117(0074) RAMD Ramp Down Change Rate 0000 0 to 999: 000 to 999 (Temp.H, Analog) 0 to 9999: 000.0 to 999.9 (Temp.L) ℃/℉/Digit 400118(0075) R.UNT Ramp Time Unit 1: MIN 0: SEC, 1: MIN, 2: HOUR 400119 to 400150 Reserved 2.4.
Digit 400160(009F) MAV.F Input Digital Filter 000.1 1 to 1200: 000.1 to 120.0 Sec. 400161(00A0) L-SV SV Low-limit Input Low-limit Value(L-SC) to -200 Set Value H-SV-1Digit ℃/℉ Input Low-limit Value(L-SC) to 000.0 H-SV-1Digit %F.S. 28 Autonics | TK Series...
Page 30
No(Address) Parameter Description Default 400172(00AB) Cooling [Relay output model] 020.0 Control Time 000.1 to 120.0 Sec. [SSR drive output model] 002.0 000.1 to 120.0 Sec. [Current output model] 002.0 001.0 to 120.0 Sec. 30 Autonics | TK Series...
Page 31
Input Type and Using Range Setting Input type Decimal Display Use range (℃) Use range (℉) K (CA) KCaH -200 ~ 1,350 -328 ~ 2,462 K (CA) KCaL -199.9 ~ 999.9 -199.9 ~ 999.9 J (IC) JIcH -200 ~ 800 -328 ~ 1,472 J (IC) JIcL...
0 to 3600: 0000 to 3600 Sec. 400212(00D3) A2.OF Alarm Output 2 OFF Delay Time 0000 0 to 3600: 0000 to 3600 Sec. 400213(00D4) LBA.T LBA Time 0000 0 to 9999: 0000 to 9999 Sec. 32 Autonics | TK Series...
Page 33
No(Address) Parameter Description Default 400214(00D5) Reserved 400215(00D6) LBA.B LBA Band 1 to 9999: 000 to 999 (Temp.H) ℃/℉ LBA Band 002.0 1 to 9999: 000.0 to 999.9 (Temp.L) ℃/℉ LBA Band 000.2 1 to 9999: 000.0 to 100.0 (Analog) %F.S. 400216(00D7) AO.M1 Analog Transmission Output 1 Mode...
2.4.6. Parameter 5 Group (Func: 03/06/16) No(Address) Parameter Description Default 400251(00FA) MT.SV Multi SV 0: 1 0: 1, 1: 2, 2: 4 400252(00FB) DI-K Digital Input Key 0: STOP 0: STOP, 1: AlRE, 2: AT, 3: OFF 400253(00FC) DI-1 DI-1 Input Terminal Function 0: OFF 0: OFF, 1: STOP, 2: AlRE, 3: MAN 4: MT.SV 400254(00FD)
Page 36
0: OFF, 1: ON 400267(010A) LC.P5 Parameter 5 Group Lock 0: OFF 0: OFF, 1: ON 400268(010B) Password Setting 0000 0000: OFF 0002 to 9999: Password Set Range (※ 0001: read-only password) 400269 to 400300 Reserved 36 Autonics | TK Series...
2.4.7. User parameter group (Func: 03/06/16) No(Address) Parameter Set Range Default 400301(012C) PARU>Parameter 0 Set range by each parameter 400302(012D) PARU>Parameter 1 Set range by each parameter 400303(012E) PARU>Parameter 2 Set range by each parameter 400304(012F) PARU>Parameter 3 Set range by each parameter 400305(0130) PARU>Parameter 4 Set range by each parameter...
Page 38
Dimensions or specifications on this manual are subject to change and some models may be discontinued without notice. www.autonics.com...