5.
Wiring Diagrams (continued)
SN200 Wiegand UL294/TAMPER Configuration Application Diagram #1
Note: Tamper will trigger when reader is removed from door and tamper wiring is connected at the panel.
Reader Electronics Requires 12VDC Filtered and Regulated
Reader**
Actuator (ET)
*UL294, S319, & BHMA A156.25 not applicable to SN200 with Non-
UL294 Configuration option
**Maximum AVG - RMS current draw during continuous card reads
Not evaluated by UL
Peak - highest instantaneous current draw during RF communication
12/24VDC System
12 Conductor
ElectroLynx Harness
From McKinney
IMPORTANT: Pin 7 must be tied to earth ground in the access
*
control panel.
• Wiring in accordance with the NEC, ANSI/NFPA 70
• Fail secure installations are subject to approval of local AHJ
• Fail secure installations shall permit use of Listed panic
hardware to allow emergency exit from the protected area
Failure to follow proper ESD safe grounding
procedures could lead to equipment failure.
UL294 is a United States based standard.
FM563 11/2024
12V
Average
Peak
75mA
250mA
15mA
500mA
QC12 Electric
Hinge From
McKinney
SN200/210
9600
Series Lock
10
SN200 Wiegand SN210 OSDP
24V
Average
Peak
n/a
n/a
15mA
500mA
120 VAC
H N G
Input
12-24VDC
- +
READER NEG - Black, 1
READER POS - Red, 2
DATA_1 - White, 3
DATA_0 - Green, 4
RX (NO) - Orange, 5
RX (COM) - Blue, 6
*EARTH GROUND - Brown, 7
TAMPER - Yellow, 8
LOCK NEG - Violet, 9
LOCK POS - Gray, 10
DPS (NC) - Pink, 11
DPS (COM) - Tan, 12
Unsupervised Open
Collector Tamper
Copyright © 2020 - 2024, ASSA ABLOY Access and Egress Hardware Group, Inc. All rights
reserved. Reproduction in whole or in part without the express written permission of
ED5000 Series Exit Device
Installation Instructions
Power Supply
12VDC
(By Others)
- +
Electrical
(-)
12VDC
(+)
Access
DATA_1
Control
DATA_0
Panel
RX (NO)
Use (NC) for
(by Others)
RX (COM)
Fail Safe
Operation
DPS
DPS
(NO) Fail
Secure
Operation
Panel Circuitry
5VDC
Input
1KΩ
Connection
(+)
1KΩ
Input
Connection (-)
1KΩ
1-800-810-9473 • techsupport.corbinrusswin@assaabloy.com
ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
Lock Relay
A to D Converter