Technical manual
SNI01C, SNI02C, SNI03C
Conventional fire detectors to be
connected to a remote LED
1
DECLARATION OF CONFORMITY
AND PERFORMANCE
SNI01C: 2831-CPR-F4359
SNI02C: 2831-CPR-F4358
2831 20
SNI03C: 2831-CPR-F4357
SNI01C
1163a/03
2
DESCRIPTION
SNI01C is an optical smoke detector.
SNI02C is a heat detector.
SNI03C is a heat and optical smoke detector.
4
TECHNICAL DATA
Model
General features
Protection class
Alarm threshold
Operating voltage
Consumption at power voltage, idle mode
Addressee for this information:
SNI02C
SNI03C
1163c/07
1163p/01
Smoke
Heat
Power supply
Maximum operating voltage
Minimum power supply
User |
Installer
3
WARNINGS
The maximum number of detectors that can be connected
to a line depends on the control unit model and it is stated
by the local regulations.
According to European laws, only 32 detectors can be in-
stalled on one line.
The total maximum power consumption on a single line shall
not be greater than the maximum current available on the
same line.
Keep plastic protections until works are finished.
Do not paint the detector.
Do not install detectors in areas where air speed is
above 5 km/h.
The detector does not provide early warnings for fire events
and cannot detect gas, fire particles or flames.
SNI01C
SNI02C
IP 43
0,08÷0,12
-
-
A1R
24
33,0
9,0
0,045
0,035
1 1 1
SNI03C
0,08÷0,13
dB/m
A2
V
V
V
0,050
mA