Advertisement
Before the SQ/SQE pump is lowered into the borehole, this page should be filled in with the relevant nameplate data.
These installation and operating instructions must be kept in a dry place near the installation site for reference purposes.
The SQ and SQE pumps are designed for pumping thin, clean, non-aggressive, non-explosive liquids, not containing solid particles or fibres.
Typical applications:
The SQE-NE pumps are designed for pumping thin, clean, non-explosive liquids, not containing solid particles or fibres.
These pumps are suitable for pumping contaminated or hydrogen-carbonate containing groundwater, e.g. from
The SQE-NE pumps can also be used for sampling and monitoring and to some extent for incorporation in water treatment systems.
Information applying to all pump types
The maximum sand content of the water must not exceed 50 g/m3. A larger sand content will reduce the life of the pump and increase the risk of blocking.
Note
If liquids with a viscosity higher than that of water are to be pumped, please contact Grundfos.
pH values
SQ and SQE: 5 to 9.
SQE-NE: Please contact Grundfos.
Liquid temperature
The temperature of the pumped liquid must not exceed 35°C.
Supply voltage
1 x 200-240 V - 10%/+ 6%, 50/60 Hz, PE. Operation via generator: As a minimum, the generator output must be equal to the motor P1 [kW] + 10%.
Starting current
The motor starting current is equal to the highest value stated on the motor nameplate.
Power factor
PF = 1.
Motor liquid
Type SML 3.
Motor cable
1.5 m, 3 x 1.5 mm2, PE.
Liquid temperature
Maximum 35°C.
Pump outlet size
SQ 1, SQ 2, SQ 3: Rp 1 1/4.
SQ 5, SQ 7: Rp 1 1/2.
Pump diameter
74 mm.
Borehole diameter
Minimum 76 mm.
Installation depth
Maximum 150 m below static water level.
See also Installation depths section.
Net weight
Maximum 6.5 kg.
Storage temperature: -20°C to +60°C.
If the pump has to be stored after use, it must be stored on a frost-free location or it must be ensured that the motor liquid is frost-proof.
The motor must not be stored without being filled with motor liquid.
The sound pressure level of the pump is lower than the limiting values stated in the EC Council Directive 2006/42/EC relating to machinery.
Grundfos MS 3 and MSE 3 submersible motors have water-lubricated slide bearings. No additional lubrication is required.
The submersible motors are factory-filled with a special Grundfos motor liquid (type SML 3), which is frost-proof down to - 20°C and preserved to prevent the growth of bacteria.
The level of motor liquid is decisive for the operating life of the bearings and consequently the life of the motor.
If for any reason the motor liquid has been drained or lost, the motor must be refilled with Grundfos motor liquid SML 3.
To refill the motor, proceed as follows:
The pump is now ready for installation.
The pump is suitable for vertical as well as horizontal installation, however, the pump shaft must never fall below the horizontal plane. See fig. 2:
Fig. 2
If the pump is to be installed horizontally, e.g. in a tank, and there is a risk that the pump might be covered by mud, it must be fitted in a flow sleeve.
For installation depths, see Installation depths section.
Figure 3 shows an SQ/SQE pump installed in a borehole. The pump is operating.
Figure 3 illustrates the following:
To ensure sufficient cooling of the motor, it is important to observe the maximum liquid temperature of 35°C under all conditions.
The borehole diameter must be at least 76 mm (approx. 3").
The motor should always be installed above the well screen. If a flow sleeve is used, the pump may be installed freely in the borehole.
Do not let the pump run against a closed discharge pipe for more than 5 minutes. When the discharge pipe is closed, there is no cooling flow and there is a risk of overtemperature in motor and pump.
If the actual temperature of the pumped liquid exceeds the specified value or the operating conditions otherwise fall outside the specified conditions, the pump may stop. Please contact Grundfos.
The electrical connection should be carried out by an authorised electrician in accordance with local regulations.
The supply voltage, rated maximum current and power factor (PF) appear from the motor nameplate.
The required voltage for Grundfos submersible motors, measured at the motor terminals, is - 10%/ + 6% of the nominal voltage during continuous operation (including variation in the supply voltage and losses in cables).
If the pump is connected to an electric installation where an earth-leakage circuit breaker (ELCB) is used as an additional protection, this circuit breaker must trip out when earth fault currents with DC content (pulsating DC) occur.
The earth leakage circuit breaker must be marked with the following symbol: .
Supply voltage
1 x 200-240 V - 10%/+ 6%, 50/60 Hz, PE.
The current consumption can only be measured by means of a true RMS instrument. If other instruments are used, the value measured will differ from the actual value.
On SQ/SQE pumps, a leakage current of 2.5 mA at 230 V, 50 Hz, can typically be measured. The leakage current is proportional to the supply voltage.
The SQE and SQE-NE pumps can be connected to a control box, type CU 300 or CU 301.
The pump must never be connected to a capacitor or to another type of control box than CU 300 or CU 301.
The pump must never be connected to an external frequency converter.
The motor incorporates thermal overload protection and requires no additional motor protection.
The motor incorporates a starter device and can therefore be connected directly to the mains.
Start/stop of the pump will typically be done via a pressure switch. See fig. 4:
Fig. 4
The pressure switch must be rated for the maximum amps of the specific pump size.
Before starting any work on the pump/ motor, make sure that the power supply has been switched off and that it cannot be accidentally switched on.
Do not lower or lift the pump by means of the motor cable.
The loose data plate supplied with the pump should be fixed close to the installation site.
To assemble pump part and motor, proceed as follows:
Motor (P2) [kW] | L [mm] |
0.70 | 120 |
1.15 | 102 |
1.55 | 84 |
1.85 | 66 |
When pump part and motor have been assembled correctly, there must not be a clearance between pump part and motor.
If a pump without non-return valve is required, the valve can be removed as follows:
Note
SQE-NE is supplied without non-return valve.
The non-return valve can be fitted in a Grundfos service workshop.
The cable plug supplied with the motor is factory-greased. Check that the plug is greased correctly.
To fit the cable plug, proceed as follows:
When the plug has been fitted, there must not be a clearance between the motor and the cable plug.
To fit the cable guard, proceed as follows:
Grundfos can supply submersible drop cables for any type of installation.
The cross-section of the submersible drop cable must be large enough to meet the voltage requirements specified in General section.
The table values below are calculated from the following formula:
where q = Cross-section of submersible drop cable [mm2].
I = Rated maximum current of the motor [A].
PF = 1.0.
L = Length of submersible drop cable [m].
ρ = Specific resistance: 0.02 [Ωmm2/m].
U = Nominal voltage [V].
ΔU = Voltage drop [%] = 4%.
The 4% voltage drop is according to IEC 3-64, HD-384 Series.
The calculation gives the following maximum cable lengths at a supply voltage of 240 V:
Max. cable length [m]
Motor (P2) | IN | Cable size | |||||
[kW] | [A] | 1.5 mm2 | 2.1 mm2 /14 AWG | 2.5 mm2 | 3.3 mm2 / 12 AWG | 4 mm2 | 6 mm2 |
0.7 | 5.2 | 80 | 112 | 133 | 176 | 213 | 320 |
1.15 | 8.4 | 50 | 69 | 83 | 109 | 132 | 198 |
1.55 | 11.0 | 37 | 52 | 62 | 82 | 99 | 149 |
1.85 | 12 | 35 | 49 | 58 | 76 | 92 | 139 |
It is recommended to join the submersible drop cable and the motor cable by means of a Grundfos cable termination kit, type KM.
Cable termination kit, type KM
Cross-sectional area | Product number |
4.0 to 6.0 mm 2 | 96021473 |
For larger cross-sections, please contact Grundfos.
If a tool, e.g. a chain pipe wrench, is used when the riser pipe is fitted to the pump, the pump must only be gripped by the pump discharge chamber.
When connecting plastic pipes, a compression coupling should be used between the pump and the first pipe section.
Note
For pumps fitted with plastic pipes, the expansion of the pipes when loaded should be taken into consideration, when deciding on the installation depth of the pump.
Where flanged pipes are used, the flanges should be slotted to take the submersible drop cable. Figure 11 shows a pump installation with indication of:
Cable clips must be fitted every 3 metres. See fig. 11.
When connecting plastic pipes, some slackness must be left between each cable clip as plastic pipes expand when loaded.
Where flanged pipes are used, the cable clips should be fitted above and below each joint.
Maximum installation depth below the static water level: 150 metres. See fig. 11.
Minimum installation depths below the dynamic water level:
It is recommended to secure the pump by an unloaded straining wire. See fig. 11, pos. 2.
Slacken the straining wire so that it becomes unloaded and lock it to the borehole seal by means of wire locks.
The straining wire must not be used for pulling the pump with riser pipe out of the borehole.
Do not lower or lift the pump by means of the motor cable.
Make sure that the well is capable of yielding a minimum quantity of water corresponding to the pump capacity.
Do not start the pump until it is completely submerged in the liquid.
Start the pump and do not stop it until the pumped liquid is completely clean, as otherwise the pump parts and the non-return valve may choke up.
To ensure the necessary cooling of the motor, the pump flow rate should never be set to a value lower than 50 l/h.
If the flow rate suddenly falls, the reason might be that the pump is pumping more water than the borehole can yield. The pump must be stopped and the fault corrected.
The pump dry-running protection is effective only within the recommended duty range of the pump.
The installation must be designed for the maximum pump pressure.
As the pump has a built-in soft starter giving a run-up time of 2 seconds, the pressure at the pressure switch and diaphragm tank during starting will be lower than the pump cut-in pressure set on the pressure switch (pcut-in). This lower pressure is called minimum pressure (pmin).
pmin is equal to the desired minimum pressure at the highest tap + head and head loss in the pipe from the pressure switch and diaphragm tank to the highest tap (pmin = B + C).
See fig. 12:
Fig. 12
Make sure that the selected pump can deliver a pressure higher than Pcut-out + A.
ppre: Precharge pressure of diaphragm tank
pmin: Desired minimum pressure.
pcut-in: Cut-in pressure set on pressure switch.
pcut-out: Cut-out pressure set on pressure switch.
Qmax: Maximum flow at pmin.
Using pmin and Qmax, the minimum diaphragm tank size, precharge pressure and pressure switch settings can be found in the guideline table below:
Example
pmin = 35 m head, Qmax = 2.5 m3/h.
On the basis of this information, the following values can be found in the table:
Minimum diaphragm tank size = 33 litres.
ppre = 31.5 m head.
pcut-in = 36 m head.
pcut-out = 50 m head.
1 m head = 0.098 bar.
The motor incorporates an electronic unit which protects the motor in various situations.
In case of overload, the built-in overload protection will stop the pump for 5 minutes. After that period, the pump will attempt to restart.
If the pump has been stopped as a result of dry running, it will start automatically after 5 minutes.
If the pump is restarted and the borehole is empty, the pump will stop after 30 seconds.
Resetting of the pump: Switch off the power supply for 1 minute.
The motor is protected in case of:
SQE pumps/MSE 3 motors
Note
Via the CU 300 or CU 301, the dry-running stop limit of the MSE 3 motors can be adjusted to match the actual application.
The pumps are normally maintenance-free.
Deposits and wear may occur. For that purpose, service kits and service tools are available from Grundfos. The Grundfos Service Manual is available on request.
The pumps can be serviced at a Grundfos service centre.
Note
If a pump has been used for a liquid which is injurious to health or toxic, the pump will be classified as contaminated.
If Grundfos is requested to service the pump, Grundfos must be contacted with details about the pumped liquid, etc. before the pump is returned for service. Otherwise Grundfos can refuse to accept the pump for service.
However, any application for service (no matter to whom it may be made) must include details about the pumped liquid if the pump has been used for liquids which are injurious to health or toxic.
SQE-NE: Only pumps that can be certified as uncontaminated, i.e. pumps containing no hazardous and/or toxic material, may be returned to Grundfos for servicing.
To prevent injury to the health of persons involved and to the environment, a document certifying that the pump is clean is required.
Grundfos must receive this certificate before the product. Otherwise, Grundfos will refuse to accept the product for servicing.
Possible costs of returning the pump are paid by the customer.
Before starting any work on the pump/ motor, make sure that the power supply has been switched off and that it cannot be accidentally switched on.
Fault | Cause | Remedy |
|
| Replace the blown fuses. If the new ones blow too, the electric installation and the submersible drop cable should be checked. |
| Cut in the circuit breaker. | |
| Contact the power supply authorities. | |
| Check whether the motor/pump is blocked. | |
| Repair/replace the pump/cable. | |
| Check the power supply. | |
|
| Open the valve. |
| See item 3 a). | |
| Pull out the pump and clean or replace the valve. | |
| Pull out the pump and clean the strainer. | |
| Repair/replace the pump. | |
|
| Increase the installation depth of the pump, throttle the pump or replace it by a smaller model to obtain a smaller capacity. |
| Check and clean/replace the valves, if necessary. | |
| Clean/replace the discharge pipe. | |
| Pull out the pump and check/replace the valve. | |
| Pull out the pump. Check and clean or replace the pump, if necessary. Clean the pipes. | |
| Repair/replace the pump. | |
| Check and repair the pipework. | |
| Replace the riser pipe. | |
| Check the power supply. | |
|
| Increase the differential. However, the stop pressure must not exceed the operating pressure of the pressure tank, and the start pressure should be high enough to ensure sufficient water supply. |
| Adjust the intervals of the electrodes/level switches to ensure suitable time between the cutting-in and cutting-out of the pump. See installation and operating instructions for the automatic devices used. If the intervals between stop/start cannot be changed via the automatics, the pump capacity may be reduced by throttling the discharge valve. | |
| Pull out the pump and clean/replace the non-return valve. | |
| Check the power supply. | |
| Check the water temperature. |
Megging of an installation incorporating SQ/SQE pumps is not allowed, as the built-in electronics may be damaged. See fig. 13.
Fig. 13
Before starting any work on the pump/ motor, make sure that the power supply has been switched off and that it cannot be accidentally switched on.
| Measure the voltage (RMS) between phase and neutral. Connect the voltmeter to the terminals at the connection. | The voltage should, when the motor is loaded, be within the range specified in Electrical connection section. Large variations in supply voltage indicate poor power supply, and the pump should be stopped until the defect has been remedied. |
| Measure the current (RMS) while the pump is operating at a constant discharge head (if possible, at the capacity where the motor is most heavily loaded). For maximum current, see nameplate. | If the current exceeds the full load current, there are the following possible faults:
|
Canada
Phone: +1-905 829 9533
Telefax: +1-905 829 9512
U.S.A.
Phone: +1-913-227-3400
Telefax: +1-913-227-3500
www.grundfos.com
Prior to installation, read these installation and operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice.
If these safety instructions are not observed, it may result in personal injury.
If these safety instructions are not observed, it may result in malfunction or damage to the equipment.
Note
Notes or instructions that make the job easier and ensure safe operation.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download GRUNDFOS SQ Series, SQE Series, SQE-NE Series Manual
Advertisement
Need help?
Do you have a question about the SQ Series and is the answer not in the manual?
Questions and answers