Advertisement
If these safety instructions are not observed, it may result in personal injury. | |
If these instructions are not observed, it may lead to electric shock with consequent risk of serious personal injury or death. | |
The surface of the product may be so hot that it may cause burns or personal injury. | |
If these safety instructions are not observed, it may result in malfunction or damage to the equipment. | |
Note | Notes or instructions that make the job easier and ensure safe operation. |
AI | Analog input. |
AL | Alarm, out of range at lower limit. |
AO | Analog output. |
AU | Alarm, out of range at upper limit. |
CIM | Communication interface module. |
Current sinking | The ability to draw current into the terminal and guide it towards GND in the internal circuitry. |
Current sourcing | The ability to push current out of the terminal and into an external load which must return it to GND. |
DI | Digital input. |
DO | Digital output. |
ELCB | Earth leakage circuit breaker. |
GDS | Grundfos Digital Sensor. Factory-fitted sensor in some Grundfos pumps. |
GENIbus | Proprietary Grundfos fieldbus standard. |
GFCI | Ground fault circuit interrupter. (USA and Canada). |
GND | Ground. |
Grundfos Eye | Status indicator light. |
LIVE | Low voltage with the risk of electric shock if the terminals are touched. |
OC | Open collector: Configurable open-collector output. |
PE | Protective earth. |
PELV | Protective extra-low voltage. A voltage that cannot exceed ELV under normal conditions and under single-fault conditions, except earth faults in other circuits. |
SELV | Safety extra-low voltage. A voltage that cannot exceed ELV under normal conditions and under single-fault conditions, including earth faults in other circuits. |
These installation and operating instructions are a supplement to the installation and operating instructions for the corresponding standard pumps CR, CRI, CRN, SPK, MTR and CM.
For instructions not mentioned specifically in this manual, see the installation and operating instructions for the standard pump.
Grundfos E-pumps are fitted with frequency-controlled permanent-magnet motors for single-phase or three-phase mains connection.
The pumps have a built-in PI controller and can be set up for an external sensor enabling the control of the following parameters:
The pumps have been factory-set to constant-curve control mode. The control mode can be changed with the R100 or Grundfos GO Remote.
The pumps have a built-in PI controller and are set up with a pressure sensor enabling the control of the pump discharge pressure.
The pumps have been factory-set to constant-pressure control mode. The pumps are typically used to keep a constant pressure in variable-demand systems.
The description of settings applies both to pumps without factory-fitted sensor and to pumps with a factory-fitted pressure sensor.
Setpoint
The desired setpoint can be set in three ways:
Other settings
All other settings can only be made with the R100 or Grundfos GO Remote.
Important parameters, such as actual value of the control parameter and power consumption, can be read via the R100 or Grundfos GO Remote.
If special or customised settings are required, use the Grundfos PC Tool. Contact your local Grundfos company for more information.
This product incorporates a radio module for remote control which is a class 1 device and can be used anywhere in the EU member states without restrictions.
Note
Some variants of these products and all products sold in China and Korea have no possibility of radio communication according to local legislation.
This product can communicate with the Grundfos GO Remote and other products of the same type via the built-in radio module.
In some cases, an external antenna may be required. Only Grundfos-approved external antennas may be connected to this product, and only by a Grundfos-approved installer.
A Li-ion battery is fitted in CRE, CRIE, CRNE, SPKE and MTRE pumps. The Li-ion battery complies with the Battery Directive (2006/66/EC). The battery does not contain mercury, lead and cadmium.
Installation and operation must comply with local regulations and accepted codes of good practice.
The pump must be secured to a solid foundation by bolts through the holes in the flange or the base plate.
Note
In order to maintain the ETL mark, additional installation procedures must be followed.
The motor has four M20 screwed cable entries fitted with blind plugs from factory.
The following cable glands are included:
Note
In order to ensure sufficient cooling of the motor, the distance (D) between the end of the fan cover and a wall or other fixed objects must always be at least 50 mm, irrespective of motor size.
When installed outdoors, the motor must be provided with a suitable cover to avoid condensation on the electronic components.
Note
When fitting a cover to the motor, observe the guideline in section "Ensuring motor cooling".
The cover must be sufficiently large to ensure that the motor is not exposed to direct sunlight, rain or snow. Grundfos does not supply covers. We therefore recommend that you have a cover built for the specific application. In areas with high air humidity, we recommend that you enable the built-in standstill heating function. See section Standstill heating.
When the motor is installed in moist surroundings or areas with high air humidity, the bottom drain hole should be open.
The enclosure class of the motor will then be lower. The open drain hole helps prevent condensation in the motor as it will make the motor self-venting and allow water and humid air to escape.
The motor has a plugged drain hole on the drive side. The flange can be turned 90 ° to both sides or 180 °.
Carry out the electrical connection according to local regulations. Check that the supply voltage and frequency correspond to the values stated on the nameplate.
Do not make any connections in the terminal box unless the power supply has been switched off for at least 5 minutes.
Make sure that the power supply cannot be accidentally switched on.
The motor must be earthed and protected against indirect contact in accordance with local regulations.
If the power supply cable is damaged, it must be replaced by the manufacturer, the manufacturer's service partner or a similarly qualified person.
Note
The user or the installer is responsible for the installation of correct earthing and protection Note according to local regulations. All operations must be carried out by a qualified electrician.
The motor must be earthed and protected against indirect contact in accordance with local regulations.
Protective-earth conductors must always have a yellow/green (PE) or yellow/green/blue (PEN) colour marking.
Protection against mains voltage transients
The motor is protected against mains voltage transients in accordance with EN 61800-3.
Motor protection
The motor requires no external motor protection. The motor incorporates thermal protection against slow overloading and blocking.
Check that the supply voltage and frequency correspond to the values stated on the nameplate.
Note
If the motor is supplied through an IT network, a dedicated IT network motor should be used. Contact Grundfos.
The wires in the motor terminal box must be as short as possible. Excepted from this is the separated earth conductor which must be so long that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry.
For maximum backup fuse, see section Supply voltage.
In order to avoid loose connections, ensure that the terminal block for L1, L2 and L3 is pressed home in its socket when the supply cable has been connected.
Note
Corner grounding is not allowed for supply voltages above 3 x 480 V, 50/60 Hz.
Check that the supply voltage and frequency correspond to the values stated on the nameplate.
Note
If the motor is supplied through an IT network, a dedicated IT network motor should be used. Contact Grundfos.
The wires in the motor terminal box must be as short as possible. Excepted from this is the separated earth conductor which must be so long that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry.
For maximum backup fuse, see section Supply voltage.
If the motor is connected to an electric installation where an earth leakage circuit breaker (ELCB) or ground fault circuit interrupter (GFCI) is used as additional protection, this circuit breaker or interrupter must be marked with the following symbol:
ELCB
(GFCI)
Note
When an earth leakage circuit breaker or ground fault circuit interrupter is selected, the total leakage current of all the electrical equipment in the installation must be taken into account.
The leakage current of the motor can be found in section Leakage current.
If the motor is connected to an electric installation where an earth leakage circuit breaker (ELCB) or ground fault circuit interrupter (GFCI) is used as additional protection, this circuit breaker or interrupter must be of the following type:
For these motors an earth leakage circuit breaker or ground fault circuit interrupter, type B, must be used.
This circuit breaker or interrupter must be marked with the following symbols:
ELCB
(GFCI)
Note
When an earth leakage circuit breaker or ground fault circuit interrupter is selected, the total leakage current of all the electrical equipment in the installation must be taken into account.
The leakage current of the motor can be found in section Leakage current.
Protection against phase unbalance
The motor must be connected to a power supply with a quality corresponding to IEC 60146-1-1, class C, to ensure correct motor operation at phase unbalance.
This also ensures long life of the components.
The descriptions and terminal overviews in this section apply to both single- and three-phase motors.
For maximum tightening torques, see section Torques.
CRE, CRIE, CRNE, SPKE and MTRE pumps have a number of inputs and outputs enabling the pumps to be used in advanced applications where many inputs and outputs are required.
The pumps have these connections:
See fig. 8.
Note
Digital input 1 is factory-set to be start/stop input where open circuit will result in stop. A jumper has been factory-fitted between terminals 2 and 6. Remove the jumper if digital input 1 is to be used as external start/stop or any other external function.
Note
As a precaution, the wires to be connected to the connection groups below must be separated from each other by reinforced insulation in their entire lengths.
A galvanically safe separation must fulfil the requirements for reinforced insulation including creepage distances and clearances specified in EN 61800-5-1.
Terminal | Type | Function |
NC | Normally closed contact | Signal relay 1 (LIVE or SELV) |
C1 | Common | |
NO | Normally open contact | |
NC | Normally closed contact | Signal relay 2 (SELV only) |
C2 | Common | |
NO | Normally open contact | |
18 | GND | Ground |
11 | DI4/OC2 | Digital input/output, configurable. Open collector: Max. 24 V resistive or inductive. |
19 | Pt100/1000 input 2 | Pt100/1000 sensor input |
17 | Pt100/1000 input 1 | Pt100/1000 sensor input |
12 | AO | Analog output: 0-20 mA/4-20 mA 0-10 V |
9 | GND | Ground |
14 | AI3 | Analog input: 0-20 mA/4-20 mA 0-10 V |
1 | DI2 | Digital input, configurable |
21 | LiqTec sensor input 1 | LiqTec sensor input (white conductor) |
20 | GND | Ground (brown and black conductors) |
22 | LiqTec sensor input 2 | LiqTec sensor input (blue conductor) |
10 | DI3/OC1 | Digital input/output, configurable. Open collector: Max. 24 V resistive or inductive. |
4 | AI1 | Analog input: 0-20 mA/4-20 mA 0.5 - 3.5 V/0-5 V/0-10 V |
2 | DI1 | Digital input, configurable |
5 | +5 V | Supply to potentiometer and sensor |
6 | GND | Ground |
A | GENIbus, A | GENIbus, A (+) |
Y | GENIbus, Y | GENIbus, GND |
B | GENIbus, B | GENIbus, B (-) |
3 | GND | Ground |
15 | +24 V | Supply |
8 | +24 V | Supply |
26 | +5 V | Supply to potentiometer and sensor |
23 | GND | Ground |
25 | GDS TX | Grundfos Digital Sensor output |
24 | GDS RX | Grundfos Digital Sensor input |
7 | AI2 | Analog input: 0-20 mA/4-20 mA 0.5 - 3.5 V/0-5 V/0-10 V |
The CME pump has these connections:
See fig. 9.
Note
Digital input 1 is factory-set to be start/stop input where open circuit will result in stop. A jumper has been factory-fitted between terminals 2 and 6. Remove the jumper if digital input 1 is to be used as external start/stop or any other external function.
Note
As a precaution, the wires to be connected to the connection groups below must be separated from each other by reinforced insulation in their entire lengths.
A galvanically safe separation must fulfil the requirements for reinforced insulation including creepage distances and clearances specified in EN 61800-5-1.
Terminal | Type | Function |
NC | Normally closed contact | Signal relay 1 (LIVE or SELV) |
C1 | Common | |
NO | Normally open contact | |
NC | Normally closed contact | Signal relay 2 (SELV only) |
C2 | Common | |
NO | Normally open contact | |
10 | DI3/OC1 | Digital input/output, configurable. Open collector: Max. 24 V resistive or inductive. |
4 | AI1 | Analog input: 0-20 mA/4-20 mA 0.5 - 3.5 V/0-5 V/0-10 V |
2 | DI1 | Digital input, configurable |
5 | +5 V | Supply to potentiometer and sensor |
6 | GND | Ground |
A | GENIbus, A | GENIbus, A (+) |
Y | GENIbus, Y | GENIbus, GND |
B | GENIbus, B | GENIbus, B (-) |
3 | GND | Ground |
15 | +24 V | Supply |
8 | +24 V | Supply |
26 | +5 V | Supply to potentiometer and sensor |
23 | GND | Ground |
25 | GDS TX | Grundfos Digital Sensor output |
24 | GDS RX | Grundfos Digital Sensor input |
7 | AI2 | Analog input: 0-20 mA/4-20 mA 0.5 - 3.5 V/0-5 V/0-10 V |
For the bus connection, use a screened 3-core cable with a cross-sectional area of min. 0.5 mm2 and max. 1.5 mm2.
The number of starts and stops via the power supply must not exceed four times per hour.
When switched on via the power supply, the pump will start after approx. 5 seconds.
If a higher number of starts and stops is desired, use the input for external start/stop when starting/stopping the pump.
When started via an external on/off switch, the pump will start immediately.
Ambient temperature during storage and transportation
Minimum -30°C
Maximum +60°C.
Ambient temperature during operation
Minimum -20°C
Maximum +50°C.
The motor can operate with the rated power output (P2) at 50°C, but continuous operation at higher temperatures will reduce the expected product life. If the motor is to operate at ambient temperatures between 50 and 60°C, an oversized motor must be selected. Contact Grundfos for further information.
The motor must not be installed more than 2000 metres above sea level.
Installation altitude is the height above sea level of the installation site.
Maximum air humidity: 95%.
If the air humidity is constantly high and above 85%, the drain holes in the drive-end flange should be open.
See section Drain holes.
To ensure cooling of motor and electronics, the following must be observed:
Grundfos E-pumps are set and controlled according to operating and control modes.
Operating modes
Control modes
Example
If the pump is fitted with a pressure sensor, the control mode must be set to constant pressure. If the pump is for instance fitted with a temperature sensor, the control mode should be constant temperature. See section Control mode for further information.
When the operating mode is set to "Normal", the control mode can be set to constant curve or any other control mode.
See section Control mode.
Other operating modes:
Figure 14 illustrates the min. and max. curves.
The max. curve can for instance be used in connection with the venting procedure during installation.
The min. curve can be used in periods in which a minimum flow is required.
If the power supply to the pump is disconnected, the setting of operating mode will be stored.
The pumps have been factory-set to constant-curve control mode.
In this control mode, the pump will operate according to the constant curve set.
Factory setting
Pumps supplied without sensor have been factory-set to constant-curve control mode.
The setpoint value corresponds to 100% of the maximum pump performance. See data booklet or WebCAPS.
The pressure sensor is fitted on the pump discharge side, and the pump is set to constant pressure.
In this control mode, the pump will adjust its performance, i.e. pump discharge pressure, to the desired setpoint (Hset).
Factory setting
Pumps supplied with pressure sensor have been factory-set to constant-pressure control mode.
The setpoint value corresponds to 50% of the sensor measuring range. See sensor nameplate.
The product may be so hot that only the buttons should be touched to avoid burns.
Pump settings can be made by means of the following user interfaces:
Control panel
Remote controls
If the power supply to the pump is switched off, the settings will be stored.
Pos. | Symbol | Description |
1 | ![]() | Grundfos Eye Shows the operating status of the pump. See section Grundfos Eye for further information. |
2 | - | Light fields for indication of setpoint. |
3 | ![]() | Changes the setpoint. |
4 | ![]() | Enables radio communication with the Grundfos GO Remote and other products of the same type. |
5 | ![]() | Makes the pump ready for operation/starts and stops the pump. Start: If the button is pressed when the pump is stopped, the pump will only start if no other functions with higher priority have been enabled. See section Priority of settings. Stop: If the button is pressed when the pump is running, the pump will always be stopped. When the pump is stopped via this button, the "Stop" text next to the button will illuminate. |
Set the desired setpoint of the pump by pressing or
.
The light fields on the control panel will indicate the setpoint set.
Pump in constant-pressure control mode
The following example applies to a pump in an application where a pressure sensor gives a feedback to the pump. If the sensor is retrofitted to the pump, it must be set up manually as the pump does not automatically register a connected sensor.
Figure 18 shows that the light fields 5 and 6 are activated, indicating a desired setpoint of 3 bar with a sensor measuring range from 0 to 6 bar. The setting range is equal to the sensor measuring range.
Pump in constant-curve control mode
In constant-curve control mode, the pump performance will lie between the max. and min. curve of the pump.
Setting to max. curve:
Example: Pump set to max. curve.
Figure 20 shows that the top light field is flashing, indicating max. curve.
Setting to min. curve:
Example: Pump set to min. curve.
Figure 21 shows that the bottom light field is flashing, indicating min. curve.
Stop the pump by pressing . When the pump is stopped, the "Stop" text next to the button will illuminate. The pump can also be stopped by continuously pressing
until none of the light fields are on.
Start the pump by pressing or by continuously pressing
until the desired setpoint is indicated.
If the pump has been stopped by pressing , it can only be given free to operation by pressing
again.
If the pump has been stopped by pressing , it can only be restarted by pressing
.
The pump can also be stopped with the R100, Grundfos GO Remote or via a digital input set to "External stop".
See section Priority of settings.
A fault indication can be reset in one of the following ways:
It is possible to turn the control panel 180 °. Follow the instructions below.
The pumps are designed for wireless communication with the Grundfos R100 remote control.
During communication, the R100 must be pointed at the control panel. When the R100 communicates with the pump, the indicator light in the middle of the Grundfos Eye will flash green.
The R100 offers additional possibilities of setting and status displays for the pump.
The displays are divided into four parallel menus:
See section R100 menu structure.
When communication between the R100 and the pump has been established, the first display in this menu will appear.
Setpoint
In constant-curve control mode, the setpoint is set in % of the maximum performance. The setting range will lie between the min. and max. curves.
In all other control modes, for example constant pressure, the setting range is equal to the sensor measuring range.
If the pump is connected to an external setpoint signal, the value in this display will be the maximum value of the external setpoint signal. See section External setpoint signal.
Setpoint and external signal
The setpoint cannot be set if the pump is controlled via external signals (Stop, Min. curve or Max. curve).
The R100 will give this warning: "External".
Check if the pump has been stopped via one of the digital inputs set to "External stop" (open circuit) or it has been set to min. or max. via one of the digital inputs (closed circuit).
See section Priority of settings.
Setpoint and bus communication
The setpoint cannot be set if the pump is controlled from an external control system via bus communication.
The R100 will give this warning: "Bus".
To override bus communication, disconnect the bus connection.
See section Priority of settings.
Operating mode
Select one of the following operating modes:
The operating modes can be selected without changing the setpoint setting.
See section Operating mode for further information.
Manual speed
In this display, the pump speed can be set in %. When the operating mode has been set to "Manual", the pump will run at the set speed.
Alarm
In case of an alarm, the cause will appear in the display together with a fault code.
Possible alarms:
Alarm | Fault code |
External fault | 3 |
Too many restarts | 4 |
Forced pumping | 29 |
Overvoltage | 32 |
Undervoltage | 40 |
Overload | 49 |
Blocked pump | 51 |
Dry running | 56, 57 |
Too high motor temperature | 65 |
Electronics temperature too high | 66 |
Internal communication fault | 76 |
Internal fault | 83, 85 |
Sensor signal outside signal range | 88 |
Temperature sensor 1 outside signal range | 91 |
Internal fault | 163 |
LiqTec sensor fault | 164 |
Signal outside range, analog input 1 | 165 |
Signal outside range, analog input 2 | 166 |
Signal outside range, analog input 3 | 167 |
Temperature sensor 2 outside signal range | 175 |
Limit 1 exceeded | 190 |
Limit 2 exceeded | 191 |
An alarm indication can be reset in this display by pressing [OK] if the cause of the fault has disappeared.
Warning
In case of a warning, the cause will appear in this display together with a fault code.
Possible warnings:
Warning | Fault code |
No contact to pump | 10 |
Replace motor bearings | 30 |
Too high motor temperature | 65 |
Electronics temperature too high | 66 |
Internal fault | 83, 85, 163 |
Sensor signal outside signal range | 88 |
Temperature sensor 1 outside signal range | 91 |
Sensor supply fault, 5 V | 161 |
Sensor supply fault, 24 V | 162 |
LiqTec sensor fault | 164 |
Signal outside range, analog input 1 | 165 |
Signal outside range, analog input 2 | 166 |
Signal outside range, analog input 3 | 167 |
Temperature sensor 2 outside signal range | 175 |
Limit 1 exceeded | 190 |
Limit 2 exceeded | 191 |
A warning indication will disappear automatically once the fault has been remedied.
Alarm log 1 to 5
In case of "alarm" faults, the last five alarm indications will appear in the alarm log. "Alarm log 1" shows the latest fault, "Alarm log 2" shows the latest fault but one, etc.
The example above gives this information:
Warning log 1 to 5
In case of "warning" faults, the last five warning indications will appear in the warning log. "Warning log 1" shows the latest fault, "Warning log 2" shows the latest fault but one, etc.
The example above gives this information:
The displays appearing in this menu are status displays only. It is not possible to change or set values.
The displayed values are the values that applied when the last communication between the pump and the R100 took place. If a status value is to be updated, point the R100 at the control panel and press [OK].
If a parameter, for example speed, should be called up continuously, press [OK] constantly during the period in which the parameter in question should be monitored.
The tolerance of the displayed value is stated under each display. The tolerances are stated as a guide in % of the maximum values of the parameters.
Actual setpoint and external setpoint
This display shows the actual setpoint and the external setpoint in % of the range from minimum value of sensor measuring range to the setpoint set.
At a min. speed of 12%, a set setpoint of 65% and an external setpoint of 70%, the actual setpoint will be 0.70 x (65 - 12) + 12 = 49%.
Operating mode
This display shows the actual operating mode (Stop, Min., Normal (duty), Max. or Manual (operation)). Furthermore, it shows where this operating mode was selected (Handheld, Pump, Bus, External or Start/stop button). See section Operating and control modes for further information.
Actual controlled value
The actual controlled value will appear in this display if a sensor has been connected and the function of the analog input has been set to "Feedback sensor".
If two separate sensors are used to measure a differential parameter, the function of two analog inputs must be set to "Feedback sensor". The actual controlled value will be the absolute difference between the two sensor measurements.
See section Analog input 1, 2 and 3, Function.
Analog input 1, 2 and 3
These displays show the measured parameter and the corresponding value.
The number of available displays depends on the pump type. See below.
Function (terminal) | CME | CRE, CRIE, CRNE, SPKE, MTRE |
Analog input 1 (4) | ● | ● |
Analog input 2 (7) | ● | ● |
Analog input 3 (14) | - | ● |
Pt100/1000 input 1 and 2
These displays show the measured parameter and the corresponding value. The measured temperatures will appear in these displays if Pt100 or Pt1000 sensors have been connected.
The number of available displays depends on the pump type. See below.
Function (terminal) | CME | CRE, CRIE, CRNE, SPKE, MTRE |
Pt100/1000 input 1 (17) | - | ● |
Pt100/1000 input 2 (19) | - | ● |
Speed
Tolerance: ± 5%.
This display shows the actual speed.
Power input and power consumption
Tolerance: ± 10%.
Operating hours
Tolerance: ± 2%.
The value of operating hours is an accumulated value and cannot be reset.
Replace motor bearings
This display shows when to replace the motor bearings.
The controller monitors the operating pattern of the motor and calculates the period between bearing replacements.
Displayable values:
Control mode
Select one of the following control modes:
See section Operating and control modes for further information.
Note
If the pump is connected to a bus (see section Bus signal), it is not possible to select the control mode via the R100.
Controller
E-pumps have a factory default setting of gain (Kp) and integral time (Ti). However, if the factory setting is not the optimum setting, the gain and the integral time can be changed in this display:
Guidelines for setting of PI controller
The table below shows the recommended controller settings:
System/application | Kp | Ti | |
Heating system1]) | Cooling system2]) | ||
![]() | 0.5 | 0.5 | |
![]() | 0.1 | 0.5 | |
![]() | 0.5 | 0.5 | |
![]() | 0.5 | -0.5 | 10 + 5L2 |
![]() | 0.5 | 10 + 5L2 | |
![]() | |||
![]() | 0.5 | -0.5 | 30 + 5L2 |
![]() | 0.5 | 0.5 | |
![]() | |||
![]() | 0.5 | L1 < 5 m: 0.5 L1 > 5 m: 3 L1 > 10 m: 5 | |
![]() |
L1 = Distance [m] between pump and sensor.
L2 = Distance [m] between heat exchanger and sensor.
General rules of thumb
Signal relay 1 and 2
The signal relays can be configured to be activated by one of the following incidents:
The number of available displays depends on the pump type. See below.
Function (terminal) | CME | CRE, CRIE, CRNE, SPKE, MTRE |
Signal relay 1 (NC, C1, NO) | ● | ● |
Signal relay 2 (NC, C2, NO) | ● | ● |
Buttons on pump
The buttons on the pump can be set to the following:
Number
A number between 1 and 64 can be allocated to the pump. In the case of bus communication, a number must be allocated to each pump.
Digital input 1 and 2, Function
The digital inputs can be set to various functions.
Select one of these functions:
The priority of the selected functions in relation to each other appears from section Priority of settings.
A stop command will always have the highest priority.
The number of available displays depends on the pump type. See below.
Function (terminal) | CME | CRE, CRIE, CRNE, SPKE, MTRE |
Digital input 1, Function (2 and 6) | ● | ● |
Digital input 2, Function (1 and 9) | - | ● |
Digital input/output 3 and 4, State
The digital input/output 3 and 4 can be set to act as digital input or digital output.
Possible settings:
The number of available displays depends on the pump type. See below.
Function (terminal) | CME | CRE, CRIE, CRNE, SPKE, MTRE |
Digital input/output 3, State (10 and 6) | ● | ● |
Digital input/output 4, State (11 and 18) | - | ● |
Digital input/output 3 and 4, Function
The digital input/output 3 and 4 can be set to these functions:
Possible functions, digital input/output 3
Set to digital input
Set to digital output
Possible functions, digital input/output 4
Set to digital input
Set to digital output
The number of available displays depends on the pump type. See below.
Function (terminal) | CME | CRE, CRIE, CRNE, SPKE, MTRE |
Digital input/output 3, Function (10 and 6) | ● | ● |
Digital input/output 4, Function (11 and 18) | - | ● |
Low-flow stop function
The low-flow stop function can be set to these values:
When the low-flow stop function is active, the flow will be monitored. If the flow becomes lower than the set minimum flow (Qmin), the pump will change from continuous operation at constant pressure to start/stop operation and finally be stopped if the flow reaches zero.
The advantages of enabling the low-flow stop function are the following:
The disadvantages of enabling the low-flow stop function may be the following:
The impact of the above disadvantages very much depends on the setting selected for the low-flow stop function.
The "High comfort" setting will minimise pressure fluctuations and acoustic noise.
If "Energy optimal" is selected, the main priority will be to reduce the energy consumption as much as possible.
Possible settings of the low-flow stop function:
In start/stop operation, the pressure will vary between the start and stop pressures.
In "User-defined" mode, ∆H has been factory-set to 10% of the actual setpoint. ∆H can be set within the range from 5 to 30% of actual setpoint.
The pump will change to start/stop operation if the flow becomes lower than Qmin.
Qmin is set in % of the rated flow of the pump (see pump nameplate).
In "User-defined" mode, Qmin has been factory-set to 10% of rated flow.
Low-flow detection
Low flow can be detected in two ways:
Operating conditions for the low-flow stop function
It is only possible to use the stop function if the system incorporates a pressure sensor, a non-return valve and a diaphragm tank.
The non-return valve must always be installed before the pressure sensor.
Set min. flow
Set the minimum flow (Qmin) in this display. This setting determines at which flow rate the system is to change from continuous operation at constant pressure to start/stop operation. The setting range is 5 to 30% of rated flow.
Factory setting: 10%.
Diaphragm tank volume
The stop function requires a diaphragm tank of a certain minimum size. Set the size of the installed tank in this display.
In order to reduce the number of start/stops per hour or to reduce the ∆H, a larger tank can be installed.
The tank must be installed immediately after the pump and the precharge pressure must be 0.7 x actual setpoint.
Recommended diaphragm tank size:
Rated flow rate of pump [m3/h] | CRE pump | Typical diaphragm tank size [litres] |
0-6 | 1s, 1, 3, 5 | 8 |
7-24 | 10, 15, 20 | 18 |
25-40 | 32 | 50 |
41-70 | 45, 64 | 120 |
71-100 | 90 | 180 |
Analog input 1, 2 and 3, Function
The analog inputs can be set to these functions:
The number of available displays depends on the pump type. See below.
Function (terminal) | CME | CRE, CRIE, CRNE, SPKE, MTRE |
Analog input 1, Function (4) | ● | ● |
Analog input 2, Function (7) | ● | ● |
Analog input 3, Function (14) | - | ● |
Analog input 1, 2 and 3, Measured parameter
The analog inputs can be set to these parameters:
The number of available displays depends on the pump type. See below.
Function (terminal) | CME | CRE, CRIE, CRNE, SPKE, MTRE |
Analog input 1, Measured parameter (4) | ● | ● |
Analog input 2, Measured parameter (7) | ● | ● |
Analog input 3, Measured parameter (14) | - | ● |
Analog input 1, 2 and 3
Select the following:
Parameter | Possible units |
Pressure | bar, m, kPa, psi, ft |
Flow rate | m3/h, l/s, yd3/h, gpm |
Temperature | °C, °F |
Other | % |
The number of available displays depends on the pump type. See below.
Function (terminal) | CME | CRE, CRIE, CRNE, SPKE, MTRE |
Analog input 1 (4) | ● | ● |
Analog input 2 (7) | ● | ● |
Analog input 3 (14) | - | ● |
Pt100/1000 input 1 and 2, Function
The Pt100/1000 inputs can be set to these functions:
The number of available displays depends on the pump type. See below.
Function (terminal) | CME | CRE, CRIE, CRNE, SPKE, MTRE |
Pt100/1000 input 1, Function (17 and 18) | - | ● |
Pt100/1000 input 2, Function (19 and 18) | - | ● |
Pt100/1000 input 1 and 2, Measured parameter
The Pt100/1000 inputs can be set to these parameters:
The number of available displays depends on the pump type. See below.
Function (terminal) | CME | CRE, CRIE, CRNE, SPKE, MTRE |
Pt100/1000 input 1, Measured parameter (17 and 18) | - | ● |
Pt100/1000 input 2, Measured parameter (19 and 18) | - | ● |
LiqTec function
The function of LiqTec sensors can be enabled or disabled in this display. A LiqTec sensor protects the pump against dry running and too high liquid temperature (130 ± 5°C).
When the LiqTec function has been enabled, it will stop the pump if dry running occurs or if the liquid temperature becomes too high. The pump must be restarted manually if it has been stopped due to dry running or too high liquid temperature.
Possible settings:
The number of available displays depends on the pump type. See below.
Function (terminal) | CME | CRE, CRIE, CRNE, SPKE, MTRE |
LiqTec function (21 and 22) | - | ● |
Operating range
Set the operating range as follows:
The range between the user-set min. and max. speeds is the operating range.
Ramps
The setting of ramps is only relevant in the case of constant-curve operation.
The ramps determine how quickly the pump can accelerate and decelerate, respectively, during start/stop or setpoint changes.
The following can be set:
The times apply to the acceleration from stop to rated speed and the deceleration from rated speed to stop, respectively.
At short deceleration times, the deceleration of the pump may depend on load and inertia as there is no possibility of actively braking the pump.
If the power supply is switched off, the deceleration of the pump will only depend on load and inertia.
Motor bearing monitoring
The motor bearing monitoring function can be set to these values:
When the function is set to "Active", the controller will monitor the operating pattern of the motor and calculate when the bearings need to be replaced.
Note
Even if the function is changed to "Not active", the controller will continue to calculate when the bearings need to be replaced, but no warning will be given when it is time for replacement.
When the function is changed back to "Active", the accumulated calculations for bearing wear will be used to calculate the replacement time.
Motor bearings
This function can be set to these values:
When the bearing monitoring function is active, the controller will give a warning indication when the motor bearings are due to be replaced. See section Alarm.
When the motor bearings have been replaced, confirm this action in the above display by pressing [OK].
Standstill heating
The standstill heating function can be set to these values:
When the function is set to "Active", an AC voltage will be applied to the motor windings. The applied voltage will ensure that sufficient heat is generated to avoid condensation in the motor.
The pump is designed for wireless radio or infrared communication with the Grundfos GO Remote.
The Grundfos GO Remote enables setting of functions and gives access to status overviews, technical product information and actual operating parameters.
The Grundfos GO Remote offers three different mobile interfaces (MI).
Pos. | Description |
1 | Grundfos MI 201: Consists of an Apple iPod touch 4G and a Grundfos cover. |
2 | Grundfos MI 202: Add-on module which can be used in conjunction with Apple iPod touch 4, iPhone 4G or later. |
3 | Grundfos MI 301: Separate module enabling radio or infrared communication. The module can be used in conjunction with an Android or iOS-based Smartphone with Bluetooth connection. |
When the Grundfos GO Remote communicates with the pump, the indicator light in the middle of the Grundfos Eye will flash green. See section Grundfos Eye.
Communication must be established using one of these communication types:
Radio communication
Radio communication can take place at distances up to 30 metres. It is necessary to enable communication by pressing or
on the pump control panel.
Infrared communication
When communicating via infrared light, the Grundfos GO Remote must be pointed at the pump control panel.
Navigation can be done from the dashboard. See fig. 34.
Dashboard
Pos. | Description | Action |
1 | Connection indicator | This text appears when the Grundfos GO Remote app has connected to an MI 201, MI 202 or MI 301. If the hardware is not connected, it will not be possible to communicate with a Grundfos product. |
2 | Back button | Returns to the previous display. |
3 | Product information | Provides technical information about the product. |
4 | Product name | Name of the product communicating with the Grundfos GO Remote. |
5 | Alarms and warnings | Shows alarms and warnings. |
6 | Grundfos Eye | Shows the operating condition of the product. |
7 | Primary status value | Shows the primary status value. |
8 | Secondary status value | Shows the secondary status value. |
9 | Control source | Shows by which interface the product is controlled. |
10 | Control mode | Shows the control mode of the product. |
11 | Actual setpoint value | Shows the actual setpoint value. |
12 | Operating mode | Shows the operating mode. |
13 | Show menu | Gives access to other menus. |
14 | Stop | Stops the product. |
Tool bar | ||
15 | Help | The help function describes the menus making it easy for the user to change settings, etc. |
16 | Documentation | Gives access to installation and operating instructions and quick guides. |
17 | Report | Enables the creation of user-defined reports. |
18 | Update | Enables update of the Grundfos GO Remote app. |
It is possible to remote-set the setpoint by connecting an analog signal transmitter to one of the analog inputs setup for external setpoint influence. See section Analog input 1, 2 and 3, Function.
The actual external signal (0.5 - 3.5 V, 0-5 V, 0-10 V, 0-20 mA, 4-20 mA) must be selected with the R100 or Grundfos GO Remote.
If constant-curve operation is selected with the R100 or Grundfos GO Remote, the pump can be controlled by any controller.
If fitted with a sensor, the pump can operate according to the control modes below:
If operation with sensor feedback is selected, the setpoint can be set externally within the range from the lower value of the sensor measuring range to the setpoint set on the motor or with the R100 or Grundfos GO Remote.
Example: At a lower sensor value of 0 bar, a set setpoint of 5 bar and an external setpoint of 70%, the actual setpoint is 0.70 x (5 - 0) + 0 = 3.5 bar.
If constant-curve operation is selected, the setpoint can be set externally within the range from the min. speed to the setpoint set on the motor or with the R100 or Grundfos GO Remote.
Example: At a set setpoint of 65% of nmax. and an external setpoint of 70%, the actual setpoint is 0.70 x (65 - 12) + 12 = 49%.
The motor enables serial communication via an RS-485 input. The communication is carried out according to the Grundfos GENIbus protocol and enables connection to a building management system or another external control system.
Via a bus signal, it is possible to remote-set motor operating parameters, such as setpoint and operating mode. At the same time, the motor can, via the bus, provide status information about important parameters, such as actual value of control parameter, input power and fault indications.
Contact Grundfos for further information.
Note
If a bus signal is used, the number of settings available via the R100 or Grundfos GO Remote will be reduced.
The motor can always be set to operation at max. speed or to stop with the R100 or Grundfos GO Remote.
If two or more functions are enabled at the same time, the motor will operate according to the function with the highest priority.
Example: If, via the digital input, the motor has been set to max. speed, the motor control panel, the R100 or Grundfos GO Remote can only set the motor to "Manual" or "Stop".
The priority of the settings appears from the table below:
Priority | Start/stop button | R100, Grundfos GO Remote or control panel on motor | Digital input | Bus communication |
1 | Stop | |||
2 | Stop* | |||
3 | Manual | |||
4 | Max. speed* | |||
5 | Stop | |||
6 | Stop | |||
7 | Max. speed | |||
8 | Min. speed | |||
9 | Start | |||
10 | Max. speed | |||
11 | Min. speed | |||
12 | Min. speed | |||
13 | Start | |||
14 | Start |
* If the bus communication is interrupted, the motor will resume its previous operating mode, for example "Stop", selected with the R100, Grundfos GO Remote or on the motor control panel.
The operating condition of the motor is indicated by the Grundfos Eye on the motor control panel. See fig. 37, pos. A.
Grundfos Eye | Indication | Description |
![]() | No lights on. | Power off. Motor not running. |
![]() | Two opposite green indicator lights rotating in the direction of rotation of the motor when seen from the non-drive end. | Power on. Motor running. |
![]() | Two opposite green indicator lights permanently on. | Power on. Motor not running. |
![]() | One yellow indicator light rotating in the direction of rotation of the motor when seen from the non-drive end. | Motor running. |
![]() | One yellow indicator light permanently on. | Motor stopped. |
![]() | Two opposite red indicator lights flashing simultaneously. | Alarm. Motor stopped. |
![]() | The green indicator light in the middle flashes quickly four times.![]() | Remote control with the Grundfos GO Remote via radio. The motor is trying to communicate with the Grundfos GO Remote. The motor in question is highlighted in the Grundfos GO Remote display to inform the user of the location of the motor. |
The green indicator light in the middle flashes continuously.![]() | When the motor in question is selected in the Grundfos GO Remote menu, the green indicator light in the middle will flash continuously. Press ![]() | |
![]() | The green indicator light in the middle is permanently on.![]() | Remote control with the Grundfos GO Remote via radio. The motor is communicating with the Grundfos GO Remote via radio connection. |
![]() | The green indicator light in the middle flashes quickly while the R100 or Grundfos Go Remote is exchanging data with the motor. It will take a few seconds.![]() | Remote control with the R100 or Grundfos GO Remote via infrared light. The motor is receiving data from the R100 or Grundfos GO Remote via infrared communication. |
The motor has two outputs for potential-free signals via two internal relays.
The signal outputs can be set to "Operation", "Running", "Ready", "Alarm" and "Warning".
The functions of the two signal relays appear from the table below:
Megging of an installation incorporating MGE motors is not allowed, as the built-in electronics may be damaged.
Check that the supply voltage and frequency correspond to the values stated on the nameplate.
Recommended fuse size
Motor size [kW] | Min. [A] | Max. [A] |
0.25 - 0.75 | 6 | 10 |
1.1 - 1.5 | 10 | 16 |
Standard as well as quick-blow or slow-blow fuses may be used.
Earth leakage current < 3.5 mA (AC supply).
Earth leakage current < 10 mA (DC supply).
The leakage currents are measured in accordance with EN 61800-5-1:2007.
Check that the supply voltage and frequency correspond to the values stated on the nameplate.
Recommended fuse size
Motor size [kW] | Min. [A] | Max. [A] |
0.25 -1.1 | 6 | 6 |
1.5 - 2.2 | 6 | 10 |
Standard as well as quick-blow or slow-blow fuses may be used.
Motor size [kW] | Leakage current [mA] |
0.75 - 2.2 (supply voltage < 400 V) | < 3.5 |
0.75 - 2.2 (supply voltage > 400 V) | < 5 |
The leakage currents are measured in accordance with EN 61800-5-1:2007.
Ground reference (GND)
All voltages refer to GND.
All currents return to GND.
Absolute maximum voltage and current limits
Exceeding the following electrical limits may result in severely reduced operating reliability and motor life:
Relay 1:
Maximum contact load: 250 VAC, 2 A or 30 VDC, 2 A.
Relay 2:
Maximum contact load: 30 VDC, 2 A.
GENI terminals: -5.5 to 9.0 VDC or < 25 mADC.
Other input/output terminals: -0.5 to 26 VDC or < 15 mADC.
Digital inputs (DI)
Internal pull-up current > 10 mA at Vi = 0 VDC.
Internal pull-up to 5 VDC (currentless for Vi > 5 VDC).
Certain low logic level: Vi < 1.5 VDC.
Certain high logic level: Vi > 3.0 VDC.
Hysteresis: No.
Screened cable: 0.5 - 1.5 mm2/28-16 AWG.
Maximum cable length: 500 m.
Open-collector digital outputs (OC)
Current sinking capability: 75 mADC, no current sourcing.
Load types: Resistive or/and inductive.
Low-state output voltage at 75 mADC: Max. 1.2 VDC.
Low-state output voltage at 10 mADC: Max. 0.6 VDC.
Overcurrent protection: Yes.
Screened cable: 0.5 - 1.5 mm2/28-16 AWG.
Maximum cable length: 500 m.
Analog inputs (AI)
Voltage signal ranges:
Voltage signal: Ri > 100 kΩ at +25°C.
Leak currents may occur at high operating temperatures. Keep the source impedance low.
Current signal ranges:
Current signal: Ri = 292 Ω.
Current overload protection: Yes. Change to voltage signal.
Measurement tolerance: - 0/+ 3% of full scale (max.-point coverage).
Screened cable: 0.5 - 1.5 mm2/28-16 AWG.
Maximum cable length: 500 m (excl. potentiometer).
Potentiometer connected to +5 V, GND, any AI:
Use maximum 10 kΩ.
Maximum cable length: 100 m.
Analog output (AO)
Current sourcing capability only.
Voltage signal:
Current signal:
Tolerance: - 0/+ 4% of full scale (max-point coverage).
Screened cable: 0.5 - 1.5 mm2/28-16 AWG.
Maximum cable length: 500 m.
Pt100/1000 inputs (PT)
Temperature range:
Measurement tolerance: ± 1.5°C.
Measurement resolution: < 0.3°C.
Automatic range detection (Pt100 or Pt1000): Yes.
Sensor fault alarm: Yes.
Screened cable: 0.5 - 1.5 mm2/28-16 AWG.
Use Pt100 for short wires.
Use Pt1000 for long wires.
LiqTec sensor inputs
Use Grundfos LiqTec sensor only.
Screened cable: 0.5 - 1.5 mm2/28-16 AWG.
Grundfos Digital Sensor input and output (GDS)
Use Grundfos Digital Sensor only.
Power supplies (+5 V, +24 V)
+5 V:
+24 V:
Digital outputs (relays)
Potential-free changeover contacts.
Minimum contact load when in use: 5 VDC, 10 mA.
Screened cable: 0.5 - 2.5 mm2/28-12 AWG.
Maximum cable length: 500 m.
Bus input
Grundfos GENIbus protocol, RS-485.
Screened 3-core cable: 0.5 - 1.5 mm2/28-16 AWG.
Maximum cable length: 500 m.
EMC (electromagnetic compatibility)
EN 61800-3.
Residential areas, unlimited distribution, corresponding to CISPR 11, class B, group 1.
Industrial areas, unlimited distribution, corresponding to CISPR 11, class A, group 1.
Contact Grundfos for further information.
Enclosure class
Standard: IP55 (IEC 34-5).
Optional: IP66 (IEC 34-5).
Insulation class
F (IEC 85).
Torques
Terminal | Thread size | Max. torque [Nm] |
L1, L2, L3, L, N | M4 | 1.8 |
NC, C1, C2, NO | M2.5 | 0.5 |
1 to 26 and A, Y, B | M2 | 0.5 |
Motor [kW] | Max. speed stated on nameplate [min -1 ] | Speed -1 [min ] | Sound pressure level ISO 3743 [dB(A)] | |
1-phase motors | 3-phase motors | |||
0.25 to 0.75 | 2000 | 1500 | 38 | 38 |
2000 | 42 | 42 | ||
4000 | 3000 | 53 | 53 | |
4000 | 58 | 58 | ||
5900 | 4000 | 58 | 58 | |
5900 | 68 | 68 | ||
1.1 | 2000 | 1500 | 38 | |
2000 | 42 | |||
4000 | 3000 | 53 | 53 | |
4000 | 58 | 58 | ||
5900 | 4000 | 58 | 58 | |
5900 | 68 | 68 | ||
1.5 | 2000 | 1500 | ||
2000 | ||||
4000 | 3000 | 57 | 57 | |
4000 | 64 | 64 | ||
5900 | 4000 | 58 | 58 | |
5900 | 68 | 68 | ||
2.2 | 2000 | 1500 | ||
2000 | ||||
4000 | 3000 | 57 | ||
4000 | 64 | |||
5900 | 4000 | 58 | ||
5900 | 68 |
The grey fields indicate that the motor is not yet available in this MGE motor range, but is available in the previous MGE motor range.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Grundfos CRE Series, CRIE Series, CRNE Series, SPKE Series, MTRE Series Manual
Advertisement
Need help?
Do you have a question about the CRE Series and is the answer not in the manual?
Questions and answers