Advertisement

Grundfos CRE, CRNE Manual

General

GRUNDFOS E-pumps are pumps fitted with frequency-controlled standard motors for three-phase mains connection. The pumps have a built-in PI controller and can be connected to an external sensor enabling control of for instance pressure, differential pressure, temperature, differential temperature or flow in the system in which the pumps are installed. The pumps can be set to uncontrolled operation, i.e. the pump performance can be set according to the demand.
The pumps are typically used as pressure booster pumps in systems with variable demands.
The desired setpoint can be set directly on the pump control panel, via an input for external setpoint signal or by means of the GRUNDFOS wireless remote control R100.
All other settings are made by means of the R100.
Important parameters such as actual value of control parameter, power consumption, etc. can be read via the R100.
The pump incorporates inputs for external potential-free contacts for start/stop and digital function. The digital function enables external setting of max. curve, min. curve, external fault function or flow switch.
The pump incorporates an output for a potential-free fault, operating or ready signal.
Furthermore, the pump has an input for bus communication. Via the bus communication input, the pump can be controlled and monitored by a building management system or another external control system.

Installation

To ensure cooling of motor and electronics, the following must be observed:

  • Place the pump in such a way that sufficient cooling is ensured.
  • The temperature of the cooling air must not exceed 40°C.
  • Motor cooling fins and fan blades must be kept clean.

In the case of outdoor installation, it must be ensured that the motor is protected against climatic influences, such as rain, snow and ice.
Fig. 1 shows an example of an outdoor installation. To protect the motor against condensation on the electronic components, a cover has been fitted to the motor. In other cases, the specific operating conditions determine the protection solution.
Installation - Step 1
For further installation, see installation and operating instructions for the standard pump.

Handling

When the entire pump is to be lifted, observe the following:

  • CRE, CRNE 32, 45, 64 and 90 pumps fitted with MMGE motors of 11 kW should be lifted by means of the eye bolts fitted to the pump head.
  • CRE, CRNE 32, 45, 64 and 90 pumps fitted with MMGE motors of 15 kW and up to 22 kW should be lifted by means of the eye bolts fitted to the motor.

Handling examples are shown in fig. 2.
Installation - Step 2 - Handling

Electrical connection

Note: The user or the installer is responsible for the installation of the correct earthing and protection according to valid national and local standards. All operations must be carried out by a qualified electrician.
shock hazard Never make any connections in the pump terminal box unless the electricity supply has been switched off for at least 5 minutes.

Mains switch
The pump must be connected to an external all-pole mains switch with a contact separation of at least 3 mm in each pole according to IEC 364.

Protection against electric shock - indirect contact
shock hazard The pump must be earthed and protected against indirect contact in accordance with national regulations.
Protective earth conductors must always have a yellow/green (PE) or yellow/green/blue (PEN) colour marking.
Note: As the leakage current is > 10 mA, these motors must be connected to especially reliable/sturdy earth connections.
The leakage current of the pump can be found in section Leakage current.
EN 50 178 and BS 7671 specify the following:
The pump must be stationary and installed permanently. Furthermore, the pump must be connected permanently to the electricity supply or may be connected via an industrial type of plug (CEE). The plug must comply with EN 60 309 or IEC 309. This plug must incorporate an additional earthing contact which must be connected to an additional protective earth conductor having a minimum cross-sectional area of 4 mm².
In addition, tightened precautions as regards earth connection must be observed.
One of the following installation examples must be used:

  • A single protective earth conductor having a cross-sectional area of 10 mm².
  • Separate duplicate conductors each having a minimum crosssectional area of 4 mm².
  • Duplicate (protective earth) conductors in a multicore cable. One of the conductors may be the metallic armour or sheath of the cable.
  • A protective earth conductor contained in a cable conduit, trunking or cable tray so forming a duplicate conductor.

Additional protection
If the pump is connected to an electric installation where an earth leakage circuit breaker is used as additional protection, this circuit breaker must be of the type:

  • which is suitable for handling leakage currents and cutting-in with short pulse-shaped leakage.
  • which trips out when alternating fault currents and fault currents with DC content, i.e. pulsating DC and smooth DC fault currents, occur.

For these pumps an earth leakage circuit breaker type B must be used.
This circuit breaker must be marked with the following symbols:

Note: When an earth leakage circuit breaker is selected, the total leakage current of all the electrical equipment in the installation must be taken into account.
The leakage current of the pump can be found in section Leakage current.

Motor protection
The pump requires no external motor protection. The motor incorporates thermal protection against slow overloading and blocking.

Protection against mains voltage transients
The pump is protected against mains voltage transients in accordance with EN 61 800-3.

Supply voltage
3 x 380-415 V ±10%, 50/60 Hz, PE.
The supply voltage and frequency are marked on the pump nameplate. Please make sure that the motor is suitable for the electricity supply on which it will be used.
The wires in the pump terminal box must be as short as possible. Excepted from this is the protective earth conductor which must be so long that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry.
Figure 3 shows an example of a mains-connected pump with mains switch, back-up fuses and additional protection.
For maximum backup fuse, see section Supply voltage.
Installation - Step 3 - Electrical connection

Actual mains connection is shown in fig. 4.
Installation - Step 4

Start/stop of pump
The number of starts and stops via the mains voltage must not exceed 4 times per hour.
When the pump is switched on via the mains, it will start after approx. 5 seconds.
If a higher number of starts and stops is desired, the input for external start/stop must be used when starting/stopping the pump. When the pump is started/stopped via an external on/off switch, it will start immediately.

Other connections

The connection terminals of external potential-free contacts for start/stop and digital function, external setpoint signal, sensor signal, GENIbus and signal relay are shown in fig. 5.
Installation - Step 5
Note: If no external on/off switch is connected, short-circuit terminals 2 and 3 using a short wire.
Note: As a precaution, the wires to be connected to the following connection groups must be separated from each other by reinforced insulation in their entire lengths:

  1. Inputs (external start/stop, digital function, setpoint and sensor signals, terminals 1-8, and bus connection, A, Y, B).
    All inputs (group 1) are internally separated from the mainsconducting parts by reinforced insulation and galvanically separated from other circuits.
    All control terminals are supplied by protective extra-low voltage (PELV), thus ensuring protection against electric shock.
  2. Output (signal relay, terminals NC, NO, C).
    The output (group 2) is galvanically separated from other circuits. Therefore, the supply voltage or protective extra-low voltage can be connected to the output as desired.

A galvanically safe separation must fulfil the requirements for reinforced insulation including creepage distances and clearances specified in EN 50 178.

Signal cables

  • Use screened cables having a cross-sectional area of min.
    0.5 mm² and max. 1.5 mm² for external on/off switch, digital input, setpoint and sensor signals.
  • The screens of the cables must be connected to frame at both ends with good frame connection. They must be as close as possible to the terminals, fig. 6.
    Installation - Step 6 - Signal cables
  • Screws for frame connections must always be tightened whether a cable is fitted or not.
  • The wires in the pump terminal box must be as short as possible.

For the bus connection a screened 2-core cable must be used. Connect the screen to terminal Y at both ends, fig. 7.

Setting the pump

E-pumps can be set to two control modes, i.e. controlled and uncontrolled operation.
Setting the pump
In controlled-operation mode, the pump will adjust its performance to the desired setpoint for the control parameter (pressure, differential pressure, temperature, differential temperature or flow). Figure 8 shows a pressure-controlled pump as an example of controlled operation.
In uncontrolled-operation mode, the pump will operate according to the constant curve set.
The pumps have been factory-set to uncontrolled operation, see section Factory setting.

In addition to normal operation (controlled or uncontrolled operation), the following operating modes can be selected, Stop, Min. or Max..

The max. curve can for instance be used in connection with the venting procedure during installation.
The min. curve can be used in periods in which a minimum flow is required.
The operating modes (Stop, Normal, Min., Max.) can all be set on the pump control panel.
If the electricity supply to the pump is disconnected, the pump setting will be stored.
The remote control R100 offers additional possibilities of setting and status displays, see section Setting by means of R100.

Factory setting

The pumps have been factory-set to uncontrolled operation. The setpoint value corresponds to 100% of the maximum pump performance (see data sheet for the pump).
Other pump settings are marked with bold-faced type under each individual display in sections Menu OPERATION and Menu INSTALLATION.

Setting by means of control panel

warning At high system temperatures, the pump may be so hot that only the buttons should be touched to avoid burns.
The pump control panel, fig. 10, incorporates the following:

  • Buttons, "+" and "–", for setpoint setting.
  • Light fields, yellow, for indication of setpoint.
  • Indicator lights, green (operation) and red (fault).

Setpoint setting

The desired setpoint is set by pressing the button "+" or "–".
The light fields on the control panel will indicate the setpoint set.

Pump in controlled-operation mode (pressure control)

Figure 11 shows that the light fields 5 and 6 are activated, indicating a desired setpoint of 3 bar with a sensor measuring range from 0 to 6 bar. The setting range is equal to the sensor measuring range (see sensor nameplate).

Pump in uncontrolled-operation mode

In uncontrolled-operation mode, the pump performance is set within the range from min. to max. curve.

Setting to max. curve duty

Press "+" continuously to change over to the max. curve of the pump (top light field flashes). When the top light field is on, "+" must be pressed for 3 seconds before the light field starts flashing.
To change back, press "–" continuously until the desired setpoint is indicated.
Setting by means of control panel

Setting to min. curve duty

Press "–" continuously to change over to the min. curve of the pump (bottom light field flashes). When the bottom light field is on, "–" must be pressed for 3 seconds before the light field starts flashing.
To change back, press "+" continuously until the desired setpoint is indicated.

Start/stop of pump

Stop the pump by continuously pressing "–" until none of the light fields are activated and the green indicator light flashes.
Start the pump by continuously pressing "+" until the desired setpoint is indicated.

Setting by means of R100

The pump is designed for wireless communication with the GRUNDFOS remote control R100.
The R100 communicates with the pump via infra-red light. The transmitter and the receiver are incorporated in the pump control panel.
Setting by means of R100 - Step 1
During communication, the R100 must be pointed at the control panel.
When the R100 communicates with the pump, the red indicator light will flash rapidly.
The R100 offers additional possibilities of setting and status displays for the pump.

The displays are divided into four parallel menus:
Setting by means of R100 - Step 2

  1. GENERAL (see operating instructions for the R100)
  2. OPERATION
  3. STATUS
  4. INSTALLATION

The number stated at each individual display in fig. 16 refers to the section in which the display is described.

When communication between the R100 and the pump has been established, the first display in this menu will appear.

  1. Setpoint setting

    Setpoint set
    Actual setpoint
    Actual value
    In this display, the setpoint is set.
    In controlled-operation mode, the setting range is equal to the sensor measuring range.
    In uncontrolled-operation mode, the setpoint is set in % of the maximum performance. The setting range will lie between the min. and max. curves.
    Select one of the following operating modes:
    • Stop,
    • Min. (min. curve),
    • Max. (max. curve).

If the pump is connected to an external setpoint signal, the setpoint in this display will be the maximum value of the external setpoint signal, see section External setpoint signal.
If the pump is controlled via external signals (Stop, Min. curve or Max. curve) or a bus, this will be indicated in the display if setpoint setting is attempted.
In this case, the number of possible settings will be reduced, see section Priority of settings.

  1. Setting of operating mode

    Select one of the following operating modes:
    • Stop,
    • Min.,
    • Normal (duty),
    • Max.

The operating modes can be selected without changing the setpoint setting.

  1. Fault indications

    If the pump is faulty, the cause will appear in this display.
    Possible causes:
    • Too high motor temperature
    • Undervoltage
    • Overvoltage
    • Phase failure
    • Mains supply failure
    • Too many restarts (after faults)
    • Overload
    • Sensor signal outside signal range (only 4-20 mA)
    • Setpoint signal outside signal range (only 4-20 mA)
    • External fault
    • Dry running
    • Other fault

    A fault indication can be reset in this display if the cause of the fault has disappeared.

  2. Alarm log

    If faults have been indicated, the last five fault indications will appear in the alarm log. "Alarm log 1" shows the newest/latest fault.
    The example shows the fault indication "Undervoltage" and the fault code.

The displays appearing in this menu are status displays only. It is not possible to change or set values.
The displayed values are the values that applied when the last communication between the pump and the R100 took place. If a status value is to be updated, point the R100 at the control panel and press "OK".
If a parameter, e.g. speed, should be called up continuously, press "OK" constantly during the period in which the parameter in question should be monitored.
The tolerance of the displayed value is stated under each display. The tolerances are stated as a guide in % of the maximum values of the parameters.

  1. Display of actual setpoint
    Tolerance: ±2%

    This display shows the actual setpoint and the external setpoint in % of the range from minimum value to the setpoint set, see section External setpoint signal.
  2. Display of operating mode

    This display shows the actual operating mode (Stop, Min., Normal (duty) or Max.). Furthermore, it shows where this operating mode was selected (R100, Pump, BUS, External or Stop func.). For further details about the stop function (Stop func.), see section Menu INSTALLATION > step 8. Setting of stop function.
  3. Display of actual value

    The actually measured value of a connected sensor will appear in this display.
    If no sensor is connected to the pump, "–" will appear in the display.
  4. Display of actual speed
    Tolerance: ±5%

    The actual pump speed will appear in this display.
  5. Display of input power and power consumption
    Tolerance: ±10%

    This display shows the actual pump input power from the mains supply. The power is displayed in W.
    The pump power consumption can also be read from this display. The value of power consumption is an accumulated value calculated from the pump's birth and it cannot be reset.
  6. Display of operating hours
    Tolerance: ±2%

    The value of operating hours is an accumulated value and cannot be reset.
  1. Selection of control mode

    Select one of the following control modes (see fig. 8):
    • Controlled,
    • Uncontrolled.

    The desired performance is set in section Menu OPERATION > step 1.Setpoint setting.
    Note: If the pump is connected to a bus (see section Bus signal), it is not possible to select the control mode via the R100.

  2. Setting of controller

    In this display, the gain (Kp) and the integral-action time (Ti) of the built-in PI controller can be set if the factory setting is not the optimum setting:
    • The gain (Kp) is set within the range from 0.1 to 20.
    • The integral-action time (Ti) is set within the range from 0.1 to 3600 s. If 3600 s is selected, the controller will function as a P controller.

    Furthermore, it is possible to set the controller to inverse control (if the setpoint is increased, the speed will be reduced). In the case of inverse control, the gain (Kp) must be set within the range from –0.1 to –20.
    Setting the PI controller:
    For most applications, the factory setting of the controller constants Kp and Ti will ensure optimum pump operation. In the following cases, a change of the setting can be useful or necessary.
    A change of the Ti setting can be useful:

    • in a differential-pressure control system if the sensor is placed far away from the pump.

    A change of the Ti setting, and in some cases the Kp setting, may be necessary:

    • if the pump is controlled on the basis of temperature or differential temperature.

    The table below shows the recommended controller settings:

    System/application Kp Ti
    Heating system1 Cooling system2
    0.5 0.5
    0.5 L < 5 m: 0.5
    L > 5 m: 3
    L > 10 m: 5
    0.5 0.5
    0.5 0.5
    0.5 –0.5 10 + 5L
    0.5 10 + 5L
    0.5 –0.5 30 + 5L
    1. Heating systems are systems in which an increase in pump performance will result in a rise in temperature at the sensor.
    2. Cooling systems are systems in which an increase in pump performance will result in a drop in temperature at the sensor.
  3. Selection of external setpoint signal

    The input for external setpoint signal can be set to different signal types.
    Select one of the following types:
    • 0-5 V (potentiometer),
    • 0-10 V,
    • 0-20 mA,
    • 4-20 mA,
    • Not active.

    If Not active is selected, the setpoint set by means of the R100 or on the control panel will apply.
    The setpoint set is the maximum value of the external setpoint signal, section External setpoint signal. The actual value of the external setpoint can be read from section Menu STATUS > step 1. Display of actual setpoint.

  4. Selection of fault, operating or ready signal relay

    It can be selected in which situation the relay should be activated:
    • Fault (fault indication),
    • Operation (operating indication),
    • Ready (ready indication).

    See section Indicator lights and signal relay.

  5. Blocking of the buttons on the pump

    The buttons "+" and "–" on the pump can be set to:
    • Active,
    • Not active.
  6. Allocation of pump number

    A number between 1 and 64 can be allocated to the pump. In the case of bus communication, a number must be allocated to each pump.
  7. Selection of function for digital input

    The digital input of the pump (terminal 1, fig. 5) can be set to different functions.
    Select one of the following functions:
    • Min. (min. curve),
    • Max. (max. curve),
    • Ext. fault (external fault),
    • Flow switch.

    The selected function is activated by closing the contact between terminals 1 and 3 (fig. 5).
    See also section Digital input.
    Min.:
    When the input is activated, the pump is operating according to the min. curve.
    Max.:
    When the input is activated, the pump is operating according to the max. curve.
    Ext. fault:
    When the input is activated, a timer is started. If the input is activated for more than 5 seconds, the pump is stopped and a fault is indicated. If the connection is disconnected for more than 5 seconds, the fault condition will cease and the pump can be restarted manually by resetting the fault indication.
    The typical application will be detection of missing inlet pressure or water shortage by means of a pressure switch installed on the suction side of a pump.
    Flow switch:
    When this function is active, the pump will be stopped when a connected flow switch detects a low flow.
    It is only possible to use this function if the pump is connected to a pressure sensor.
    When the input is activated for more than 5 seconds, the stop function incorporated in the pump will take over, see below.

  8. Setting of stop function

    When the stop function is active, the pump will be stopped at very low flows to avoid unnecessary power consumption. It is only possible to use this function if the pump is connected to a pressure sensor.
    The stop function can be set to:
    • Active,
    • Not active.

    There are two possibilities of low-flow detection:

    1. By means of the built-in "low-flow detector" which automatically starts functioning if no flow switch is chosen/connected to the digital input. The pump will check the flow regularly by reducing the speed for a short time, thus checking the change in pressure. If there is no or a small change in pressure, the pump will detect a low flow.
    2. By means of a flow switch connected to the digital input. When the input is activated for more than 5 seconds, the stop function of the pump takes over. Unlike the built-in low-flow detector, the flow switch measures the minimum flow at which the pump must stop. The pump will not check the flow regularly by reducing the speed.

    When the pump detects a low flow, the speed will be increased until the stop pressure (actual setpoint + 0.5 x ∆H) is reached and the pump stops. When the pressure has fallen to the start pressure (actual setpoint – 0.5 x ∆H), the pump will restart.
    ∆H indicates the difference between start and stop pressures.
    Setting by means of R100 - Step 3
    ∆H is factory-set to 10% of actual setpoint.
    ∆H can be set within the range from 5% to 30% of actual setpoint.
    Note: The non-return valve must be fitted immediately before the pump, fig. 18. If the non-return valve is fitted between pump and diaphragm tank, the pressure sensor must be fitted after the nonreturn valve.

    The stop function requires a diaphragm tank of a certain minimum size. The tank must be installed immediately after the pump and the precharge pressure must be 0.7 x actual setpoint.
    Recommended diaphragm tank size when no flow switch is connected.

    Nominal flow of pump
    [m³/h]
    Diaphragm tank size
    [litres]
    0-6 8
    7-24 18
    25-40 50
    41-70 120
    71-100 180

    If a diaphragm tank of the above size is installed in the system, the factory setting of ∆H is the correct setting.
    If the tank installed is too small, the pump will start and stop too often. This can be remedied by increasing ∆H.

  9. Setting of sensor

    The setting of the sensor is only carried out in the case of controlled operation.
    Select the following:
    • Sensor output signal 0-5 V, 0-10 V, 0-20 mA or 4-20 mA,
    • sensor measuring unit (bar, mbar, m, kPa, psi, ft, m³/h, m³/s, l/s, gpm, °C, °F or %) and
    • sensor measuring range.
  10. Setting of min. and max. curves

    Set the min. and max. curves in % of maximum performance if the operating range must be reduced.
    • The max. curve can be adjusted within the range from maximum performance (100%) to min. curve.
    • The min. curve can be adjusted within the range from max. curve to 12% of maximum performance. The pump has been factory-set to 24% of maximum performance.
    • The operating range lies between the min. and max. curves.

External forced-control signals

The pump has inputs for external signals for the forced-control functions:

  • Start/stop of pump.
  • Digital function.

Start/stop input

Functional diagram: Start/stop input:
External forced-control signals - Part 1

Digital input

By means of the R100, one of the following functions can be selected for the digital input:

  • Min. curve.
  • Max. curve.
  • External fault.
  • Flow switch.

Functional diagram: Input for digital function:
External forced-control signals - Part 2

External setpoint signal

By connecting an analog signal transmitter to the input for the setpoint signal (terminal 4), it is possible to remote-set the setpoint.
The actual external signal 0-5 V, 0-10 V, 0-20 mA, 4-20 mA, must be selected via the R100, see section Menu INSTALLATION > 3.Selection of external setpoint signal.
If uncontrolled operation is selected by means of the R100, the pump can be controlled by any controller.
In controlled-operation mode, the setpoint can be set externally within the range from the lower value of the sensor measuring range to the setpoint set on the pump or by means of the R100.
External setpoint signal
Example: At a lower pressure-sensor value of 0 bar, a setpoint set of 5 bar and an external setpoint of 80%, the actual setpoint will be as follows:
Hactual = (Hset – Hlower) x %external setpoint + Hlower
= (5 - 0) x 80% + 0
= 4 bar

In uncontrolled-operation mode, the setpoint can be set externally within the range from the min. curve to the setpoint set on the pump or by means of the R100.

Bus signal

The pump enables serial communication via an RS-485 input. The communication is carried out according to the GRUNDFOS bus protocol, GENIbus protocol, and enables connection to a building management system or another external control system.
Via the bus signal, it is possible to remote-set pump operating parameters, like setpoint, operating mode, etc. At the same time, the pump can provide status information about important parameters, like actual value of control parameter, input power, fault indications, etc.
Contact GRUNDFOS for further details.
Note: If a bus signal is used, the number of settings available via the R100 will be reduced.

Priority of settings

The start/stop and digital inputs will influence the number of possible settings.
By means of the R100, the pump can always be set to max. curve duty or to stop.
If two or more functions are activated at the same time, the pump will operate according to the function with the highest priority.
The priority of the settings is as shown in the following tables:

Without bus signal
Priority Possible settings
Control panel on pump or R100 External signals
1 Stop
2 Max. curve
3 Stop
4 Max. curve
5 Min. curve Min. curve
6 Setpoint setting Setpoint setting

Example: If, via the digital input, the pump has been forced to operate according to the max. curve, the pump control panel and the R100 can only set the pump to stop.

With bus signal
Priority Possible settings
Control panel on pump or R100 External signals Bus signal
1 Stop
2 Max. curve
3 Stop Stop
4 Max. curve
5 Min. curve
6 Setpoint setting

Example: If, via the digital input, the pump has been forced to operate according to the max. curve, the pump control panel, the R100 and the bus signal can only set the pump to stop.

Indicator lights and signal relay

The operating condition of the pump is indicated by the green and red indicator lights on the pump control panel.

The pump incorporates an output for a potential-free signal via an internal relay.
The signal output can be set to fault, operating or ready indication by means of the R100, see section Menu INSTALLATION > 4. Selection of fault, operating or ready signal relay.
The functions of the two indicator lights and the signal relay are as shown in the following table:

Indicator lights Signal relay activated during: Description
Fault
(red)
Operation
(green)
Fault Operation Ready
Off Off The electricity supply has been switched off.
Off Permanently on The pump is operating.
Off Flashing The pump has been set to stop.
Permanently on Off The pump has stopped because of a fault. Restarting will be attempted (it may be necessary to restart the pump by resetting the fault indication). In case of the fault causes "dry running" and "external fault", the pump must be restarted manually by resetting the fault indication.
Permanently on Permanently on The pump is operating, but it has been stopped because of a fault.
If the cause is "sensor signal outside signal range", the pump will continue operating according to the max. curve and the fault indication cannot be reset until the signal is inside the signal range.
If the cause is "setpoint signal outside signal range", the pump will continue operating according to the min. curve and the fault indication cannot be reset until the signal is inside the signal range.
Permanently on Flashing The pump has been set to stop, but it has been stopped because of a fault.

A fault indication can be reset in one of the following ways:

  • By briefly pressing the button "+" or "–" on the pump. This will not change the setting of the pump. A fault indication cannot be reset by means of "+" or "–" if the buttons have been locked.
  • By switching off the electricity supply until the indicator lights are off.
  • By means of the R100, see section Menu OPERATION > 3. Fault indications.

When the R100 communicates with the pump, the red indicator light will flash rapidly.

Megging

Note: Megging of an installation incorporating E-pumps is not allowed, as the built-in electronics may be damaged.

Technical data

Supply voltage

3 x 380-415 V ±10%, 50/60 Hz, PE.
See nameplate.

Back-up fuse

Motor size
[kW]
Max.
[A]
11 25
15 35
18.5 50
22 50

Standard as well as quick-blow or slow-blow fuses may be used.

Leakage current

Earth leakage current > 30 mA.
The leakage currents are measured in accordance with EN 60 355-1.

Inputs/output

Start/stop
External potential-free switch.
Voltage: 5 VDC.
Current: < 5 mA.
Screened cable.*

Digital
External potential-free switch.
Voltage: 5 VDC.
Current: < 5 mA.
Screened cable.*

Setpoint signals

  • Potentiometer
    0-5 VDC, 10 kΩ (via internal voltage supply).
    Screened cable.*
    Maximum cable length: 100 m.
  • Voltage signal
    0-5 VDC/0-10 VDC, Ri > 50 kΩ.
    Tolerance: +0%/–3% at maximum voltage signal.
    Screened cable.*
    Maximum cable length: 500 m.
  • Current signal
    DC 0-20 mA/4-20 mA, Ri = 250 Ω.
    Tolerance: +0%/–3% at maximum current signal.
    Screened cable.*
    Maximum cable length: 500 m.

Sensor signals

  • Voltage signal
    0-5 VDC/0-10 VDC, Ri > 50 kΩ (via internal voltage supply).
    Tolerance: +0%/–3% at maximum voltage signal.
    Screened cable.*
    Maximum cable length: 500 m.
  • Current signal
    DC 0-20 mA/4-20 mA, Ri = 250 Ω.
    Tolerance: +0%/–3% at maximum current signal.
    Screened cable.*
    Maximum cable length: 500 m.
  • Electricity supply to sensor:
    +24 VDC, max. 40 mA.
    +5 VDC, max. 5 mA.

Signal relay output
Potential-free changeover contact.
Maximum contact load: 250 VAC, 2 A.
Minimum contact load: 5 VDC, 1 mA.
Screened cable: 0.5 - 2.5 mm².
Maximum cable length: 500 m.

Bus input
GRUNDFOS bus protocol, GENIbus protocol, RS-485.
0.5 - 1.5 mm² screened 2-core cable.
Maximum cable length: 500 m.
* Cross section min. 0.5 mm² and max. 1.5 mm².

Other technical data

EMC (electromagnetic compatibility)
EN 61 800-3.
Immunity to electromagnetic disturbance - second environment (industrial areas).
Contact GRUNDFOS for further information.

Enclosure class
Standard: IP 54 (IEC 34-5).

Insulation class
F (IEC 85).

Ambient temperature
During operation: –20°C to +40°C.
During storage/transport: –30°C to +60°C.

Relative air humidity
Maximum 95%.

Sound pressure level

Motor
[kW]
Speed stated on nameplate
[min-1]
Sound pressure level
[dB(A)]
11 2800-3000 69
15 2800-3000 70
18.5 2800-3000 70
22 2800-3000 73

Re-lubrication of motor motor bearings

The motor bearings are pre-lubricated on delivery. After approx. 3000 operating hours, the bearings must be re-lubricated.
Note: Before re-lubrication, the bottom plug in the motor flange and the plug in the bearing cover must be removed to ensure that old and excess grease can run out.
When lubricating the first time, use the double quantity of lubricating grease as the lubricating channel is still empty.

Frame size Quantity of lubricating grease
[ml]
Lubricating intervals
[hours]
Drive end
(DE)
Non-drive end
(NDE)
MMGE 160 23 20 3000
MMGE 180 23 23

The recommended grease type is Asonic GHY 72, which is a polycarbamide-based lubricating grease.

Documents / Resources

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Grundfos CRE, CRNE Manual

Advertisement

Need help?

Need help?

Do you have a question about the CRE and is the answer not in the manual?

Questions and answers

Table of Contents