Page 1
SR-1600 PLUS Inverter Operation Handbook Document: IPN 997-00012-97A Issue 1, April 2023 Eaton Corporation Eaton.com DCinfo@eaton.com...
Page 2
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to...
2 Functional Characteristics Introduction 2.1 System The SR-1600 PLUS is a highly reliable, modular design DC-AC inverter system, designed with advanced power electronics and microprocessor technology offering the following features: Simple setting and scalable system capacity that supports up to 32 pcs (51.2KW) ...
PLUS PLUS PLUS Transfer Utility AC to 0 second Performance Inverter Operating Temp. -25°C ~ 40°C; refer to SR-1600 PLUS power de-rating curve Storage Temp. -40℃~70℃ Environment Relative Humidity 95%, non-condensing Vibration Meet BS EN 61373 Safety standards Meets UL 62368-1...
2.5 SR-1600 PLUS De-rating Curve Figure 3. SR-1600 PLUS de-rating curve: SR-1600-124/224 PLUS Figure 4. SR-1600 PLUS de-rating curve: SR-1600-148/248 PLUS 2.6 Protection Mechanism Over Voltage Under Voltage Type Shutdown Restart Alarm Shutdown Restart Alarm 130±3% 125±3% 125±3% 90±3% 95±3% 95±3%...
Parallel connection: non-terminal shelf (Refer to 3-2-2.) Table 8. SR-1600 PLUS jumper A & B status description *Note: Jumper A pin1 & pin2 must be shorted and Jumper B pin1 & pin2 must be shorted. Dry contact and remote ⑨...
Page 20
Signal voltage: 5V wire size 20~24AWG / 0.5~0.25mm Low: 0V Normal Digital signal input for Pin 13~14 Minor alarm Table 9. SR-1600 PLUS CN3 status description Possible Cause Alarm Description The system over the rated capacity (OLA >15sec) Overload Module Fault Parallel Fault or Module Fault Over Temp.
AC Input Terminal ④ SR-1600 PLUS provides the AC utility input terminal at the rear side, and the user can connect the AC cable at L / N / PE. The SR-1600 PLUS supports the AC input side internal parallel connection.
Connect the 24V/48V battery [+] / [-] to the SR-1600 PLUS [DC+] / [DC-] There are four battery input sets (DC+, DC-) on the SR-1600 PLUS rear side, and every set is independent. In case the user needs parallel connection, please do the parallel wiring outside the SR-1600 PLUS (please refer to following typical wiring figures).
Page 23
Figure 13. SR-1600 PLUS battery cabling (multi battery I) Figure 14. SR-1600 PLUS battery cabling (multi battery II) Please refer to the suggested battery cable size. Cable diameter / Fuse (slow) / Fuse (slow) / Models AWG / mm per module...
Figure 15. SR-1600 PLUS installation space requirement Note: Keep minimum 20 cm clear space for air flow at front and rear side of SR-1600 Plus. Note: The rack chassis must be fixed and supported at both the front and rear.
Warning! Please utilise a technically competant person to replace fan the module. Step 1: Please follow the 3-3-1-1. to remove the SR-1600 PLUS module out of shelf. Step 2: Use a screwdriver to remove the 4 screws on the fan module (top side 2 pcs, rear side 2 pcs), and user can then remove the fan module.
Eaton or local distributor. Your local Eaton sales office can confirm the warranty status, duration and conditions. This warranty will be considered void if the unit has been misused, altered, or accidentally damaged. Eaton is not liable for anything that occurs as a result of the user’s fault.
Please enter as much information as you can. Send the completed form, together with the item for repair to your nearest authorized service agent. NOTE: Only one fault to be recorded per form. For further information contact your local Eaton dc product supplier or Eaton (see contact details on page 39). Date: ________________...
Need help?
Do you have a question about the SR-1600 PLUS and is the answer not in the manual?
Questions and answers