All other changes to the hardware and/or software and the non-conforming use of the components entail the exclusion of liability on part of WAGO Kon- takttechnik GmbH & Co. KG.
More information References on additional literature, manuals, data sheets and internet pages. 1.3 Number Notation Number Code Example Note Decimal normal notation Hexadecimal 0x64 C notation Binary '100' within inverted commas, '0110.0100' nibble separated with dots WAGO-I/O-SYSTEM 750 I/O Modules...
Do not use any contact spray. The spray may impair the functioning of the contact area. The WAGO-I/O-SYSTEM 750 and its components are an open system. It must only be assembled in housings, cabinets or in electrical operation rooms. Access must only be given via a key or tool to authorized qualified personnel.
8 • 750-473 [2 AI 4-20 mA, Single-Ended, S.C.Protec.] Description 2.1.1.3 Description The analog input module and its variations receives signals with standardized values of 4-20 mA. 2- or 3-conductor sensors without own power supply may be connected to the input module, e.g.
However, if such a case should occur, another supply module must be added. The analog input module can be used with all couplers/controllers of the WAGO-I/O-SYSTEM 750 (except for the economy types 750-320, -323, -324 and -327). 2.1.1.4 Display Elements...
10 • 750-473 [2 AI 4-20 mA, Single-Ended, S.C.Protec.] Schematic Diagram 2.1.1.5 Schematic Diagram AI 1 AI 2 U V 1 U V 2 24 V 24 V Logic Error Function 10 nF Shield Shield (screen) (screen) 750-473 Fig. 2.1.1-3: 2-Channel Analog Input Module 750-473...
750-473 [2 AI 4-20 mA, Single-Ended, S.C.Protec.] • 11 Technical Data 2.1.1.6 Technical Data Module Specific Data Number of inputs Voltage supply via system voltage DC /DC Current consumption . (internal) 100 mA Signal current 4 mA ... 20 mA...
Some fieldbus systems can process input channel status information by means of a status byte. This status byte can be displayed via the starting tool WAGO-I/O-CHECK 2. However, processing via the coupler / controller is optional, which means that accessing or parsing the status information depends on the fieldbus system.
Process Image 2.1.1.7.1 Standard Data Format For the standard module 750-473 and the variations 750-473/005-000 the in- put current ranging from 0 mA to 32 mA is scaled on the numerical values ranging from 0x0000 to 0x7FF9. Process values of module 750-473, 750-473/005-000...