Bms control system
Hide thumbs Also See for PTP:

Advertisement

BMS OBJECT LIST AND DEFAULT VALUES
MODBUS
Table 7.1: Modbus FC Object List
No.
Object
Value
1
0x0000
-50...200°F (-46...93°C)
2
0x0001
-50...200°F (-46...93°C)
3
0x0002
-40...90°F (5...32°C)
4
0x0003
-40...90°F (5...32°C)
5
0x0004
60...80°F (15...26°C)
6
0x0005
0...4°F (0...2°C)
7
0x0006
0...6°F (0...3°C)
8
0x0007
1-On, 0-Off
9
0x0008
1-On, 0-Off
10
0x0009
1-On, 0-Off
11
0x000A
1-On, 0-Off
12
0x000B
1-On, 0-Off
13
0x000C
1-On, 0-Off
14
0x000D
1-On, 0-Off
15
0x000E
1-On, 0-Off
16
0x000F
1-On, 0-Off
17
0x0010
1-On, 0-Off
18
0x0011
1-On, 0-Off
19
0x0012
1-On, 0-Off
20
0x0013
1-On (°C), 0-Off (°F)
21
0x0014
1-On, 0-Off
22
0x0015
1-On, 0-Off
23
0x0016
1-On, 0-Off
24
0x0017
1-On, 0-Off
25
0x0018
1-On, 0-Off
26
0x0019
1-On, 0-Off
* If a setpoint outside of the range defined above is sent via BMS to the controller no change will happen and the unit will continue to
operate to the last known setpoint.
Object Name
ra_temp_BMS
Control Temperature in Room
intake_air_temp_BMS
Temperature at Unit
heat_setpt_BMS
Heating Setpoint
fan_setpt_BMS
Cooling / Fan-Only Setpoint
Saver_setpt_BMS
Energy Saver Mode Setpoint
setpoint_band
Heating/Cooling Setpoint Deadband
saver_band
Energy Saver Mode Setpoint Deadband
din_supply_fan
Thermostat G Call
Thermostat W/W1 Call (Low or Single
din_heat1
Stage)
din_heat2
Thermostat W2 Call (High Stage)
Valve_status
Gas Valve Status
Powered Exhauster Pressure Switch
Pressure_Switch_status
Status
Highlimit_FRO_status
Temperature Limit or Flame Rollout Status
Supply_fan
Fan Relay
Gas_ht1
Low or Single Stage Gas Valve Relay
Gas_ht2
High Stage Gas Valve Relay
alarm
General Alarm
Superv_OnOff
Supervisor On/Off Control
heartbeat
BMS Communication Heartbeat
C_F_Scale
Setting of Temperature Units
al_BrokenPrbTemp
Temperature Sensor Failure Alarm
al_highlimit_FRO_alarm Temperature Limit or Flame Rollout Alarm
al_pressure_switch
Powered Exhauster Pressure Switch Alarm
al_valve_ignition_alarm
Gas Valve Ignition Alarm
SummerWinter
Setting of Summer/Winter Mode
BV_RestoreDefault
Restores all Values to Default
6.520.3
Description
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Default
R
-
R
-
70°F (21°C)
75°F (24°C)
80°F (26°C)
1°F (1°C)
3°F (1.5°C)
R
0
R
0
R
0
R
0
R
0
R
0
R
0
R
0
R
0
R
0
1
R
0
0
R
0
R
0
R
0
R
0
0
0
7