BMS OBJECT LIST AND DEFAULT VALUES
BACNET
Table 6.1: BACnet MSTP Object List
No.
Object
Analog Inputs
1
Analog Input #3
2
Analog Input #4
Analog Values
3
Analog Value #0
4
Analog Value #1
5
Analog Value #2
6
Analog Value #3
7
Analog Value #5
8
Analog Value #10
Binary Inputs
9
Binary Output #12
10
Binary Output #13
11
Binary Output #14
12
Binary Output #15
13
Binary Output #16
14
Binary Output #17
Binary Outputs
15
Binary Output #0
16
Binary Output #1
17
Binary Output #2
18
Binary Output #3
Binary Values
19
Binary Value #12
20
Binary Value #1
21
Binary Value #5
22
Binary Value #6
23
Binary Value #7
24
Binary Value #8
25
Binary Value #9
26
Binary Value #11
27
Binary Value #0
* If a setpoint outside of the range defined above is sent via BMS to the controller no change will happen and the unit will continue to operate
to the last known setpoint.
6
Value
-50...200°F (-46...93°C) ra_temp_BMS
-50...200°F (-46...93°C) intake_air_temp_BMS
-40...90°F (5...32°C)
heat_setpt_BMS
-40...90°F (5...32°C)
fan_setpt_BMS
60...80°F (15...26°C)
Saver_setpt_BMS
0...4°F (0...2°C)
setpoint_band
0...6°F (0...3°C)
saver_band
0-4000193
BacnetDeviceInstanceNumber Bacnet Device ID
1-On, 0-Off
din_supply_fan
1-On, 0-Off
din_heat1
1-On, 0-Off
din_heat2
1-On, 0-Off
Valve_status
1-On, 0-Off
Pressure_Switch_status
1-On, 0-Off
Highlimit_FRO_status
1-On, 0-Off
Supply_fan
1-On, 0-Off
Gas_ht1
1-On, 0-Off
Gas_ht2
1-On, 0-Off
alarm
1-On (°C), 0-Off (°F)
C_F_Scale
1-On, 0-Off
heartbeat
1-On, 0-Off
al_BrokenPrbTemp
1-On, 0-Off
al_highlimit_FRO_alarm
1-On, 0-Off
al_pressure_switch
1-On, 0-Off
al_valve_ignition_alarm
1-On, 0-Off
Summer_winter
1-On, 0-Off
RestoreDefault
1-On, 0-Off
Superv_OnOff
Object Name
Control Temperature in Room
Temperature at Unit
Heating Setpoint
Cooling / Fan-Only Setpoint
Energy Saver Mode Setpoint
Heating/Cooling Setpoint
Deadband
Energy Saver Mode Setpoint
Deadband
Thermostat G Call
Thermostat W/W1 Call (Low or
Single Stage)
Thermostat W2 Call (High Stage)
Gas Valve Status
Powered Exhauster Pressure
Switch Status
Temperature Limit or Flame Rollout
Status
Fan Relay
Low or Single Stage Gas Valve
Relay
High Stage Gas Valve Relay
General Alarm
Setting of Temperature Units
BMS Communication Heartbeat
Temperature Sensor Failure Alarm
Temperature Limit or Flame Rollout
Alarm
Powered Exhauster Pressure
Switch Alarm
Gas Valve Ignition Alarm
Setting of Summer/Winter Mode
Restores all Values to Default
Supervisor On/Off Control
6-520.3
Description
R/W
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R/W
R
R
R
R
R
R/W
R/W
R/W
Default
-
-
70°F (21°C)
75°F (24°C)
80°F (26°C)
1°F (1°C)
3°F (1.5°C)
315000+MAC
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1