Diagnostic information
The fault can be identified using the diagnostic information. The short text helps you by
providing information about the fault. In addition, the corresponding symbol for the
diagnostic behavior is displayed in front of the diagnostic information on the local display.
12.3.2
Calling up remedy information
Remedy information is provided for every diagnostic event to ensure that problems can be
rectified quickly:
• On the home page
Remedy information is displayed in a separate field below the diagnostics information.
• In the Diagnostics menu
Remedy information can be called up in the working area of the user interface.
The user is in the Diagnostics menu.
1. Call up the desired parameter.
2. On the right in the working area, mouse over the parameter.
 A tool tip with remedy information for the diagnostic event appears.
12.4
Adapting the diagnostic information
12.4.1
Adapting the diagnostic behavior
Each item of diagnostic information is assigned a specific diagnostic behavior at the
factory. The user can change this assignment for certain diagnostic information in the
Diagnostic behavior submenu .
"Expert" menu → System → Diagnostic handling → Diagnostic behavior
12.4.2
Adapting the status signal
Each item of diagnostic information is assigned a specific status signal at the factory. The
user can change this assignment for certain diagnostic information in the Diagnostic
event category submenu .
"Expert" menu → Communication → Diagnostic event category
Available status signals
Configuration as per FOUNDATION Fieldbus Specification (FF912), in accordance with
NAMUR NE107.
Symbol
Meaning
Failure
A device error has occurred. The measured value is no longer valid.
A0013956
Function check
The device is in service mode (e.g. during a simulation).
A0013959
Out of specification
The device is operated:
• Outside its technical specification limits (e.g. outside the process temperature range)
• Outside of the configuration carried out by the user (e.g. maximum flow in parameter
A0013958
20 mA value)
Maintenance required
Maintenance is required. The measured value remains valid.
A0013957
Diagnostics and troubleshooting
99