Transmitting the diagnostic information over the bus
Prioritizing diagnostic information for transmission over the bus
Diagnostic information is only transmitted over the bus if its priority is between 2 and 15.
Priority 1-events are displayed but are not transmitted over the bus. Diagnostic
information with priority 0 (default value) is ignored.
It is possible to change the priority individually for the different status signals. The
following parameters of the Resource Block are used for this purpose:
• FD_FAIL_PRI
• FD_CHECK_PRI
• FD_OFFSPEC_PRI
• FD_MAINT_PRI
Suppressing certain diagnostic information
It is possible to suppress certain events during transmission over the bus using a mask.
While these events are displayed they are not transmitted over the bus. This mask is in
FieldCare Expert → Communication → Field diagnostics → Alarm broadcast enable. The
mask is a negative selection mask, i.e. if a field is selected the associated diagnostic
information is not transmitted over the bus.
12.5
Overview of diagnostic information
The amount of diagnostic information and the number of measured variables affected
increase if the measuring device has one or more application packages.
Diagnostic
Short text
number
Diagnostic of sensor
022
Sensor temperature
046
Sensor limit exceeded
062
Sensor connection
082
Data storage
083
Memory content
140
Sensor signal
Diagnostic of electronic
242
Software incompatible
252
Modules incompatible
261
Electronic modules
Diagnostics and troubleshooting
Remedy instructions
1.Change main electronic module
2.Change sensor
1. Inspect sensor
2. Check process condition
1.Change main electronic module
2.Change sensor
1.Change main electronic module
2.Change sensor
1. Restart device
2. Restore S-Dat data
3. Change sensor
1.Check or change main electronics
2.Change sensor
1. Check software
2. Flash or change main electronics
module
1. Check electronic modules
2. Change I/O or main electronic
module
1. Restart device
2. Check electronic modules
3. Change I/O Modul or main
electronics
Status
Diagnostic
signal
behavior
[from the
[from the
factory]
factory]
F
Alarm
1)
S
Warning
F
Alarm
F
Alarm
F
Alarm
1)
S
Warning
F
Alarm
F
Alarm
F
Alarm
103