It works with input voltages ranging 10V ~ 500V, supporting a wide range of applications. The PM-4324A is the same model as the PM-4324, except for the AC Measurement. The PM-4324A has 2 independent main circuit inputs, which can be used in different power supply systems.
Page 9
5.08mm (For Measurement Voltage, Aux Power and Alarm Output): Use Copper Conductors Only, wires range 12-24 AWG, torque value 7.0 lb-in. 7.62mm: Use Copper Conductors Only, wires range 12-24 AWG, torque value 4.5 lb-in. PM-4324A User’s Manual v1.03 Last Revised:Apr. 2024 Page: 9 ...
Page 12
Please re-confirm the measure position. PM-4324A series can be installed as rail mounting mode or embedded, no need to drill a hole or screw to fix it (rail mounting width can up to the length of 35 mm). ...
3.2.2. Mounting and Dismounting Mounting Assembly: Place the PM-4324A on the DIN-Rail. Push the front of the PM-4324A toward the mounting surface until it audibly snaps into place. Dismantling: Pull out the latch and then remove the PM-4324A from the DIN-Rail ...
Page 16
1. The external CT’s are fragile, please handle with care. 2. The current input of PM-4324A series is in mA range. Only the ex-factory attached CT’s can be used. The other CT’s, for example, from panel will damage the instrument due to its large current (around 5A) 3.
Page 18
CT1 ~ CT12 for reference voltage V1; CT13 ~ CT24 for reference voltage V2. 1P2W-3CT (PM-4324A): CT1 ~ CT12 for reference voltage V1; CT13 ~ CT24 for reference voltage V2. PM-4324A User’s Manual v1.03 Last Revised:Apr. 2024 Page: 18 ...
Page 19
CT1 ~ CT12 for reference voltage V1; CT13 ~ CT24 for reference voltage V2. 3P3W-2CT (PM-4324A): CT1 ~ CT12 for reference voltage V1; CT13 ~ CT24 for reference voltage V2. PM-4324A User’s Manual v1.03 Last Revised:Apr. 2024 Page: 19 ...
Page 20
CT1 ~ CT12 for reference voltage V1; CT13 ~ CT24 for reference voltage V2. 3P4W-3CT (PM-4324A): CT1 ~ CT12 for reference voltage V1; CT13 ~ CT24 for reference voltage V2. PM-4324A User’s Manual v1.03 Last Revised:Apr. 2024 Page: 20 ...
Page 24
1M bps Add the Bias Resistor on RS-485 Network for stable signal The RS-485 master is required to provide the bias for PM-4324A series. Otherwise, the tM-SG4 or SG-785 should be added to provide the bias. All ICP DAS controllers and converters provide the bias.
OFF position and repower on after settings changed. User also can recover settings to default value by Modbus command. SW9-SW12 setting PM-4324A:Select the different wiring mode (Please select the Software setting, if 1P2W-1CT, 1P2W-3CT or 1P3W-2CT is used) Reference voltage...
In the Power Meter Utility, please select “Modbus TCP” in the Communication Interface. Click “Search” to enter the “Communication Interface Setting” window. Click ”Search” button to search the available power meter. PM-4324A User’s Manual v1.03 Last Revised:Apr. 2024 Page: 49 ...
Page 50
Select the power meter which you want to modify parameters from the meter list, then click ”Configuration” button to setup the meter parameters. After complete all setting, click “OK”, and return to the meter list windows. PM-4324A User’s Manual v1.03 Last Revised:Apr. 2024 Page: 50 ...
Page 54
SW7-SW8 setting PM-4324A-CPS:For CANopen Baud Rate Setting Baud Rate SW 7 125 K bps(Default) 250 K bps 500 K bps 1M bps SW9-SW10 setting PM-4324A-CPS:Select the different wiring mode (Please select the Software setting, if 1P2W-1CT, 1P2W-3CT or 1P3W-2CT is used)
Page 56
After finishing the transmission of the initiate SDO upload protocol, the SDO client will start to upload the data. The upload SDO segment protocol will comply with the process shown below. PM-4324A User’s Manual v1.03 Last Revised:Apr. 2024 Page: 56 ...
Page 57
4 bytes, the download action will finish in the download initialization protocol. Otherwise, the download segment protocol will be needed. These two protocols are shown below. PM-4324A User’s Manual v1.03 Last Revised:Apr. 2024 Page: 57 ...
Page 65
PDO consumer. If ‘L’ is less than 'n', the PDO message will not be disposed by the PDO consumer, and an Emergency message with error code 8210h will be transmitted to the PDO producer. The PDO communication set is shown as follows. PM-4324A User’s Manual v1.03 Last Revised:Apr. 2024 Page: 65 ...
Page 69
The value of this bit will be alternatively changed between two consecutive responses from the NMT slave. After the Node Guarding protocol becomes active, the value of the toggle-bit of the first response will be 0. PM-4324A User’s Manual v1.03 Last Revised:Apr. 2024 Page: 69 ...
Page 84
The users can write the object the value 65766173h to object with index 1010h and subindex 1 to save the application setting, or write the value 64616F6Ch to object with index 1011h and subindex 1 and reboot the module to load the factory default. PM-4324A User’s Manual v1.03 Last Revised:Apr. 2024 Page: 84 ...
Page 85
Q1. Can we use the other 5A CT’s (like 600/5) to directly connect to the input current terminals of PM-4324A series? No, because the input current is only mA size on PM-4324A series,definitely not to directly use other 5A CT’s to connect and apply (like100/5…) ,It could causes the fetal damages.
Page 86
Q9. Regarding to the split type clip-on CT’s, if the wire is not long enough? Φ10, Φ16, Φ24, Φ36 split type CT,the standard length is 4M. For special length, please contact ICP DAS. PM-4324A User’s Manual v1.03 Last Revised:Apr. 2024 Page: 86 ...
Page 87
For example the target is to measure maximum 800A current. We can measure big CT output and set a CT Ratio. Note: A. Primary CT accuracy will influence the measurement. B. Even primary CT output current max is 5A, please don’t wire to PM-4324A and PM-4324AP directly. PM-4324A User’s Manual v1.03 Last Revised:Apr. 2024 Page: 87 ...
Page 88
Q11. Can I use CT's that I currently own with PM-4324A Power Meter? You can use CT's that you currently own with PM-4324AP (without CTs) Power Meter. The CT inputs of the PM-4324AP can handle a maximum of 333mV(Rogowski coils are not supported) of AC current.
Page 89
1.73. An example, on a 380 volt wye system, line to line voltage is 380 volts and line to ground voltage is 380/1.73 = 220 volts PM-4324A User’s Manual v1.03 Last Revised:Apr. 2024 Page: 89 ...