3. Choose one of the following based on the number of posts the jars have:
•
If the jar has more than one set of posts, attach the black and red clamps or probes
to the next set of posts on the jar.
•
If the jar has one set of posts, test the jar connected to the jar you just tested.
Follow the steps in "Attaching the cable to jar posts."
4. Repeat the steps in "Attaching the cable to jar posts" and "Attaching the cable to a strap"
until you are finished testing the string.
5. Refer to "Chapter 4: Test Results" to view test results or "Retesting jar posts or straps" to
retest the set of jar posts or straps.
Retesting jar posts or straps
Introduction
You can retest jar posts or straps if you get test results you think are not accurate. Factors such as
operating conditions, site conditions, manufacturer changes, can vary test results. If you accept
results under these conditions, your maintenance routine might not have an accurate history.
You can retest a set of jar posts or straps right after you test them or you can test the rest of the
string before you retest certain jar posts or straps.
Retesting after testing the jar post or strap
To retest a set of jar posts or a strap just after you test it, press
displayed again for that jar post or strap.
If you are still connected to the jar and in
Retesting after testing the string
To retest a set of jar posts or a strap after you test the entire string:
1. Remove the probes or clamps from the set of jar posts or strap.
2. Press and hold the
AUTO START
button to turn on the analyzer.
MENU
RETEST
, the retest will begin immediately.
30
. The test results are