6.4.2 - Selection table of minimum and maximum wire sections for connection to BW05 units
400 V-3 ph-50 Hz
BW05
Minimum wire
section (mm
020
1x 6
025
1x 6
030
1x 6
040
1x 6
045
1x 6
060
1x 10
070
1x 10
080
1x 16
090
1x 16
110
1x 25
120
1x 25
135
1x 35
150
1x 35
160
1x 35
185
1x 50
210
1x 70
245
1x 70
275
1x 70
300
1x 95
S
Power supply wire section (see diagram in chapter 'Electrical connection').
VUGFB102
2
)
Wire type
XLPE Cu
XLPE Cu
XLPE Cu
XLPE Cu
XLPE Cu
XLPE Cu
XLPE Cu
XLPE Cu
XLPE Cu
XLPE Cu
XLPE Cu
XLPE Cu
XLPE Cu
XLPE Cu
XLPE Cu
XLPE Cu
XLPE Cu
XLPE Cu
XLPE Cu
Maximum wire
L (m)
section (mm
85
1x16
80
1x16
80
1x16
75
1x16
75
1x16
90
1x25
90
1x35
110
1x35
108
1x50
135
1x70
130
1x70
145
1x95
145
1x95
142
1x120
162
1x120
175
1x120
170
1x150
168
1x150
180
1x185
2
)
Wire type
PVC Al
PVC Al
PVC Al
PVC Al
PVC Al
PVC Al
PVC Al
PVC Al
PVC Al
PVC Al
PVC Al
PVC Al
PVC Al
PVC Al
XLPE Al
XLPE Al
XLPE Al
XLPE Al
XLPE Al
L (m)
160
155
150
145
145
165
185
185
215
230
230
250
250
260
205
205
210
210
220
19