Variable Flow Evaporator; Evaporator Flow Rate (L/S); Condenser Water Flow Rate (L/S); Minimum Chilled Water Loop Volume - Danfoss BW05 Installation, Operation And Maintenance Instructions

Brine water heat pump with integrated hydronic modules
Table of Contents

Advertisement

5.6 - Evaporator flow rate (l/s)
BW05
Minimum
Maximum flow rate*
flow rate
Single pump
020
0.3
1.7
025
0.4
2.5
030
0.5
2.5
040
0.7
3.4
045
0.8
3.8
060
0.9
5.7
070
1.2
6.2
080
1.4
6.4
090
1.5
6.6
110
1.8
8.3
120
2.2
8.5
135
2.4
8.8
150
2.7
9.0
160
2.7
14.2
185
3.1
14.5
210
3.8
17.4
245
4.4
17.4
275
5.0
18.1
300
5.5
18.1
*
Maximum flow rate for an available pressure of 50 kPa (unit with hydronic module)
**
Maximum flow rate for a pressure drop of 100 kPa in the plate heat exchanger (unit
without hydronic module)
5.7 - Condenser water flow rate (l/s)
BW05
Minimum flow rate*
Nom. condenser
at min. condenser
flow rate at Eurovent
capacity
conditions
t = 10 K
020
0.5
1.2
025
0.7
1.5
030
0.8
1.7
040
1.0
2.3
045
1.2
2.7
060
1.4
3.3
070
1.8
4.1
080
2.1
4.7
090
2.3
5.4
110
2.8
6.4
120
3.3
7.3
135
3.6
8.3
150
4.0
9.1
160
4.2
9.4
185
4.7
10.8
210
5.7
12.7
245
6.5
14.5
275
7.3
16.6
300
8.0
18.2
*
The minimum flow rate given is for units without hydronic module that have a
fixed condenser flow rate.
Units with a hydronic module have a variable flow rate and no minimum fixed flow
rate.
The minimum flow rate is optimised by unit control in parallel with the drycooler
fan stages for all operating conditions, especially at low outdoor temperature and
low load conditions.
**
The maximum flow rate given is for units without hydronic module that have a
fixed condenser flow rate.
Units with a hydronic module have a variable flow rate.
The maximum flow rate is optimised by unit control at all operating conditions,
based on pump capacity, system pressure losses and outdoor temperature.

5.8 - Minimum chilled water loop volume

Whichever the system, the water loop minimum capacity is
given by the formula:
Capacity = Cap (kW) x N Liters
Where Cap is the nominal system cooling capacity (kW) at
the nominal operating conditions of the installation.
This volume is necessary for stable operation and accurate
temperature control.
Application
Air conditioning
BW05 020-045
BW05 060-300
VUGFB102
Maximum
Dual pump
flow rate**
-
1.7
-
3.1
-
3.1
-
3.7
-
4.7
5.6
5.9
6.1
7.3
6.2
8.0
6.3
8.4
11.7
10.3
12.4
11.4
13.1
12.8
13.7
14.3
14.2
15.9
14.5
17.0
22.0
24.0
22.0
24.0
23.3
29.1
23.3
29.1
Maximum flow rate**
at max. condenser
capacity
t = 5 K
1.4
1.8
2.0
2.7
3.1
3.8
4.8
5.5
6.2
7.4
8.5
9.5
10.3
10.9
12.5
14.6
16.8
19.0
20.5
N
3.5
2.5
Industrial process applications
Certain industrial processes may require high leaving water
stability. In these cases the values above must be increased.
It may be necessary to add a buffer water tank to the circuit in
order to achieve the required volume. The tank must itself be
internally baffled in order to ensure proper mixing of the
liquid (water or brine). Refer to the examples below.
Bad
Bad
5.9 - Maximum water loop volume (evaporator and
condenser side)
Units with hydronic module incorporate an expansion tank
sized for the maximum water loop volume.
The table below gives the maximum water loop volume (in
litres) for pure water or ethylene glycol with various con-
centrations.
BW05
020-045
Pure water
673
10% ethylene glycol
487
20% ethylene glycol
358
35% ethylene glycol
290

5.10 - Minimum hot water loop volume

The condenser water loop volume has no impact on the chiller
operation. For heat pump operation (unit control based on the
hot-water temperature) the minimum condenser water loop
volume must be calculated in accordance with the method
used for the evaporator loop, replacing the cooling capacity
with the heating capacity.
Good
Good
060-080
090-150
160-210
245-300
1000
2080
2900
4162
730
1525
2135
3053
540
1120
1570
2236
430
910
1260
1800
15

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BW05 and is the answer not in the manual?

Table of Contents