Main circuit
Terminal
AC power supply input
R/L1, S/L2, T/L3
Inverter output
U/T1, V/T2, W/T3
DC reactor connection
+2, +1
DC power supply input
+1, –
Grounding
Control circuit
Type
No.
Multi-function input selection 1
S1
Multi-function input selection 2
S2
Multi-function input selection 3
S3
Multi-function input selection 4
S4
Multi-function input selection 5
S5
Multi-function input selection
SC
common
Power supply terminal for
FS
frequency setting
Speed frequency reference
FR
Frequency reference common
FC
NO contact output
MA
NC contact output
MB
Contact output common
MC
Analog monitor output
AM
Analog monitor common
AC
Varispeed J7
Name
Main circuit power supply input (Use R/L1 and S/L2 for single-phase power supply inverter.
Do not use T/L3 of the models less than 0.75kW for other usage, such as a junction terminal.)
For inverter output
Remove the short bar between +2 and +1 when connecting DC reactor (option)
For power supply input (+1: positive electrode; – : negative electrode)*
For grounding (grounding should conform to the local grounding code.)
Signal name
Factory setting: runs when CLOSED, stops when OPEN.
Factory setting: runs when CLOSED, stops when OPEN.
Factory setting: "fault reset"
Factory setting: "external fault (NO contact)"
Factory setting: "multi-step speed reference 1"
Common for control signal
+12V (allowable current: 20 mA max.)
0 to +10 VDC (20 k ) or 4 to 20 mA (250 ), 0 to 20 mA (250 ) (resolution 1/1000)
0 V
Factory setting: "running"
Factory setting: "output frequency" 0 to +10 V output
0 V
Function (signal level)
Function
Signal level
24VDC, 8mA
photocoupler
isolation
Contact capacity
250 VAC, 1A or less
30 VDC, 1A or less
0 to 10 V 2 mA or less
Resolution: 8bits
359