Nominal Input Voltage
Item
Nominal Input Current
Efficiency (400 VAC FULL LOAD)
Voltage range
Frequency
Current (max.)
(Vin = Range min., Pmax)
Power factor (400 VAC FULL
LOAD)
Input
Leakage current (max.)
Inrush current (max.)
(Pmax)
EMI filter
Line fuses
Voltage adjustment range
Tolerance adjustment
accuracy
Ripple & noise (Pmax.)
Load variation influence
Input variation influence
Temperature variation
influence
Output
Startup time (max.)
Hold time (min.)
(Vin = 400 VAC)
Protection
Parallel operation
Serial operation
Indicator
Heat radiation
Ambient temperature
Temperature power derating
Storage temperature
Ambient humidity
Dielectric strength
Insulation resistance
Others
Vibration resistance
Shock resistance
EMC
Approval standards
(AC and DC input)
Life expectancy
MTBF *2
Weight
*1) UL approval up to 600 VDC
*2) MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device failures,
and indicates reliability of devices.
2
5 A
86%
90%
340 to 576 V 3AC resp. 480 to 810 VDC
50 to 60 Hz
0.5A
1A
0.66
0.66
<3.5mA
<3.5mA
< 30A @ Vin max.
< 30A @ Vin max.
2×10 mH
2×27 mH
T2A
T3.15A
21.6 to 28.0 VDC min.
1%
100 mV max. (p.p. 0-20 MHz)
±0.5% max.
±0.25% max.
Less than 0.05%/°C
1.3 s
1.3 s
15 ms
15 ms
- Short circuit protection continuative
- Over load protection
- Over voltage protection
Yes (for two units)
Yes (for two units)
Yes (Green LED)
Natural air cooling
-10 to 70°C (de-rating: 5%/°C for 60 to 70°C)
60 to 70°C see diagram
-40 to 85°C
10 to 90% noncondensing
2.5 kVAC Input-PE (for 1 sec.; routine test)
3 kVAC Input-Output on isolation components (transformers) (for 1 sec.; high-pot routine test)
1 kVAC Output-PE (for 1 sec.; routine test).
500 Mohm min at 500 VDC, Output - P.E.
10 to 55 Hz, 0.375 mm single amplitude for 2 h each in X, Y and Z directions
10 to 150 Hz, 0.35 mm single amplitude for 80 min each in-X, Y and Z directions
150 m/s², 3 times each in ±X, ±Y, ±Z directions
EN55011 (EN55022) EN61000-3-2, EN61000-4-2, EN61000-4-3,EN61000-4-4,EN61000-4-5,
EN61000-4-6,EN61000-4-8,EN61000-4-11, EN61204-3
IEC60950-1, EN60950-1 UL60950-1, CSA 22.2 No. 60950-1, UL508 Listed *1, EN50178,
EN60204
10 years (Vin=400-500 VAC 50% of rated output current Ta=40°C)
> 300.000hrs
0.71 kg
0.91 kg
F: 400 to 500 VAC
10 A
20 A
91%
1.5A
0.86
<3.5mA
< 40A @ Vin max.
2×6.8 mH
T4A
1.3 s
15 ms
1.8 kg
S8VT
40 A
91%
3A
0.86
<3.5mA
< 30A @ Vin max.
2×2.2 mH
T6.3A
1.3 s
15 ms
3.3 kg

Advertisement

loading

This manual is also suitable for:

S8vt-f12024eS8vt-f24024eS8vt-f48024eS8vt-f96024e