Applicable Wires - Omron PYF S Datasheet

Screwless clamp terminal socket

Advertisement

■ Applicable Wires

Applicable Wire Sizes
0.2 to 1.5 mm
2
, AWG24 to AWG16
Applicable Wire Type
Solid wires, stranded wires, flexible wires, or wires with ferules can
be used.
(See note 1.) < 2.2 ≤ Diameter D (mm) ≤ 3.2 (3.5: see note 2.)
Conductor diameter d (mm) or length of sides a and b (mm) ≤ 1.9
Wires with Ferules
Examples of Applicable Wires (Confirmed Using Catalog Information)
Type of wire
Equipment wire 2491X
BS6004
Switchgear BS6231
Switchgear BS6231
Tri-rated control and switchgear
Conduit
UL1007
UL1015
UL1061
UL1430
■ Wiring
Use wires of the applicable sizes specified above. The length of the
exposed conductor should be 8 to 9 mm.
8.5 ±0.5 mm
Fig. 1 Exposed Conductor Length
Use the following wiring procedure.
1. Insert the specified screwdriver into the release hole located
beside the wire connection hole where the wire is to be inserted.
Wire connection holes
Release holes
Fig. 2 Wire Connection Holes and Release Holes
Wire connection hole
Release hole
Fig. 3 Section A-A of Fig. 2
4
Screwless Clamp Terminal Socket
Conductor type
Flexible
Solid
0.5 mm
Solid
Flexible
Flexible
Stranded
Flexible
18AWG
Flexible
Flexible
18AWG
Flexible
18AWG
A
A
Insert
Screwdriver
PYF@@S
Note: 1. If the outer diameter D of the wire is less than 2.2 mm and
the exposed conductor length is less than 8 mm potentially
bad connection might occur in case wire is pushed to far in-
side. Please see following drawing.
2. If the outer diameter D of the wire exceeds 3.2 mm, it might
be difficult to use double wiring.
See note 1, above.
Recommended wire sizes
0.5, 0.75, 1.0 mm
2
1.0 mm
0.5, 0.75 mm
0.5, 0.75, 1.0, 1.5 mm
1.5 mm
16AWG
18AWG, 16AWG
16AWG
2. Insert the exposed conductor into the wire connection hole.
3. Pull out the screwdriver.
See note 2, above.
2
1.5 mm
2
1.5 mm
2
1.0 mm
2
2
Insert
2
2
2
Pull out