Ratings (at an Ambient Temperature of 25 C)
Input
Rated voltage
Operating voltage
5 to 24 VDC
4 to 30 VDC
100 to 240 VAC
75 to 264 VAC
*G3NH converts the input current into a constant current.
Output
Model
G3NH-2075B
100 to 240 VAC
G3NH-4075B
180 to 440 VAC
G3NH-2150B
100 to 240 VAC
G3NH-4150B
180 to 440 VAC
Note: The load current varies depending on the ambient temperature. Refer to Load Current vs. Ambient Temperature under Engineering Data for
details.
Characteristics
Item
Operate time
Release time
Output ON voltage drop
Leakage current
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Weight
(Input current)
5 mA max.*
41 k
Rated load voltage
G3NH-2075B
1/2 of load power source cycle + 1 ms max. (DC input)
3/2 of load power source cycle + 1 ms max. (AC input)
1/2 of load power source cycle + 1 ms max. (DC input)
3/2 of load power source cycle + 1 ms max. (AC input)
1.6 V (RMS) max.
30 mA max.
(at 200 VAC)
100 M
min. (at 500 VDC)
2,500 VAC, 50/60 Hz for 1 min
Destruction: 10 to 55 to 10 Hz, 0.375-mm single amplitude
2
Destruction: 500 m/s
Operating: –30 C to 80 C (with no icing or condensation)
Storage:
–30 C to 100 C (with no icing or condensation)
Operating: 45% to 85%
Approx. 1.8 kg
Impedance
Must operate voltage
4 VDC max.
20%
75 VAC max.
Applicable load
Load voltage range
75 to 264 VAC
150 to 484 VAC
75 to 264 VAC
150 to 484 VAC
G3NH-4075B
60 mA max.
30 mA max.
(at 400 VAC)
(at 200 VAC)
Approx. 3.0 kg
Voltage level
Must release voltage
1 VDC min.
20 VAC min.
Load current
(See note.)
1 to 75 A
800 A
(60 Hz, 1 cycle)
1 to 150 A
1,800 A
(60 Hz, 1 cycle)
G3NH-2150B
G3NH-4150B
60 mA max.
(at 400 VAC)
G3NH
Solid State Relays
Inrush current
199