Specifications - Omron E5CN-H Datasheet

Advanced digital temperature controller (48 x 48 mm)
Hide thumbs Also See for E5CN-H:
Table of Contents

Advertisement

Specifications

Ratings
Power supply voltage
Operating voltage range
Power consumption
Sensor input
Input impedance
Control method
Relay output
Voltage output
(for driving SSR)
Control
output
Current output
Linear voltage
output
Number of outputs 2
Auxi-
liary
Output
output
specifications
Number of inputs
Event
External
input
contact input
specifications
Number of
operations
Logic
Operations
opera-
tions
Outputs
Work bit assign-
ments
Number of outputs 1 max.
Transfer
Output
outputs
specifications
RSP input
Setting method
Indication method
Bank switching
Other functions
Ambient operating tempera-
ture
Ambient operating humidity
Storage temperature
✽ For models with current outputs, control output 1 can be used as a transfer output.
4
Advanced Digital Temperature Controller
No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
100 to 240 VAC: 8.5 VA (max.) (E5CN-HR2 at 100 VAC: 3.0 VA)
24 VAC/VDC: 5.5 VA (24 VAC)/3.5 W (24 VDC) (max.) (E5CN-HR2D at 24 VAC: 2.7 VA)
Any of the following can be selected (i.e., fully universal input).
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.)
ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA
Output voltage: 12 VDC ±15% (PNP), max. load current: 21 mA, with short-circuit protection circuit
4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000 ✽
0 to 10 VDC (load: 1 kΩ min.), Resolution: Approx. 10,000
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable
load: 5 V, 10 mA
2
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
8 max. (Combinations can be made using work bits.)
• Logic operation: Any of the following four patterns can be selected. The input status may be inverted.
(A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D (A, B,
C, and D are four inputs.)
• Delay:
ON delay or OFF delay for the results of the logic operation given above.
Setting time: 0 to 9999 s or 0 to 9999 min
• Output inversion: Possible
One work bit per operation
Any of the following can be assigned to up to eight work bits (logic operation results): Event input operations,
auxiliary outputs, or control outputs.
Current output: 4 to 20 mA DC, Load: 600 Ω max., Resolution at 4 to 20 mA: Approx. 10,000
Not supported
Digital setting using front panel keys
11-segment digital display and individual indicators (7-segments display emulation also possible)
Character height: PV: 11 mm, SV: 6.5 mm
Supported (number of banks: 8)
Local SP, alarm settings, PID sets (PID constants, MV upper limit, MV lower limit, etc.)
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout
detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop,
protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, PV/SV
status display, logic operations, automatic cooling coefficient adjustment
−10 to 55°C (with no condensation or icing), for 3-year warranty: −10 to 50°C
25% to 85%
−25 to 65°C (with no condensation or icing)
E5CN-H

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents