Setting Output Parameters; Control Period; Direct Operation (Cool) / Reverse Operation (Heat) - Omron E5AR - MANUAL 2 User Manual

Digital controller
Hide thumbs Also See for E5AR - MANUAL 2:
Table of Contents

Advertisement

Section 4 Settings Required for Basic Control

4.7 Setting output parameters

■ Control period

cp
20.0
l.adj
c-cp
20.0
l.adj

■ Direct operation (cool) / Reverse operation (heat)

25.0
0.0
0.0
ore
or-r
l.1
4-14
• The output period (control period) must be set. A shorter control
period improves controllability, however, when a relay is used to
control a heater, a control period of at least 20 seconds is recom-
mended to preserve product life. After setting the control period in
the initial settings, readjust it as necessary using trial runs.
• Set the values in "cp: Control period (heat)" and "c-cp: Control
period (cool)". The default value is "20.0 sec".
• "Control period (cool)" can only be used in heating/cooling control.
• When each channel is used independently for control, set the control
period separately for each channel.
• Control that increases the MV as the PV increases is called direct
operation (cool), and control that increases the MV as the PV
decreases is called reverse operation (heat).
MV
100%
0%
Temperature is low
Temperature is high
Set value (in general)
Direct action
• For example, when the present value (PV) is less than the set point
(SP) during heating control, the manipulated valuable (MV) is
increased in proportion to the difference between the PV and SP. As
such, heating control is "reverse operation". Cooling control, which
does the opposite, is "direct operation".
• Set "Direct / reverse operation" to "or-r: Reverse operation" or
"or-d: Direct operation". The initial setting is "Reverse operation
(heat)".
• When each channel is used independently for control, set the direct /
reverse operation separately for each channel.
MV
100%
0%
Temperature is low
Temperature is high
Set value (in general)
Reverse action

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5er

Table of Contents