Section 8 Setting data
Input 1 input type
Input 2 input type
Input 3 input type
Input 4 input type
Function
Setting
Reference
Reference
8-36
i1-t
i2-t
i3-t
i4-t
• These settings are used to set the sensor type.
• If these settings are changed, the SP limit settings are returned to
the initial settings. In this case, reset the "SP upper limit" and "SP
lower limit" settings as necessary.
• Refer to the following table to configure the settings. Initial settings
are shaded.
Setting
Input
value
type
0
Pt100(1)
-200.0 to 850.0
1
Pt100(2) -150.00 to 150.00 -199.99 to 300.00
2
K(1)
-200.0 to 1300.0
3
K(2)
-20.0 to 500.0
4
J(1)
-100.0 to 850.0
5
J(2)
-20.0 to 400.0
6
T
-200.0 to 400.0
7
E
0.0 to 600.0
8
L
-100.0 to 850.0
9
U
-200.0 to 400.0
10
N
-200.0 to 1300.0
11
R
0.0 to 1700.0
12
S
0.0 to 1700.0
13
B
100.0 to 1800.0
14
W
0.0 to 2300.0
15
Depends on scaling
4 to 20 mA
One of the following ranges appears
16
0 to 20 mA
depending on the scaling:
17
1 to 5V
18
0 to 5V
19
0 to 10V
Set the input type switch of each input to match the "Input type" setting
of the corresponding input.
The initial setting is "2". ("TC.PT")
● Related setting data
"Input
temperature units" (Input initial setting level) (P.8-37)
"SP upper limit", "SP lower limit" (Control initial setting level) (P.8-43)
Setting range
(°C)
(°F)
-300.0 to 1500.0
-300.0 to 2300.0
0.0 to 900.0
-100.0 to 1500.0
0.0 to 750.0
-300.0 to 700.0
0.0 to 1100.0
-100.0 to 1500.0
-300.0 to 700.0
-300.0 to 2300.0
0.0 to 3000.0
0.0 to 3000.0
300.0 to 3200.0
0.0 to 4100.0
-19999 to 99999
-1999.9 to 9999.9
-199.99 to 999.99
-19.999 to 99.999
-1.9999 to 9.9999
l.0
Input type
switch
TC.PT
TC.PT
IN1
TYPE
ANALOG
ANALOG
TC.PT
IN1
TYPE
ANALOG