Monitor Value / Setting Data Compound Read Store (Write) - Omron E5AR - MANUAL 2 User Manual

Digital controller
Hide thumbs Also See for E5AR - MANUAL 2:
Table of Contents

Advertisement

Response

■ Monitor value / setting data compound read store (write)

Command
Response
6.9 Commands and responses (Communication/CompoWay/F)
To store setting data of Operation, Adjustment, Adjustment 2, Bank
setting, PID setting, or Approximation setting levels in non-volatile
memory, select "Backup" with the "Write mode" command. If not set to
"Backup", the setting data will not remain in memory when the power
is turned off. For more information on the above levels, see "4.1
Setting levels and key operation" (P.4-2).
MRC
SRC
Response code
"01"
"13"
"0000"
Response codes: The above indicates a normal end. For the response
codes, see "6.6 Writing to the variable area" (P.6-10).
MRC
SRC Variable type
Read address
"01"
"11"
Variable
Address
type
"0000"
"0100"
"C4"
"0200"
"0300"
"0000" to "007F"
"0100" to "017F"
"C5" to "CB"
"0200" to "027F"
"0300" to "037F"
"0000" to "0039"
"0100" to "0139"
"C5" to "D3"
"0200" to "0239"
"0300" to "0339"
This command is used to store the addresses of multiple monitor
values or setting data that you wish to read.
The stored monitor values or setting data can be read by sending a
single "Monitor value / setting data compound store read" command.
Up to 20 items can be stored, even if the addresses are not
contiguous.
To specify the variable type or address, see "Appendix Setting list"
(P.A-6). The upper limit of an address will vary depending on the
variable type.
This command can be used in both setting area 0 and setting area 1.
MRC
SRC
Response code
"01"
"11"
"0000"
Response codes: The above indicates a normal end. For the response
codes, see"6.5 Reading the variable area" (P.6-9).
Variable
Read address
Bit position
type
"00"
Variable type
Read address
Setting data
Ch
Explanation
1
2
Monitor values
3
4
1
2
Setting data of setting area 0
3
4
1
2
Setting data of setting area 1
3
4
Bit position
"00"
Bit position
"00"
6-19

Advertisement

Table of Contents
loading

This manual is also suitable for: