7. Press the key M to obtain the display at left.
bia5.1
8. Change the wiring as shown below.
5f165
l.cal
Short circuit
9. Wait until the count in Display 2 is sufficiently stable and then press the D
10. Press the key M to obtain the display at left. Note that this display will not
str.i1
no
l.cal
11. Turn off the power to quit calibration mode.
Open without connecting
STV
DMM
ZERO-CON
OUTPUT
INPUT
Disconnect the STV and enable the thermocouple in the cold junction
compensator. Make sure that the STV is disconnected at this time.
key. This tentatively saves the calibration data at this point.
appear if not all of the required data has been tentatively saved.
Press the U key. Display 2 will show "yes". Two seconds after the key is
released or when the M is pressed, the tentatively saved calibration data is
stored in non-volatile memory. If you do not wish to save the data in non-
volatile memory, press the M key instead of the U key.
• For a multi-point input type, connect as explained in step 2 and repeat
steps 5 to 10.
• If linear current output is selected, continue with the procedure explained
in "9.6 Output calibration" (P.9-12).
9.3 Thermocouple input calibration
Compensating wire of selected thermocouple
However, for thermocouple E, R, S, W, and B,
compensating wire of thermocouple K is used.