Program Control Functions - Omron E5AR-T Brochure

Programmable digital controller
Hide thumbs Also See for E5AR-T:

Advertisement

Ratings
CE marking
Supply voltage
UL certification
(See note 2.)
Operating voltage range
Power consumption
Sensor input (See note 3.)
Voltage (pulse) output
Control
Current output
output
Relay output
Auxiliary output
Potentiometer input
Contact
Event input
No-contact
Remote SP input
Transfer output
Control method
Setting method
Indication method
Other functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
Note 1. Do not use an inverter output as the power supply.
2. The supply voltage (i.e., 100 to 240 VAC or 24 VAC/VDC) depends on the model. Be sure to specify the required type when ordering.
3. The Controller is equipped with multiple sensor input. Temperature input or analog input can be selected with the input type setting switch.
There is basic insulation between power supply and input terminals, power supply and output terminals, and input and output terminals.

Program Control Functions

Number of programs (patterns)
Number of segments (steps)
Maximum number of segments
Segment setting method
Segment times
Number of groups
Alarm group number
specifications
Setting method
Reset operation
Startup operation
Number of groups
PID groups
Setting method
Alarm SP function
Segment operation
Program status
control
Program operation
Wait method
Wait operation
Wait width setting
Setting method
Number of outputs
Time signals
Number of ON/OFF operations
Setting method
Number of outputs
Segment outputs
Setting method
Program status output
PV start
Program startup
operation
Standby
Operation end operation
Number of event inputs
100 to 240 VAC, 50/60 Hz
100 to 120 VAC, 50/60 Hz
85% to 110% of rated supply voltage
22 VA max. (with maximum load)
Thermocouple: K, J, T, E, L, U, N, R, S, B, W
Platinum resistance thermometer: Pt100
Current input: 4 to 20 mA DC, 0 to 20 mA DC (including remote SP input)
Voltage input: 1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC (including remote SP input)
(Input impedance: 150 Ω for current input, approx. 1 MΩ for voltage input)
12 VDC, 40 mA max. with short-circuit protection circuit (E5AR-TQQE3MW-FLK and E5AR-TQQE3MWW-FLK: 21 mA max.)
0 to 20 mA DC, 4 to 20 mA DC; load: 500 Ω max. (including transfer output)
(Resolution: Approx. 54,000 for 0 to 20 mA DC; Approx. 43,000 for 4 to 20 mA DC)
Position-proportional control type (open, closed)
N.O., 250 VAC, 1 A (including inrush current)
Relay Output: N.O., 250 VAC, 1 A (resistive load)
Transistor Output: Maximum load voltage: 30 VDC; Maximum load current: 50 mA; Residual voltage: 1.5 V max.; Leakage current: 0.4 mA max.
100 Ω to 2.5 kΩ
Input ON: 1 kΩ max.; OFF: 100 kΩ min.
Input ON: Residual voltage of 1.5 V max.; OFF: Leakage current of 0.1 mA max.
Short-circuit: Approx. 4 mA
Refer to the information on sensor input.
Refer to the information on control output.
2-PID or ON/OFF control
Digital setting using front panel keys or setting using serial communications
7-segment digital display and single-lighting indicator
Character Height
E5AR: PV display: 12.8 mm; SV display: 7.7 mm; MV display: 7.7 mm, E5ER: PV display: 9.5 mm; SV display: 7.2 mm; MV display: 7.2 mm
Depends on model.
−10 to 55°C (with no icing or condensation)
For 3 years of assured use: −10 to 50°C (with no icing or condensation)
25% to 85%
−25 to 65°C (with no icing or condensation)
32 (with 8 segments/program)
32 (with 8 programs)
256
Time setting (Segment set with target value and time.)
Gradient setting (Segment set with target value, gradient, and time.)
0 h 0 min to 99 h 59 min
0 min 0 s to 99 min 59 s
0 min 00.0 s to 99 min 59.9 s
4
Set separately for each program.
Select either stopping control or fixed SP operation.
Select continuing, resetting, manual operation, run mode, or ramp back operation.
8
Set separately for each program (automatic PID group selection also supported).
Select from ramp SP and target SP.
Advance, hold, and back
Program repetitions and program links
Select from waiting at segment ends and always waiting.
Wait width upper limit and lower limit set separately for each program.
ON/OFF setting for each segment
6
3 each per output
Set separately for each program.
10
ON/OFF set for each segment.
Program end output (pulse width can be set)
Segment number output
Select from segment 1 target value, slope-priority PV start, and time-priority PV start.
Standby
Select from resetting, continuing control at final target value, and fixed SP control.
10 max.
24 VAC, 50/60 Hz; 24 VDC
24 VAC, 50/60 Hz; 24 VDC
15 VA/10 W max. (with maximum load)