Explicit Messages Specific to DeviceNet-compatible Digital Controllers
5-3-1

Reading General Status

Explicit
Read/
message
write
General
Read
Reads the DeviceNet-com-
Status
patible Controller's general
Read
status bits (8 bits). (Refer
to page 4-11).
5-3-2

Writing Maintenance Mode Data

Explicit
Read/
message
write
Mainte-
Save
Records the maintenance
nance
counter (PV of total ON/
Counter
RUN time for all Digital
Save
Controllers) in memory.
5-3-3

Setting and Monitoring the Digital Controller Channels

Explicit
Read/
message
write
Digital Con-
Read
Reads the monitor
troller
mode for maintenance
Channel
information of the Digi-
Mainte-
tal Controller channel
nance Infor-
(see note 1) specified
mation
by the Instance ID (1 to
Monitor
4).
Mode
Write
Writes the monitor
mode for maintenance
information of the Digi-
tal Controller channel
(see note 1) specified
by the Instance ID (1 to
4).
Set Value
Read
Reads the set value
for Unit
(monitor value) for the
Conduction
Unit conduction time or
Time or
total RUN time (unit: s)
Total RUN
of the Digital Controller
Time
channel (see note 1)
specified by the
Instance ID (1 to 4).
Write
Writes the set value
(monitor value) for the
Unit conduction time or
total RUN time (unit: s)
of the Digital Controller
channel (see note 1)
specified by the
Instance ID (1 to 4).
Function
Service
code
0E hex
Function
Service
code
16 hex
Function
Service
code
0E hex
10 hex
0E hex
10 hex
Command
Class
Instance
ID
ID
95 hex 01 hex
65 hex
Command
Class
Instance
ID
ID
95 hex 01 hex
75 hex
Command
Class
Instance
Attribute
ID
ID
ID
7A hex 01 to 04
65 hex
hex
7A hex 01 to 04
65 hex
hex
7A hex 01 to 04
68 hex
hex
7A hex 01 to 04
68 hex
hex
Section 5-3
Response
Attribute
Data
ID
size
---
1 byte
Response
Attribute
Data
ID
size
---
---
Response
Data size
1 byte
00 hex: Unit
conduction
time mode
01 hex: Total
RUN time
mode
1 byte
00 hex: Unit
conduction
time mode
01 hex:
Total RUN
time mode
4 bytes
00000000 to
FFFFFFFF
hex (0 to
4294967295)
4 bytes
00000000
to
FFFFFFFF
hex (0 to
429496729
5)
5-7